POTTER RA-6075R LCD Annunciator Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
RA-6075R LCD Annunciator
Owner’s Manual
Features
| Standby Current | 20 mA |
|---|---|
| Alarm Current | 25 mA |
| Operating Temperature | 0°C-49°C (32°F-120°F) 10%-93% @ 30°C (86°F) non- |
condensing humidity
Maximum Wire Length| 6500 FT
Maximum Annunciators| 31
Size (WxHxD)| 8” x 6-1/4” x 1-5/8”
Wire Gauge| 14 AWG-22 AWG
Description
The RA-6075R is a LCD remote annunciator for the PFC-6075R addressable
releasing fire control panel. The RA-6075R communicates using a RS-485
connection to the main panel providing common indication of Alarms,
Supervisory, Trouble and other system status and control functions.
The RA-6075R features a 16×2 LCD display with LED’s for Power, Alarm,
Supervisory, Trouble, and Silenced conditions. It also provides Release and
Pre-Release LED’s to indicate releasing status. It can be mounted on a single
gang electrical box or a two square electrical box. The annunciator is
enclosed in a sheet metal enclosure and has a Potter lock securing the keypad.
Installation
The RA-6075R is connected to the PFC-6075R using a four wire RS-485 connection. The connection is power limited and supervised. Up to thirty-one (31) RA-6075R LCD annunciators can be connected using Class B or Class A wiring. Class A wiring requires an optional CA-6075 Class A Expander.
NOTICE
Install in accordance with installation manual, #5403594.
Figure 1: RA-6075R Class B Wiring Example| Figure 2: RA-6075R Class A
Wiring Example
---|---
|
Address Settings
The RA-6075R address is set by dip switch S1 located on the back of the RA-
6075R. The address must be set in the range of 1 to 31 to be recognized by the
control panel.
Figure 3: RA-6075R Class A (back panel view)
Dip Switch Settings
Refer to the table below for dip switch settings per Annunciator Address.
| Annunciator Address | Dip Switch Settings |
|---|---|
| SW-I | SW-2 |
| I | On |
| 2 | Off |
| 3 | On |
| 4 | Off |
| 5 | On |
| 6 | Off |
| 7 | On |
| 8 | Off |
| 9 | On |
| 10 | Off |
| 11 | On |
| 12 | Off |
| 13 | On |
| 14 | Off |
| 15 | On |
| 16 | Off |
| 17 | On |
| 18 | Off |
| 19 | On |
| 20 | Off |
| 21 | On |
| 22 | Off |
| 23 | On |
| 24 | Off |
| 25 | On |
| 26 | Off |
| 27 | On |
| 28 | Off |
| 29 | On |
| 30 | Off |
| 31 | On |
Potter Electric Signal Company, LLC
St. Louis, MO
Cust Service: 866-956-1211
Tech Support: 866-240-1870
Canada: 888-882-1833
www.pottersignal.com
PRINTED IN USA
MFG. #5406080
REV B 9/11