POTTER SL-1224 Series Selectable Candela Strobe Owner’s Manual

June 9, 2024
POTTER

**POTTER SL-1224 Series Selectable Candela Strobe Owner’s Manual

**

  • UL and c UL listed
  • 12 VDC with 15, 35 or 60 cd setting
  • 24 VDC with 15, 35, 60, 75, 95 or 110
  • 6 distinct candela settings
  • Candela selection view window
  • 15/75 ADA compliant on 60cd setting
  • Pre-wire back plate
  • Universal back plate mounting (single gang, double gang, octagon, or 4” square)
  • Single screw mounting
  • Indoor only
  • Low current draw

The SL-1224 Strobe Series provides a wide range of candela light output options in a single device. The candela settings include a 12 or 24 volt operation for the 15, 35 and 60 (75 on axis) candela settings and 24 volt operation for the 15, 35, 60, 75, 95 and 110 candela settings. The candela setting is displayed through the front window and is selectable using a drum wheel. The voltage input can be either regulated DC or full wave rectified (FWR) 12 volt or 24 volt with an operating range from 8 to 33V DC. The strobes can be synchronized using a control panel with the Potter (Amseco) sync protocol or a SMD10-3A sync module.

The SL-1224 utilizes a universal mounting plate that will mount on a single gang, double gang, octagon and 4” square electrical boxes. The back plate allows the installer to mount the plate and terminate the wire connections. The strobe attaches in a hinge fashion from the top and is secured by a single mounting screw. The strobe completely covers the mounting back plate, therefore it can be mounted before other trades work is completed and not affect the final look.

Installation

Note: Installation must comply in accordance with applicable standards.

Stock Number Model Number Description Color
4560060 SL-1224R Selectable strobe only Red
4560061 SL-1224W Selectable strobe only White

Wiring Diagram

WARNING

High voltage may be present inside the light assembly even though power is not connected. If access to the coponent board is required (removal or replacement), the capacitor must be discarged by touching a wire to both ends of the flashtube.
DO NOT attempt to touch or move the assembly until the capacitor has been discharged.

Dimensions : inches (mm)

Specifications

Light Output Max. RMS Operating Current (mA RMS)
Reg. 12 VDC Reg. 12 FWR
15cd 115
35cd 208
60/75cd 253
75cd NA
95cd NA
110cd NA

Note: All current draw shown is worst case.

Voltage 12/24V
UL Designation Regulated 12 DC/FWR
Operating Voltage Range 8 – 17.5V
Flash Rate 60 times/min.
Sync Module (SMD10-3A) NA
Operating Temperature Range 32°F to 120°F (0°C to 49°C)

Light output in precentage when measured from the following directions per UL 1971

Engineering Specifications

The installer shall provide and install the Potter SL-1224 selectable strobe. The strobe shall have six (6) candela settings. The candela settings shall be selectable using a drum roller and shall display the candela setting on the front of the device. The strobe shall operate at 12 or 24 VDC regulated or full wave rectified. The strobe shall have an operating range between 8 and 33 VDC. The strobes can be synchronized using a control panel with the Potter (Amseco) sync protocol or a SMD10-3A sync module.

The strobe shall utilize a mounting plate that allows the installer to pre- wire the mounting plate. The mounting plate shall be universal and mount on a single gang, double gang, octagon or 4 inch square box. The mounting plate shall be completely covered by the strobe and shall be secured by a single screw. The strobe shall be UL listed to standard 1638, General Signaling, and standard 1971, Signaling Devices for the Hearing Impaired. In addition, the strobes shall be cUL listed to CAN-ULC S526.