POTTER CHS-24-WP Series Outdoor Colored Lens Horn Strobe Owner’s Manual

June 9, 2024
POTTER

CS/CHS-WP Series
Outdoor Colored Lens Strobes and
Horn/Strobes
Owner’s Manual 

7135-0328:0213
7135-0328:0212

Features

  • Fixed 75cd strobe
  • Available in surface-mount (standard) and Low Profile (LP) versions
  • WPBB/LP made of clear Lexan® – provides maximum visibility and reliability, allowing full 75cd output
  • Lens colors available in amber, blue, green, and red
  • Super-Slide® Bracket – Ease of supervision testing
  • Checkmate® – Instant voltage verification
  • Synchronize strobe and/or horn with AVSM module
  • Switch selection for high/low dBA
  • Switch for chime, whoop, mechanical, and 2400Hz tone
  • Input terminals accept 18 to 12 AWG
  • Switch for continuous or temporal 3 tone (not available on whoop)
  • Tamperproof re-entrant grill
  • 5 year warranty

Application

The CS/CHS-WP Series Outdoor Colored Lens Signals are wall mount, low profile strobes and horn/strobes that offer dependable audible and visual alarms for warning and emergency notification in outdoor locations. Applications include emergency communication, severe weather, emergency response and many more.

Description

The CS/CHS-WP Series Outdoor Colored Lens Signals are 24VDC units available in lens colors of amber, blue, green and red. The Series has a fixed 75 candela strobe. They have a minimal operating current and a minimum flash rate of 1Hz regardless of input voltage. The weatherproof enclosure is made of clear Lexan® which provides
maximum visibility and reliability for effective visible signaling, allowing full 75cd output. The strobes can be synced using a Gentex sync protocol or the AVSM Sync Module.
The Colored Lens Series is shipped with a die cast universal 4” mounting bracket which incorporates the popular Super-Slide® feature that allows the installer to easily pre-wire the system and test for supervision. The product also features a locking mechanism that secures the signal to the bracket without showing any screws. The Colored Lens Series also features the Checkmate® – Instant Voltage Verification Feature which allows the installer to check the voltage drop, current draw, and match against the blue print.
The CS/CHS-WP Series devices are available in two different versions. The standard version comes with a surface-mount back box (WPBB) to install directly on a wall. The Low Profile (LP) versions come with a low profile back box (WPLPBB) designed to be installed on a flushmounted electrical box.

Product Listings

  • ANSI/UL 464 and 1638
  • CSFM 7135-0328:0212 (CHS-WP Series)
  • CSFM 7135-0328:0213 (CS-WP Series)

Technical Specifications

Operating Voltage Nominal 24VDC (16-33VDC)
Operating Temperature -31°F – 150°F (-35° – 66°C)
Dimensions LP Version – 5.75″ H x 4.75″ W x 3.25″ D

Standard – 5.75″ H x 4.75″ W x 4.18″D
Wiring Connections| Terminals accept 18 – 12 AWG
Mounting| LP Version — Single gang, double gang, or 4″ square back box
Standard Version – Surface mount back box included
Shipping Weight| 2.05 lbs.
CS Series Outdoor Colored Lens Strobe, 75 Candela

Model Number| Stock Number| Lens Color| Body

Color

CS-24WAR-WP| 4890140| Amber| Red
CS-24WAW-WP| 4890141| Amber| Off-White
CS-24WBR-WP| 4890142| Blue| Red
CS-24WBW-WP| 4890143| Blue| Off-White
CS-24WGR-WP| 4890144| Green| Red
CS-24WGW-WP| 4890145| Green| Off-White
CS-24WRR-WP| 4890146| Red| Red
CS-24WRW-WP| 4890147| Red| Off-White
CSLP-24WAR-WP| 4890148| Amber| Red
CSLP-24WAW-WP| 4890149| Amber| Off-White
CSLP-24WBR-WP| 4890150| Blue| Red
CSLP-24WBW-WP| 4890151| Blue| Off-White
CSLP-24WGR-WP| 4890152| Green| Red
CSLP-24WGW-WP| 4890153| Green| Off-White
CSLP-24WRR-WP| 4890155| Red| Red
CSLP-24WRW-WP| 4890156| Red| Off-White

NOTE: Models with LP include the LP version enclosure.

UL Max Strobe Current Ratings (24VDC Regulated)

Candela| Amber Lens| Blue, Green, and Red Lens
75cd| 170mA| 164mA

For unfiltered FWR ratings, see installation manual.

Horn Decibel and Current Ratings

Horn Setting| Minimum dBA at 10’, Per UL 464 (HIGH)| Minimum dBA at 10’, Per UL 464 (LOW)| Regulated 24VDC Max. Operating Current, at High Setting (mA)
Temporal 3 2400Hz| 78| 71| 28
Temporal 3 Mechanical| 76| 70
| 25
Temporal 3 Chime| 70| 66| 15
Continuous 2400Hz| 81| 74| 28
Continuous Mechanical| 80| 72
| 25
Continuous Chime| 70| 66| 15
Whoop| 82| 69*| 56

*Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode).

