Standby Current | 20 mA |
---|---|
Alarm Current | 25 mA |
Operating Temperature | 0°C-49°C (32°F-120°F) 10%-93% @ 30°C (86°F) non- |
condensing humidity
Maximum Wire Length| 6500 FT
Maximum Annunciators| 31
Size (WxHxD)| 8” x 6-1/4” x 1-5/8”
Wire Gauge| 14 AWG-22 AWG
Description
The RA-6075R is a LCD remote annunciator for the PFC-6075R addressable
releasing fire control panel. The RA-6075R communicates using a RS-485
connection to the main panel providing common indication of Alarms,
Supervisory, Trouble and other system status and control functions.
The RA-6075R features a 16×2 LCD display with LED’s for Power, Alarm,
Supervisory, Trouble, and Silenced conditions. It also provides Release and
Pre-Release LED’s to indicate releasing status. It can be mounted on a single
gang electrical box or a two square electrical box. The annunciator is
enclosed in a sheet metal enclosure and has a Potter lock securing the keypad.
Installation
The RA-6075R is connected to the PFC-6075R using a four wire RS-485 connection. The connection is power limited and supervised. Up to thirty-one (31) RA-6075R LCD annunciators can be connected using Class B or Class A wiring. Class A wiring requires an optional CA-6075 Class A Expander.
NOTICE
Install in accordance with installation manual, #5403594.
Figure 1: RA-6075R Class B Wiring Example| Figure 2: RA-6075R Class A
Wiring Example
---|---
|
Address Settings
The RA-6075R address is set by dip switch S1 located on the back of the RA-
6075R. The address must be set in the range of 1 to 31 to be recognized by the
control panel.
Figure 3: RA-6075R Class A (back panel view)
Dip Switch Settings
Refer to the table below for dip switch settings per Annunciator Address.
Annunciator Address | Dip Switch Settings |
---|---|
SW-I | SW-2 |
I | On |
2 | Off |
3 | On |
4 | Off |
5 | On |
6 | Off |
7 | On |
8 | Off |
9 | On |
10 | Off |
11 | On |
12 | Off |
13 | On |
14 | Off |
15 | On |
16 | Off |
17 | On |
18 | Off |
19 | On |
20 | Off |
21 | On |
22 | Off |
23 | On |
24 | Off |
25 | On |
26 | Off |
27 | On |
28 | Off |
29 | On |
30 | Off |
31 | On |
Potter Electric Signal Company, LLC
St. Louis, MO
Cust Service: 866-956-1211
Tech Support: 866-240-1870
Canada: 888-882-1833