POTTER PTS-B Plug Type Supervisory Switch Owner’s Manual

June 9, 2024
POTTER

POTTER PTS-B Plug Type Supervisory Switch

PTS-B PLUG TYPE SUPERVISORY SWITCH

Stock No. 1010095
U.S. Patent No. 4234879

UL and ULC Listed and FM Approved

  • Dimensions: 5.25″L x 2.63″W x 2″D 13.3cm L x 6.7cm W x 5.1cm D with Bracket 8″ L (20.3cm)
  • Weight: 2 lbs. (.91 kg.)
  • Enclosure: Cast Aluminum
  • Finish: Red Wrinkle Enamel
  • Tamper: Activated by Cover Removal
  • Electrical Ratings: 250 mA at 28VDC/AC
  • Cable: 2-wire, 18 Ga. Waterproof – Approx. 8′ long

GENERAL

The Model PTS-B is designed to supervise sprinkler system control valves. This unit is particularly useful for unusual conditions, such as non-rising stem valves.
Turning the valve wheel will pull the plug out of the receptacle. The plug cannot be reinserted after operation until the cover is removed with special key provided. Cover tamper is provided.

CONTACTS : SPST normally closed when plug is in recep-tacle. Contacts rated 250 mA 28 VDC/VAC.
The PTS-B is NOT available with normally open contacts.

INSTALLATION

  • The receptacle housing is mounted near the valve. With the valve in the full OPEN position, the approximate 8′ of water-proof wire provided, can be cut to the desired length and looped through the valve wheel and terminated in the plug.
  • This forms a normally closed single circuit loop when the plug is inserted into the receptacle.
  • The cover tamper switch can be series wired into this loop or can be wired into a separate normally closed protection circuit (see wiring diagrams).

POTTER-PTS-B-Plug-Type-Supervisory-Switch-FIG-1

WARNING
As Stipulated By Factory Mutual And Underwriters Laboratories
This unit is not intended or designed for ordinary use. It is a special application device to be used for unusual conditions such as non-rising stem gate valves where no other approved or listed method of protection is available or practical. As this unit does not meet NFPA codes and standards, requiring restoration signal when the valve is positioned to normal, special attention should be given by the responsible parties to assure that the proper operation of this device is maintained. This device should only be restored to normal when the valve is in the normal condition.

Potter Electric Signal Company
2081 Craig Road, St. Louis, MO, 63146-4161
Phone: 800-325-3936/Canada 888-882-1833
www.pottersignal.com
firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

POTTER User Manuals

Related Manuals