CHS Series Colored Lens Strobe, 75 Candela

Model Number| Stock Number| Lens Color| Body Color| Reverberant dBA at 10’, per ANSI/UL 464| In Anechoic Room dBA at 10’
CHS-24AR-WP| 4890160| Amber| Red| 70-82| 100
CHS-24AW-WP| 4890161| Amber| Off-White| 70-82| 100
CHS-24BR-WP| 4890162| Blue| Red| 70-82| 100
CHS-24BW-WP| 4890163| Blue| Off-White| 70-82| 100
CHS-24GR-WP| 4890164| Green| Red| 70-82| 100
CHS-24GW-WP| 4890165| Green| Off-White| 70-82| 100
CHS-24RR-WP| 4890166| Red| Red| 70-82| 100
CHS-24RW-WP| 4890167| Red| Off-White| 70-82| 100
CHSLP-24AR-WP| 4890168| Amber| Red| 70-82| 100
CHSLP-24AW-WP| 4890169| Amber| Off-White| 70-82| 100
CHSLP-24BR-WP| 4890170| Blue| Red| 70-82| 100
CHSLP-24BW-WP| 4890171| Blue| Off-White| 70-82| 100
CHSLP-24GR-WP| 4890172| Green| Red| 70-82| 100
CHSLP-24GW-WP| 4890173| Green| Off-White| 70-82| 100
CHSLP-24RR-WP| 4890174| Red| Red| 70-82| 100
CHSLP-24RW-WP| 4890175| Red| Off-White| 70-82| 100

Tone Switch Locations

Tone Switch Position
3 4
Mechanical Temporal 3 ON
Mechanical – Continuous OFF
2400Hz – Temporal 3 ON
2400Hz – Continuous OFF
Chime – Temporal 3 ON
Chime – Continuous OFF
Whoop ON
Whoop OFF

NOTES:

  • Switch Positions 1 and 2 in the OFF position to select isolated horn and strobe power inputs
  • Switch Position 6 ON = HIGH dBA
  • Switch Position 6 OFF = LOW dBA

Super Slide® Mounting Bracket
Allows the installer to pre-wire the system, test for system supervision, remove the signal head until occupancy, switch out signals without changing mounting brackets and has locking edge connector for snap-in-place installation.

Mounting Outdoor Enclosure

Super Slide® Mounting Plate:
Mounts to WPBB Outdoor Enclosure

POTTER CHS-24-WP Series Outdoor Colored Lens Horn Strobe -
Switch1

POTTER CHS-24-WP Series Outdoor Colored Lens Horn Strobe -
Switch

Checkmate® Instant Voltage Verification
It is often necessary to confirm the voltage drop along the line of devices. The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically, this would be done at the end of the line to confirm design criteria. Most measurements will be taken using the S+ and S- locations although access is provided to other locations.
NOTE: Care should be taken to not short the test probes.
Super Slide® Mounting Plate:
Mounts to WLPBB Outdoor Enclosure

POTTER CHS-24-WP Series Outdoor Colored Lens Horn Strobe - Mounting
Plate

Wiring Diagrams

POTTER CHS-24-WP Series Outdoor Colored Lens Horn Strobe -
Diagrams

NOTES:

  • All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn.
  • FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936.

Architect and Engineering Specifications

The audible and/or visible signal shall be Potter Outdoor Colored Lens Commander Series or approved equal and shall be listed by Underwriters Laboratories Inc. per ANSI/UL 1638 and/or ANSI/UL 464. The notification appliance shall also be listed with the California State Fire Marshal (CSFM).
The notification appliance (combination audible/visible) shall produce a peak sound output of 100dBA or greater at as measured in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized.
The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2 Hz regardless of power input voltage. The appliance shall have an operating current of 112mA or less for the 75Cd strobe circuit. The appliance shall also be capable of meeting the candela requirements of the ADA (75cd).
The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current of full wave rectified power for 24 volt models.
The appliance shall be capable of testing supervision without disconnecting wires. Also the appliance shall be capable of mounting to a surface back box. The unit shall also be able to verify voltage at the unit without removing unit.
The appliance has extended temperature range of -31° to 150°F (-35° to 66° C). The appliance shall satisfy virtually all outdoor and severe environment applications. The WPBB enclosure is includes a gasket that must be inserted between the box and mounting bracket. There are drain holes in the back box to allow for drainage, the seal on the WPLPBB enclosure is not water tight. The WPLPBB enclosure includes a weather seal for mounting to wall and intended for use with universal electrical box. To allow for drainage, bottom edge of enclosure is not water tight.

Potter Electric Signal Company, LLC
St. Louis, MO
Tech Support:866-956-1211
Customer Service:866-572-3005 
www.pottersignal.com DESIGNING, MANUFACTURING, & DISTRIBUTING QUALITY SYSTEMS
firealarmresources.com

8830058 – REV B
1/15

Documents / Resources

| POTTER CHS-24-WP Series Outdoor Colored Lens Horn Strobe [pdf] Owner's Manual
CHS-24-WP Series Outdoor Colored Lens Horn Strobe, CHS-24-WP Series, Outdoor Colored Lens Horn Strobe, Colored Lens Horn Strobe, Lens Horn Strobe, Horn Strobe, Strobe
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals