  • Designed to meet or exceed NFPA/ANSI Standards and ADA accessibility guidelines
  • UL Listed for fi re protective service
  • Field selectable taps from 2, 4, and 8 Watts
  • L Listed for wall or ceiling mount
  • Available in 25V RMS and 70.7V RMS
  • Screw terminals capacity up to AWG12
  • Frequency range 400 Hz – 4000 Hz
  • Two fi eld selectable settings: 15 or 30 cd
  • Polarized strobes with wide listed voltage ranges using fi ltered or unfi ltered FWR input voltage
  • Synchronization requires the SMD10-3A Sync Module

Amseco’s high quality fi re alarm speakers are designed to generate attention grabbing tones and voice commands for emergency signaling evacuation applications. These  highly effi cient speakers are available with fi eld selectable taps from 2 – 8 Watts. The speakers are available in two input voltage models, 25V RMS and 70.7V RMS and can  be installed on a standard 4” electrical back box with an extension ring. The SFH45-153075 Series features a new and exclusive select-a-strobe. The strobe utilized a unique  candela intensity fi eld selector switch for alternating the candela output from 15 to 30. The strobe housing is clearly labeled with “FIRE” lettering and is polarized for connecting to supervised fi re alarm circuits. The strobe is designed with a xenon fl ash tube and provides a candela intensity fi eld selector switch for maximum performance. They are available in red or white housing.
The strobe can be synchronized by using the SMD10-3A Sync Module to comply with NFPA recommendations concerning photosensitive epilepsy when installing two or  more visual appliances within the fi eld of view. The strobe signals are listed for indoor use, ceiling and wall mount, under UL 1971 Standard.

Ordering Information

Model Number| Stock
Number| Speaker Voltage (VAC)| Strobe Voltage (VDC)| Strobe Candela
(Selectable)| Selectable
Wattage| Flash Rate
(Per Minute)| Grille
Type| Grille
Color
---|---|---|---|---|---|---|---|---
SFH45-153075R-255| 4650000| 25| 24| 15 or 30| 2,4,8| 60| Square| Red
SFH45-153075W-25S| 4650010| 25| 24| 15 or 30| 2,4,8| 60| Square| White
SFH45-153075R-25R| 4650005| 25| 24| 15 or 30| 2,4,8| 60| Round| Red
SFH45-153075W-25R| 4650009| 25| 24| 15 or 30| 2,4,8| 60| Round| White
SFH45-153075R-70S| 4650008| 71.| 24| 15 or 30| 2,4,8| 60| Square| Red
SFH45-153075W-70S| 4650012| 71.| 24| 15 or 30| 2,4,8| 60| Square| White
SFH45-153075R-70R| 4650007| 71.| 24| 15 or 30| 2,4,8| 60| Round| Red
SFH45-153075W-70R| 4650011| 71.| 24| 15 or 30| 2,4,8| 60| Round| White

Engineering Specifi cations

The fi re alarm speaker shall be capable of reproducing alarm tones or voice commands on 25V RMS or 70.7V RMS. Speakers shall provide incremental tap settings of 2, 4,  or 8 Watts and shall be selected by means of a jumper wire. The speaker shall have a frequency range of 400 – 4000 Hz and shall have an operating temperature between 14°F  and 140°F. The speaker shall produce a UL sound pressure level at 10 feet up to 84dB. The speaker shall be approved for fi re alarm signaling use. The strobe shall be listed  under UL 1971 standard for signaling devices for the hearing impaired and shall be approved for fi re protective service. The candela ouput shall be fi eld selectable, having a dual setting of 15/75cd or 30/120cd output. The signaling strobe shall operate on 24V DC from a non-coded regulated DC supply or full-wave rectifi ed, unfi ltered supply. It shall be designed to produce one signal fl ash per second with continuously applied minimim voltage. The SFH45-153075 shall be capable of wall or ceiling mounting. The visual signaling devices are to be installed in all non-sleeping/corridor areas as per plans and specifi cations.
Dimensions: inches (mm)

POTTER SFH45-153075 High Wattage Fire Alarm Speaker Select-A-Strobe
Combination - Figure 1

Mounting

POTTER SFH45-153075 High Wattage Fire Alarm Speaker Select-A-Strobe
Combination - Figure 2

Wiring Diagram

POTTER SFH45-153075 High Wattage Fire Alarm Speaker Select-A-Strobe
Combination - Figure 3

Multiple Tap Setting
To select desired wattage (Fig. 1) using the change lead wire, set the desired output level (2, 4, and 8 Watt). * The unit is set at the factory to the 2 Watt position.

POTTER SFH45-153075 High Wattage Fire Alarm Speaker Select-A-Strobe
Combination - Figure 4

Multiple taps are provided for fi eld wattage selection.

WARNING
To avoid electric shock, do not attempt to install wires when power is on.

Rated Input Voltage (V RMS) 2W 70.7V
Input Power (Watts) 2W 4W
Impedance (Ohms) 310 156
Sound Pressure (dB/10ft) 90 93
Frequency Response (Hz) 400-4000
Low Frequency Cut-off (Hz) 200
Operating Temperature Range 32°F – 120°F (0°C – 49°C)
Strobe Light Maximum RMS Current (mA)
--- ---

Regulated 24V DC
(Typical)| Regulated 24V DC/FWR
(Typical)
I5cd| 115 (83)| 162 (117)
30cd| 172 (112)| 232 (155)

Potter Electric Signal Company, LLC
St. Louis, MO
Tech Support: 866-956-1211 / Customer Service: 866-572-3005
www.pottersignal.com
firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals