POTTER SH-1224WP SERIES Wall Mount Weather Proof Select-A-Strobe-Horn Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
SH-1224WP SERIES
WALL MOUNT WEATHER PROOF
SELECT-A-STROBE/HORN®
SH-1224WP SERIES Wall Mount Weather Proof Select-A-Strobe-Horn
- UL and cUL listed
- 12 VDC with 15, 35 or 60 cd setting
- 24 VDC with 15, 35, 60, 75, 95 or 110 cd settings
- Outdoor and indoor
- 6 distinctive candela settings
- Candela selection view window
- 15/75 ADA compliant on 60cd setting
- 33 sound output settings
- Horn or chime sound output
- Pre-wire back plate
- Universal back plate mounting (single gang, double gang, octagon, or 4” square)
- Single screw mounting
- Low current draw
The SH-1224WP Strobe/Horn Series provides a wide range of candela light output
options in a single device. The candela settings include a 12 or 24 volt DC
operation for the 15, 35 and 60 (75 on axis) candela settings and 24 volt DC
operation for the 15, 35, 60, 75, 95 and 110 candela settings. The candela
setting is displayed through the front
window and is selectable using a drum wheel. The strobes can be synchronized
using a control panel with the Potter(Amseco) sync protocol or a SMD10-3A sync
module.
The horn settings include Temporal, Non-Temporal, March Time and a Chime
sound. The horn also has Low, Mid and High volume settings for each pattern
and tone. The tones include 2400 Hz, ElectroMechanical and Broadband.
The voltage input can be either regulated DC or full wave rectified (FWR) 12
volt or 24 volt operation with an operating range of 8 to 33V DC. The SH-
1224WP utilizes a universal mounting plate that will mount on a single gang,
double gang, octagon and 4” square electrical boxes. The back plate allows the
installer to mount the plate and terminate the wire connections. The
strobe/horn attaches in a hinge fashion from the top and is secured by a
single mounting screw. The strobe/horn completely covers the mounting back
plate, therefore it can be mounted before other trades work is completed and
not affect the final look.
The Potter SH-1224WP is listed for both outdoor and indoor installations. For
outdoor installations the device must be mounted on a matching BBX-5 back box
or a BBK-1 bell back box.
Installation
Note: Installation must comply in accordance with applicable standards.
Ordering Information
Stock Number | Model Number | Description | Color |
---|---|---|---|
4710010 | SH-1224WP-R | Selectable strobe/horn/chime | Red |
4270048 | BBX-5 | Back box (included) | Red |
4270049 | White | ||
1500001 | BBK-1 | Bell back box | Red |
Dimensions: inches (mm)
Light output in precentage when measured from the following directions per UL 1971.
Wel mount veritical dispersion
Degrees | % of Rating |
---|---|
Horizontal | Vertical |
0 | 100 |
5-25 | 90 |
30 | 75 |
35 | 75 |
40 | 75 |
45 | 75 |
50 | 55 |
55 | 45 |
60 | 40 |
65 | 35 |
70 | 35 |
75 | 30 |
80 | 30 |
85-90 | 25 |
WARNING
High voltage may be present inside the light assembly even though power is not
connected. If access to the component board is required (removal or
replacement), the capacitor must be discarged by touching a wire to both ends
of the flashtube.
DO NOT attempt to touch or move the assembly until the capacitor has been
discharged.
Specifications
Strobe Current
Setting | Light Output | Max. RMS Operating Current (mA RMS) |
---|---|---|
Reg. 12 VDC | Reg. 12 FWR | Reg. 24 VDC |
1 | 15cd | 129 |
2 | 35cd | 160 |
3 | 60/75cd | 193 |
4 | 75cd | NA |
5 | 95cd | NA |
6 | 110cd | NA |
Voltage | 12/24V | |
--- | --- | |
UL Designation | Regulated 12 DC/FWR | Regulated 24 DC/FWR |
Operating Voltage Range | 8 – 17.5V | 16 – 33V |
Flash Rate | 60 times/min. | |
Sync Module (SMD10-3A) | NA | Available |
Operating Temperature Range | Indoor installations: 32°F to 120°F (0°C to 49°C) |
Outdoor installations: -40°F to 151°F (-40°C to 66°C)
Note: To determine total current draw, add desired strobe setting and
horn selection. Refer to the installation instructions for further
information.
Horn Dipswitch
Pattern
1 ON – Non-temporal
1 OFF – Temporal
Both 2 = OFF
1 and 2 ON = March Time
Tone
3 and 4 ON = 2400Hz
3 ON and 4 OFF = Electromechanical
3 and 4 OFF = Chime
3 OFF and 4 ON = Broadband
Volume
5 and 6 ON = High
5 ON and 6 OFF = Mid
5 and 6 OFF = Low
7 and 8 ON = Horn/strobe on 2 wires
7 and 8 OFF = Horn/strobe on 4 wires
Non-Temporal Horn Current
Pattern| Volume| Max. RMS Current (mA RMS Current)| dBA
Reverberant Ratings per UL464 (dBA @ 10 ft.)| dBA Anechoic Ratings per CAN/ULC
S525 (dBA @ 10 ft.)
