POTTER VSR-SG Vane Type Waterflow Alarm Switch Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER VSR-SG Vane Type Waterflow Alarm Switch
Features
UL, CUL and CSFM Listed
Service Pressure: Up to 175 PSI (12,07 BAR)
Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) – UL
Maximum Surge: 18 FPS (5.5 m/s)
Contact Ratings: Two sets of SPDT (Form C)
10.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
10 mAmps min. at 24VDC
Conduit Entrances: Two openings provided for 1/2″ conduit.
Individual switch compartments suitable for dissimilar voltages.
Environmental Specifications:
- NEMA 4/IP54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting.
- Temperature Range: 40°F – 120°F, (4.5°C – 49°C) – UL
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Stock Number: 1144461
Optional: Cover Tamper Switch Kit, stock no. 0090148
Replaceable Components: Retard/Switch Assembly, stock no. 1029030
WARNING
- Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances.
- Shock hazard. Disconnect power source before servicing. Serious injury or death could result.
- Risk of explosion. Not for use in hazardous locations. Serious injury or death could result.
CAUTION: Waterflow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air, or short retard times.
General Information
The Model VSR-SG is a vane type waterflow switch for use on wet sprinkler systems using CPVC plastic fittings (manufactured by Tyco, Nibco, Victaulic, Ipex, and Spears Manufacturing Company) that use 1”, 1 ¼”, 1 ½”, or 2” pipe sizes. It is equipped with a union to accommodate installation in confined spaces.
The VSR-SG contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period.
Enclosure
The VSR-SG switches and retard device are enclosed in a general purpose, die- cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin number 5401103 for installation instructions of this switch.
Installation (see Fig. 1, 2, and 3)
These devices may be mounted on horizontal or vertical pipe. On horizontal
pipe they shall be installed on the top side of the pipe where they will be
accessible. The device should not be installed within 6″ (15 cm) of a fitting
which changes the direction of the waterflow or within 24″ (60 cm) of a valve
or drain. The unit has a 1″ male fitting for gluing into a CPVC plastic tee.
NOTE: Do not leave cover off for an extended period of time.
Loosen the union nut and separate the 1″ male fitting from the VSR-SG. Glue
the 1″ male fitting into the TEE following the TEE manufacturer’s instructions
for preparation and gluing of CPVC piping systems. (Note: The 1″ male fitting
must bottom out on the stop of the TEE for proper operation of the VSR-SG. See
Fig. 1.) Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-
SG to the 1″ male fitting. Select the proper paddle for the pipe size and type
of TEE used. See Fig. 3 for instructions on how to change paddle. Verify that
the o-ring is properly positioned in its groove. Hand tighten the nut on the
union after orienting the device in the appropriate direction to detect
waterflow as shown in Fig. 2.
The vane must not rub the inside of the TEE or bind in any way. The stem
should move freely when operated by hand.
CAUTION
Do not trim the paddle. Failure to follow these instructions may prevent the device from operating and will void the warranty.
CAUTION
Do not over-tighten the union nut, hand tighten only
Fig. 1
Glue the 1″ male fitting into the TEE following the TEE manufacturer’s
instructions for preparation and gluing of CPVC piping systems. Wait 2 to 4
hours to allow the glue to dry before attaching the VSR-SG to the 1″ male
fitting
Fig. 2 Retard Adjustment
The delay can be adjusted by rotating the retard adjustment knob from 0 to the
max setting (60- 90 seconds). The time delay should be set at the minimum
required to prevent false alarms.
Fig. 3
Important:
11 paddles are furnished with each unit to accommodate the various sizes and
manufacturers of TEES. The paddles have raised lettering that show the pipe
size and the TEE manufacturer they are to be used with. The proper paddle must
be used. The paddle must be properly attached (see Fig. 3) and the screw that
holds the paddle must be securely tightened.
Fig. 4
Break out thin section of cover when wiring both switches from one conduit
entrance.
**Fig. 5 Switch Terminal Connections Clamping Plate Terminal
**
WARNING
An uninsulated section of a single conductor should not be looped around the
terminal and serve as two separate connections. The wire must be severed,
thereby providing supervision of the connection in the event that the wire
become dislodged from under the terminal. Failure to sever the wire may render
the device inoperable risking severe property damage and loss of life.
Do not strip wire beyond 3/8″ of length or expose an uninsulated conductor
beyond the edge of the terminal block. When using stranded wire, capture all
strands under the clamping plate.
Fig. 6 Typical Electrical Connections
Notes:
- The Model VSR-SG has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator.
- For supervised circuits, see “Switch Terminal Connections” drawing and warning note (Fig. 5).
Testing
The frequency of inspection and testing for the Model VSR-SG and its
associated protective monitoring system shall be in accordance with applicable
NFPA Codes and Standards and/or the authority having jurisdiction
(manufacturer recommends quarterly or more frequently).
If provided, the inspector’s test valve shall always be used for test
purposes. If there are no provisions for testing the operation of the flow
detection device on the system, application of the VSR-SG is not recommended
or advisable.
A minimum flow of 10 GPM (38 LPM) is required to activate this device.
NOTICE: Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions.
**Fig. 7 Mounting Dimensions
**
Maintenance
Inspect detectors monthly. If leaks are found, replace the detector. The VSR-
SG waterfl ow switch should provide years of trouble-free service.
The retard and switch assembly are easily field replaceable. In the unlikely
event that either component does not perform properly, please order
replacement retard switch assembly stock #1029030 (see Fig. 6). There is no
maintenance required, only periodic testing and inspection.
Retard/Switch Assembly Replacement (See Fig. 9)
NOTICE The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the pipe
- Make sure the fi re alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service.
- Disconnect the power source for local bell (if applicable).
- Identify and remove all wires from the waterflow switch.
- Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws.
- Remove the retard assembly by lifting it straight up over the tripstem.
- Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fi t into the locating pin bosses on the base.
- Re-install the (2) original mounting screws.
- Reconnect all wires. Perform a flow test and place the system back in service.
Fig. 9
Removal of Waterflow Switch
- To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced.
- Turn off electrical power to the detector, then disconnect wiring.
- Loosen nuts and separate unit from the glued-in fittings
- Gently lift the unit far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing to lift the waterflow detector.
- Lift detector clear of pipe.
Customer Service
Potter Electric Signal Company, LLC •
St. Louis, MO •
Cust Service: 866-572-3005 •
Tech Support: 866-956-0988 /Canada
888-882-1833•
www.pottersignal.com
References
- Fire Alarm Resources | Download fire alarm documents
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>