POTTER SH-24H SERIES High Intensity Select-A-Strobe-Horn Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
SH-24H SERIES
HIGH INTENSITY
SELECT-A-STROBE/HORN®
SH-24H SERIES High Intensity Select-A-Strobe-Horn
- UL and cUL listed
- 24 VDC with 95, 110, 135, 150, 177 or 185 cd settings
- 6 distinct candela settings
- Candela selection view window
- 33 sound output settings
- Horn or chime sound output
- Pre-wire back plate
- Universal back plate mounting (single gang, double gang, octagon, or 4” square)
- Single screw mounting
- Wall mount
- Indoor only
- Low current draw
The SH-24H Select-A-Strobe/Horn™ Series provides a wide range of candela light
output options in a single device. The candela settings include a 24 volt DC
operation for the 95, 110, 135, 150, 177 or 185 setting. The candela setting
is displayed through the front window and is selectable using a drum wheel.
The horn settings include Temporal, Non-Temporal, March Time and a Chime
sound. The horn also has Low, Mid and High volume settings for each pattern
and tone. The tones include 2400 Hz, ElectroMechanical, Broadband and Chime.
The voltage input can be either regulated DC or full wave rectified (FWR) 24
volt operation with an operating range from 16 to 33 VDC.
The strobes can be synchronized using a control panel with the Potter (Amseco)
sync protocol or a SMD10-3A sync module.
The SH-24H utilizes a universal mounting plate that will mount on a single
gang, double gang, octagon and 4” square electrical boxes. The back plate
allows the installer to mount the plate and connect the wire connections. The
strobe attaches in a hinge fashion from the top and is secured by a single
mounting screw. The strobe completely covers the mounting back plate,
therefore it can be mounted before other trades work is completed and not
affect the final look.
Installation
CAUTION
A jumper plug is provided to test for correct wiring in the supervisory mode
only. Do not pass alarm current through the jumper.
Note: Installation must comply in accordance with applicable standards.
Ordering Information
Stock Number | Model Number | Description | Color |
---|---|---|---|
4560072 | SH-24HR | Selectable strobe/horn/chime | Red |
4560073 | SH-24HW | Selectable strobe/horn/chime | White |
Dimensions: inches (mm)
Light output in precentage when measured from the following directions per UL 1971.
WARNING
High voltage may be present inside the light assembly even though power is not
connected. If access to teh coponent board is required (removal or
replacement), the capacitor must be discarged by touching a wire to both ends
of the flashtube.
DO NOT attempt to touch or move the assembly until the capacitor has been
discharged.
Specifications
Light
Output| Max. RMS Operating Current (mA RMS)
---|---
Reg. 24 VDC| Reg. 24 FWR
95cd| 151| 201
IIOcd| 161| 215
I35cd| 178| 235
150cd| 190| 248
I77cd| 218| 283
185cd| 226| 291
Note: To determine total current draw, add desired strobe setting and horn selection. Refer to theinstallation instructions for further information.
Pattern
1 ON – Non-temporal
1 OFF – Temporal
Both 2 = OFF
1 and 2 ON = March Time
Horn Dipswitch
Tone
3 and 4 ON = 2400Hz
3 ON and 4 OFF = Electromechanical
3 and 4 OFF = Chime
3 OFF and 4 ON = Broadband
Volume
5 and 6 ON = High
5 ON and 6 OFF = Mid
5 and 6 OFF = Low
7 and 8 ON = Horn/strobe on 2 wires
7 and 8 OFF = Horn and strobe on 4 wires
Non-Temporal Horn Current
Pattern| Volume| Max. RMS Current
(mA RMS Current)| dBA Reverberant Ratings per
UL464 (dBA @ 10 ft.)| dBA Anechoic Ratings per
CAN/ULC 5525 (dBA ® 10 ft.)
---|---|---|---|---
Reg 24 VDC| Reg 24 FWR| Reg 24 VDC| Reg 24 VDC
2400 Hz| High| 87| 236| 87| 100
Mid| 28| 140| 82| 96
Low| 18| 77| 80| 92
Electro-Mechanical| High| 81| 231| 87| 100
Mid| 26| 127| 84| 97
Low| 16| 68| 80| 93
Broadband| High| 78| 261| 86| 102
Mid| 26| 112| 82| 98
Low| 16| 69| 79| 95
Chime| High| 21| 42| 70| 86
Mid| 8| 20| 62| 80
Low| | 18| 57| 75
Temporal Horn Current
Patter:.| Volume| Max. RMS Current
(mA RMS Current)| dBA Reverberant Ratings per
UL464 (dBA @ 10 ft.)| dBA Anechoic Ratings per CAN/ULC 5525 (dBA @ 10 ft.)
---|---|---|---|---
Reg 24 VDC| Reg 24 FWR| Reg 24 VDC| Reg 24 VDC
2400 Hz| High| 87| 288| 82| 100
Mid| 30| 181| 79| 96
Low| 18| 79| 75| 92
Eleciro-Mechanical| High| 80| 275| 82| 101
Mid| 27| 138| 80| 96
Low| 16| 74| 76| 93
Broadband| High| 80| 289| 82| 102
Mid| 26| 144| 78| 98
Low| 16| 61| 76| 95
Chime| High| 21| 49| 70| 86
Mid| 9| 21| 61| 79
Low| 8| 15| 55| 76
Wiring Diagram
Engineering Specifications The installer shall provide and install the Potter
SH-24H Select-AStrobe/Horn™. The strobe shall have six (6) candela settings.
The candela settings shall be selectable using a drum roller and shall display
the candela setting on the front of the device. The horn shall have 33
selectable settings configurable by dip switches. The sounder shall be capable
of ANSI Temporal Code 3, March Time and produce a chime output. The horn shall
have three distinct volume levels. The strobe/horn shall operate at 24 VDC
regulated or full wave rectified. The strobe/horn shall have an operating
range between 16 and 33 VDC. the strobes an by synchronized using a control
panel with the Potter sync protocol or the SMD10-3A sync module. The strobe
shall utilize a mounting plate that allows the installer to pre-wire the
mounting plate. The mounting plate shall be universal and mount on a single
gang, double gang, octagon or 4 inch square box. The mounting plate shall be
completely covered by the strobe and shall be secured by a single screw. The
strobe shall be UL listed to standard 1638, General Signaling, and standard
1971, Signaling Devices for the
Hearing Impaired. In addition, the strobes shall be cUL listed to CAN-
ULC S526. The horn shall be UL listed to standard 464, Audible
Signaling Devices.
Potter Electric Signal Company, LLC
St. Louis, MO
Tech Support: 866-956-1211 / Customer
Service: 866-572-3005
www.pottersignal.com
firealarmresources.com
References
- Fire Alarm Resources | Download fire alarm documents
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>