POTTER SB SERIES Smoke Detector Bases Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
SB SERIES
SMOKE DETECTOR BASES
Owner’s Manual
SB SERIES Smoke Detector Bases
UL and ULC Listed
Electrical: 24VDC – Polarized
Suitable for use with Potter PFC Series Controls
Mounting: 3 1/4” or 4” outlet box
Annunciator Output: 15mA at 24VDC
Alarm Current:
HSC-4R – 43mA @ 24 VDC – 4 WIRE BASE
SB – 46 – 46mA @ 24 VDC
SB – 81R – 81mA @ 24 VDC – RELAY BASE
SB – 93 – 93mA @ 24 VDC
HSB – 21 – 32mA @ 24 VDC
Service Use: National Fire Alarm Code NFPA-72
Application
The SB Series is a 6” polarized base with annunciator output featuring a current limiting resistor, and a blocking diode to enhance annunciator function. The SB Series Smoke Detector base is designed specifically foruse with the Potter Smoke Detector Models IS-24, PS-24 and PS-24H.
WARNING
These detectors will not sense fires which start where smoke does not reach
the detector.
Fires on other building levels, within walls, on roofs , in chimneys, or on
the other side of closed doors may not be detected.
Fires from explosions, improperly stored flammable liquids, escaping gas,
arson or fires resulting from inadequate fire protection practices may not be
detected.
Smoke detectors should be tested upon completion of installation and at least
semi-annually thereafter, in accordance with the section of “Inspections,
Tests, and Maintenance” in NFPA-72.
To Install the Detector: Insert the detector into the base, turn the detector
clockwise until it locks, then tighten the vandal resistant allen screw.
These detectors will not work without power. They must be properly connected
into the signal initiating device circuit of a fire control panel that is
listed as being compatible by Underwriters Laboratories, Inc.
CAUTION
These units must be installed and maintained in accordance with all
applicable NFPA standards, local codes and any authority having jurisdiction.
Please refer to NFPA-72 Standards for Automatic Fire Detectors for
installation guidelines, and testing procedures.
Terminal # | Designation |
---|---|
1 | Positive In |
2 | Positive Out |
3 | Negative Out |
4 | Negative In |
5 | Annunciator Out |
6 | Annunciator Out |
Ordering Information
Model# Stock# Description
SB-46 1430014 Smoke Base – 46mA draw @ 24vdc
SB-93 1430016 Smoke Base – 93mA draw @ 24vdc
SB-81R 1430015 Smoke Base W/Relay – 81mA draw
HSC-4R 1430013 Wire Smoke Base W/Relay-43mA draw Compatibility
All Potter release panels; Not for use with PFC3000, 5000, 9000 Series panels;
Check other panel manufacturer’s compatibility listings.
For use on all Potter PFC 3000, 5000 Series panels.
PFC9000 series with ZA9008 module added. Not for use on Potter release panels;
Check other panel manufacturer’s compatibility listings.
For use on Potter PFC 3000 and 5000 Series; Not for use on Potter release
panels
Check other panel manufacturer’s compatibility listings.
For use with any panel that can provide 24VDC 4-wire resettable power.
For additional 2-wire base compatibility, contact Potter Technical Support at
800-325-3936 or
tech@pottersignal.com.
Potter Electric Signal Co., LLC • St. Louis, MO
• Cust Service: 866-240-1870
Tech Support: 866-956-1211
• Canada 888-882-1833
• www.pottersignal.com
MKT. #8840008 – REV K 9/07