SB24 SERIES
SELECT-A-STROBE
Owner’s Manual
SB24 SERIES Select-A-Strobe
- Strobe with two fi eld selectable settings 15/30 and 75/110
- Designed to meet or exceed NFPA/ANSI standards and ADA accessibility giodelines
- Polarized models with wide listed voltage ranges using fi ltered DC or unfi ltered FWR input voltage
- Flying leads for in/out wiring supervision
- All models mount to 4” square back box
- Available in 24VDC polarized models
- Strobe synchronization requires an Amseco SMD10-3A (daisy chain) sync module
- Viewable candela setting
- Indoor/outdoor
Amseco’s newly designed UL1971 listed Select-A-Strobe Series SB24-153075 and
SB24-75110 are designed to provide visual signaling devices for fi re
protective systems. They meet UL 1638 standard for visual signaling devices
for the hearing impaired, ADA requirements, ANSI and NFPA standards.
The light output can be selected by a selector jumper (white) located on the
front panel. Model SB24-153075 can be set for 15cd (jumper not cut) or 30cd
(jumper cut). The SB24-75110 can be set at 75cd (jumper not cut) or 110cd
(jumper cut).
In those instances where two ore more Amseco chimes, horns, and/or strobes are
connected and require a synchronized code 3 temporal pattern and/or strobe fl
ash, the Amseco SMD10-3A Sync Module (daisy chain) may be used to meet the
required codes.
Ordering Information
Model Number| Stock Number| Rated Voltage (VDC)| Strobe
Output (cd)| Sync Module
---|---|---|---|---
SB24-1530R| 4560036| 24| 15 or 30| SMD10-3A
SB24-75110R| 4560037| 24| 75 or 110| SMD10-3A
Engineering Specifi cations
The visual alarm indicating appliance shall be Amseco model SB24 Strobe Series or equivalent device. The strobe shall be listed under UL 1971 standard for signaling devices for the hearing impaired and shall be approved for fi re protective service. The candela output shall be fi eld selectable, having a dual setting of 15/75 cd or 30/120 cd output. The signaling strobe shall operate on 24V DC from a non-coded regulated DC supply or full-wave rectifi ed, unfi ltered supply. It is designed to produce a signal fl ash of one fl ash per second with continuously applied minimum voltage. The strobe shall be capable of wall or ceiling mounting to an electrical back box. Visual signaling devices shall be mounted to 80” above the highest fl oor point or 6” below ceiling, whichever is lowest. They are to be installed as per plans and specifi cations.
Wiring Diagram
Refer to the SMD10-3A Sync Module instruction manual for Class “A” wiring or other application diagrams.
Light Output
UL Required Minimum Light Output (cd)
| Wall Mount – Horizontal| Wall Mount – Vertical
---|---|---
Degrees| 15 cd| 30cd| 75cd| 110cd| 15 cd| 30cd| 75cd| 110cd
0| 75.00| 75.00| 75.00| 110.00| 75.00| 75.00| 75.00| 110.00
5-25| 13.50| 27.00| 67.50| 99.00| 13.50| 27.00| 67.50| 99.00
30| 11.| 22.50| 56.| 82.50| 13.50| 27.00| 67.50| 99.00
35| 11.| 22.50| 56.| 82.50| 10.| 19.50| 49.| 71.50
40| 11.| 22.50| 56.| 82.50| 6.90| 13.80| 34.50| 50.60
45| 11.| 22.50| 56.| 82.50| 5.10| 10.20| 25.50| 37.40
50| 8.| 16.50| 41.| 60.50| 4.| 8.10| 20.| 29.70
-, ,| 7.| 13.50| 34.| 49.50| 3.30| 6.60| 16.50| 24.20
60| 6.00| 12.00| 30.00| 44.00| 2.70| 5.40| 13.50| 19.80
65| 5.| 10.50| 26.| 38.50| 2.40| 4.80| 12.00| 17.60
70| 5.| 10.50| 26.| 38.50| 2.| 4.50| 11.| 16.50
75| 4.50| 9.00| 22.50| 33.00| 2.| 3.90| 10.| 14.30
80| 4.50| 9.00| 22.50| 33.00| 1.80| 3.60| 9.00| 13.20
85-90| 4.| 7.50| 19.| 27.00| 1.80| 3.60| 9.00| 13.20
Compound 45| 3.60| 7.20| 18.00| 26.40| –| –| –| –
Mounting
For semi-fl ush mounting in combination with Amseco BZ-54 Horn:
- Mount the SB24-153075/75110 to the horn with provided accessory screws (#8-32 x 9/16” 14mm) by passing lead wires of the SB24-153075/75110 through the nylon bushing wire hole of the horn.
- Connect both lead wires of SB24-153075/75110 and BZ-54 to the power supply from the control panel. Mount them together to the back box (BBX-4 with the screws provided) into the strobe light mounting holes.
Dimensions: inches (mm)
Installation
For stand alone installation:
- Locate the locking tab at the center of the lowest louver on the front cover.
- Insert a small fl at head screwdriver to the lift tab in order to release the cover from the unit.
| SB24-153075| SB24-75110
---|---|---
Not Cut| 15cd| 75cd
Cut| 30cd| 110cd
Potter Electric Signal Company
2081 Craig Road, St. Louis, MO, 63146-4161
Phone: 800-325-3936/Canada
888-882-1833
www.amseco-kai.com
PRINTED IN USA
MFG. #5401400 – REV B
9/07
firealarmresources.com
Documents / Resources
|
POTTER SB24 SERIES
Select-A-Strobe
[pdf] Owner's Manual
SB24 SERIES Select-A-Strobe, SB24 SERIES, Select-A-Strobe, A-Strobe, Strobe
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>