Features
- Industry leading 4 line by 40 Character LCD
- Common buttons for navigation
- Common LEDs for status indication
- 31 annunciator per panel
- Maximum wire length of 6,500 feet
- Available in 4 colors
- Product includes a 5 year warranty
Description
The RA-6500R is a LCD remote annunciator for various Potter fire control panels. The RA-6500R communicates using a RS-485 connection to the main panel providing common indication of Alarms, Supervisory, Trouble and other system status and control functions. The RA-6500R features a 4×40 LCD display with LED’s for Power, Alarm, Supervisory, Trouble, and Silenced conditions. It can be mounted on a single gang electrical box or a four square electrical box. The annunciator is enclosed in a sheet metal enclosure and has a Potter lock securing the keypad.
Technical Specifications
Standby Current | 20 mA |
---|---|
Alarm Current | 25 mA |
Operating Temperature | 0°C-49°C (32°F-120°F) |
Operating Humidity Range | 10%-93% @ 30°C (86°F) non condensing humidity |
Maximum Wire Length | 6500 ft. |
Maximum Annunciators | 31 |
Size (WxHxD) | 10″ x 7-7/8″ x 1-5/8″ |
Wire Gauge | 14 AWG-22 AWG |
Compatible Panels | WA Series |
AFC/ARC Series
PFC-4064
P-Series
PFC-6000 Series
*Legacy Product
Installation
The RA-6500R is connected to the PFC-6000 series fire control panels using a four wire RS-485 connection. The connection is power limited and supervised. Up to thirty-one (31) RA-6500R LCD annunciators can be connected using Class B or Class A wiring. Class A wiring requires an optional Class A Expander.
Address Settings
The RA-6500R address is set by dip switch S1 located on the back of the RA- 6500R. The address must be set in the range of 1 to 31 to be recognized by the control panel.
Dip Switch Settings
Refer to the table below for dip switch settings per Annunciator Address.
Annunciator Address | Dip Switch Settings |
---|---|
SW-1 | SW-2 |
1 | On |
2 | Off |
3 | On |
4 | Off |
5 | On |
6 | Off |
7 | On |
8 | Off |
9 | On |
10 | Off |
11 | On |
12 | Off |
13 | On |
14 | Off |
15 | On |
16 | Off |
Annunciator Ad dress | Dip Switch Settings |
--- | --- |
SW-1 | SW-2 |
17 | On |
18 | Off |
19 | On |
20 | Off |
21 | On |
22 | Off |
23 | On |
24 | Off |
25 | On |
26 | Off |
27 | On |
28 | Off |
29 | On |
30 | Off |
31 | On |
Ordering Information
Model | Description | Stock No. |
---|---|---|
RA-6500R | LCD Annunciator – RED | 3992661 |
RA-6500R | LCD Annunciator – BLACK | 3992747 |
RA-6500R | LCD Annunciator Flush – GRAY | 3992748 |
RA-6500R | LCD Annunciator Flush – LIGHT GRAY | 3992749 |
Potter Electric Signal Company, LLC
St. Louis, MO
Phone:800-325-3936
www.pottersignal.com
8830114 – REV B
04/18
firealarmresources.com
Documents / Resources
|
POTTER RA-6500R LCD
Annunciator
[pdf] Owner's Manual
RA-6500R LCD Annunciator, RA-6500R, LCD Annunciator, Annunciator
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>