---|---|---|---|---
Reg 12 VDC| Reg 24 VDC| Reg 12 VDC| Reg 24 VDC| Reg 12 VDC| Reg 24 VDC
2400 Hz
| High| 119| 189| 87| 87| 99| 100
Mid| 44| 110| 82| 82| 94| 96
Low| 30| 72| 79| 80| 92| 92
Electro-Mechanical| High| 118| 174| 86| 87| 100| 100
Mid| 43| 98| 82| 84| 96| 97
Low| 27| 66| 79| 80| 93| 93
Broadband| High| 146| 205| 86| 86| 101| 102
Mid| 41| 104| 81| 82| 96| 98
Low| 28| 66| 77| 79| 94| 95
Chime| High| 37| 37| 70| 70| 86| 86
Mid| 11| 16| 62| 62| 79| 80
Low| 9| 12| 58| 57| 75| 75
Temporal Horn Current
Pattern| Volume| Max. RMS Current (mA RMS Current)| dBA Reverberant Ratings
per UL464 (dBA @ 10 ft.)| dBA Anechoic Ratings per CAN/ULC S525 (dBA @ 10 ft.)
---|---|---|---|---
Reg 12 VDC| Reg 24 VDC| Reg 12 VDC| Reg 24 VDC| Reg 12 VDC| Reg 24 VDC
2400 Hz| High| 124| 203| 82| 82| 100| 100
Mid| 46| 110| 77| 79| 95| 96
Low| 30| 82| 74| 75| 92| 92
Electro-Mechanical| High| 114| 193| 83| 82| 100| 101
Mid| 42| 113| 78| 80| 95| 96
Low| 28| 75| 75| 76| 93| 93
Broadband| High| 151| 219| 82| 82| 101| 102
Mid| 45| 110| 77| 78| 97| 98
Low| 30| 79| 75| 76| 94| 95
Chime| High| 29| 35| 68| 70| 86| 86
Mid| 10| 17| 61| 61| 79| 79
Low| 9| 12| 55| 55| 75| 76
March Time Horn Current
Pattern| Volu| Max. RMS Current (mA RMS Current)| dBA Reverberant Ratings per
UL464 (dBA @ 10 ft.)| dBA Anechoic Ratings per CAN/ULC S525 (dBA @ 10 ft.)
---|---|---|---|---
Reg 12 VDC| Reg 24 VDC| Reg 12 VDC| Reg 24 VDC| Reg 12 VDC| Reg 24 VDC
2400 Hz| High| 121| 210| 83| 84| 99| 100
Mid| 47| 116| 79| 81| 95| 96
Low| 36| 75| 76| 77| 92| 92
Electro-Mechanical| High| 114| 192| 83| 83| 100| 100
Mid| 42| 103| 80| 81| 95| 96
Low| 30| 71| 77| 77| 92| 93
Broadband| High| 153| 230| 83| 84| 101| 102
Mid| 42| 105| 79| 80| 97| 98
Low| 29| 79| 76| 77| 94| 95
Wiring Diagram
Wiring Observe Polarity Use both terminals (or Lead) for connection. Break
wire run to provide electrical supervision.
Horn I Strobe Sianal Operate Independently
Horn / Strobe Wiring Diagram for Audible Strobe Class “B” Circuit with
Audible Silence Feature. (SH-1224, SH1224W)
Horn or Strobe Wiring Diagram for Audible Strobe Class It” Circuit
without Audible Silence Feature.
Refer to the SMD 10-3A Sync Module instruction manual for Class “A” wiring or other application diagrams.
Engineering Specifications
The installer shall provide and install the Potter SH-1224WP selectable strobe/horn. The strobe shall have six (6) candela settings. The candela settings shall be selectable using a drum roller and shall display the candela setting on the front of the device. The horn shall have 33 selectable settings configurable by dip switches. The sounder shall be capable of ANSI Temporal Code 3, March Time and produce a chime output. The horn shall have three distinct volume levels. The strobe/horn shall operate at 12 or 24 VDC regulated or full wave rectified. The strobe/horn shall have an operating range between 8 and 33 VDC. The strobes can be synchronized using a control panel with the Potter(Amseco) sync protocol or a SMD10-3A sync module. The strobe/horn shall utilize a mounting plate that allows the installer to pre- wire the mounting plate. The mounting plate shall be universal and mount on a single gang, double gang, octagon or 4 inch square box. The Potter SH-1224-WP is listed for both outdoor and indoor applications. For outdoor installations, the device must be mounted on a matching BBX-5 or BBK-1 outdoor bell back box. The mounting plate shall be completely covered by the strobe/horn and shall be secured by a single screw. The strobe/horn shall be UL listed to standard 1638, General Signaling, and standard 1971, Signaling Devices for the Hearing Impaired. In addition, the strobe/horns shall be cUL listed to CAN-ULC S526. The horn shall be UL listed to standard 464, Audible Signaling Devices.
Potter Electric Signal Co., LLC
St. Louis, MO
Cust Service: 866-240-1870
Tech Support:866-956-1211
Canada 888-882-1833
www.pottersignal.com
PRINTED IN USA
MKT. #8910008 – REV I
12/17
firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>