POTTER SMD10-3A Sync Module

  • Polarized with wide operating voltage range using filtered DC or unfiltered FWR input voltage
  • Mounts to 4” square back box
  • Daisy chain up to 20 modules maximum
  • Screw terminal capacity up to AWG #12
  • Red metal plate
    Stock Number – 4670017

The Sync Module is designed to provide a synchronized temporal pattern (code 3) tone, and synchronize the strobe flashes when used with Amseco’s Select-A-Strobe, Select-A-Horn, and Select-A-Horn/Strobe series as well as the ability to silence the horn while maintaining the strobe flashes.
The SMD10-3A has the capability of connecting two Style Y (Class B) circuits or one Style Z (Class A) circuit and is rated for 3 Amperes per circuit.

The SMD10-3A can be interconnected so that more than two alarm zones can be synchronized by connecting the sync terminals (daisy chain connection). The maximum number of interconnected modules is twenty. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by F.A.C.P.
For additional compatibility information refer to Compatibility Document 5401513 Rev. A.

Specifications

Input Voltage Regulated 24V DC/FWR
Operating Voltage Range 16 – 33V DC/ FWR
Max. Load on Loop 3A Average Max. 5A Peak
Max. RMS Operating Current DC – 34mA FWR – 68mA
Mounting Back Box 4” x 4” x 1 1/2”
Operating Temperature Range 32°F – 120°F (0°C – 49°C)

Compatible Potter Products

CM24C SCM24-3075110 SL24C
CSH-1224W SCM24C SL24C-177
CSH24W SH-1224 SL24C-3075110
CSHB24 SH-1224-WP SL-24H
CSL-1224W SH24-153075 SL-24H-WP
CSL-24C SH24-75110 SL24W-153075
CSL-24W SH24C SL24W-75110
CSLB24 SH24C-177 SLB24-75
CSS SH24C-3075110 SSC2-3075110
H-1224 SH-24H SSC8-3075110
H24W SH-24H-WP SSR-2
HP-25T SHB24-75 SSR-8
SB24 SL-1224 SSS-2
SC-24 SL-1224-WP SSS-8

Daisy Chain Modules

POTTER SMD10-3A Sync Module-fig2

Potter Electric Signal Co., LLC • St. Louis, MO • Cust Service: 866-240-1870 • Tech Support: 866-956-1211/Canada 888-882-1833www.pottersignal.com

firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals