POTTER SPB-24N Projected Beam Smoke Detector Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
SPB-24N Projected Beam Smoke Detector
Owner’s Manual
SPB-24N
PROJECTED BEAM SMOKE DETECTOR
STANDARD FEATURES
- Microprocessor based for reliability
- Simple setup & alignment with signal strength LED’s
- Provides 60 feet on center linear protection at a range of 32.8 feet to 328 feet
- Automatic compensation for signal drift or dirty lens
- Three field adjustable sensitivity settings
- Form A alarm and Form B trouble contacts
- Calibrated filters available to verify sensitivity
- Color-coded emitter and receiver labels for easy recognition
SPECIFICATIONS
Rated Voltage | 24VDC |
---|---|
Working Voltage | 19VDC – 33VDC |
Supervisory Current | 250uA @ 24VDC |
Alarm Current | 20mA @ 24VDC |
Trouble Current | 20mA @ 24VDC |
AmbientTemperature Range | 32°F-122°F |
Sensitivity Test Feature | Manufacturers test filters |
Dimensions | 5.5″ Tall |
3.2″ Wide
4.0″ Deep
Mounting| Wall mount or Single Gang Box
Specifications subject to change without notice.
APPLICATION
The SPB-24N Projected Beam Smoke Detector consists of an emitter and receiver.
The projected beam smoke detector should be placed so that smoke generated by
a fire will likely rise into the path of the beam. The receiver is constantly
monitoring and measuring the intensity of the beam transmitted by the emitter.
Should the smoke from a fire cause a decrease in the signal strength of a
magnitude that exceeds the programmed obscuration setting, an alarm signal is
generated.
The SPB-24N Projected Beam Smoke Detector can provide vital fire detection in
applications where other type detectors may not be able to respond quickly, or
at all, to a fire condition. Examples of some applications where projected
beam smoke detectors have been successfully used include:
atriums, gymnasiums, theatres, museums, factories, tunnels, churches, stables,
anechoic chambers and high air velocity areas. The SPB- 24N Projected Beam
Smoke Detector may also be used in conjunction with more traditional spot type
smoke detection devices to provide an even more comprehensive detection
system.
For more information on how to install the SPB-24N Projected Beam Smoke
Detector consult the SPB-24N Installation Instruction Guide and the applicable
NFPA Standards for additional guidance.
OPERATION
The near infrared pulsed beam generated by the emitter is sensed by the
photodiode of the receiver, where it is converted into an electrical signal.
This signal is then amplified and applied, via an analog to digital converter,
to a microprocessor. The normal state signal (the initial beam data) once
stored in the microprocessor is used as reference for comparison with
subsequent beam signals.
When there is a difference between actual beam strength and stored reference
data that exceeds the programmed alarm obscuration reference level, a fire
signal is produced. A trouble signal is generated if the beam is more than 90%
obstructed (as opposed to partially obscured by smoke).
The microprocessor also provides compensation for a change in received signal
value, with time, caused by contamination of the optics. Since such a change
with time appears as a slow change in the beam signal, the microcomputer
compensates in such a manner that the signal moves closer to the reference
data at a rate approximately +1% per hour. When this compensating capability
reaches a limit, the microcomputer automatically generates a trouble signal.
A calibrated test filter is available upon request to test and verify the
sensitivity setting of the projected beam smoke detectors.
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install, where indicated on the plans, the
SPB-24N Projected Beam Smoke Detector. The detector shall have a range of 32.8
feet to 328 feet. The projected beam smoke detector shall be field adjustable
to one of the three obscuration settings of 25%, 50% or 70% per span. These
settings shall be capable of being verified with calibrated filters. Side to
side spacing shall be a maximum of 60 feet on center.
The projected beam smoke detector shall posses circuitry that automatically
compensates for normal ambient changes in the intensity of the emitted beam
strength. The microprocessor shall provide compensation for a change in
received signal value, with time, caused by contamination of the optics. Since
such a change with time appears as a slow change in the beam signal, the
microcomputer compensates in such a manner that the signal moves closer to the
reference data at a rate of approximately +1 % per hour. When this
compensating capability reaches a limit, the microcomputer automatically
generates a trouble signal.
The projected beam smoke detector(s) shall also signal a trouble condition if
the beam has a blockage of 90% or more than 20 seconds and automatically
resets to normal when blockage is removed.
The projected beam smoke detector(s) shall be UL listed for these
applications. Voltage and RF transient protection shall be integral to the
internal circuitry of the projected beam smoke detector so as to minimize
false alarm potential.
To facilitate easy installation and setup, the projected beam smoke detectors
shall employ signal strength indicating LEDs. Alignment shall be facilitated
by turning an alignment adjustment wheel and monitoring the relative signal
strength based upon which LEDs are illuminated.
The detectors shall also illuminate a red LED, which is visible externally,
when an alarm condition is indicated.
The projected beam smoke detector shall provide a Form “A” dry contact for
alarm and Form “B” dry contact for trouble.
INSTALLATION
The SPB-24N Projected Beam Smoke Detector shall be installed in accordance with the Installation Instruction Guide provided with every unit. Refer to the applicable NFPA Standards for additional guidance on spacing, irregular ceiling surfaces and other design considerations.
Potter Electric Signal Company
2081 Craig Road, St. Louis, MO, 63146-4161
Phone: 800-325-3936/Canada
888-882-1833
www.pottersignal.com
MKT. #8840016 – REV D
firealarmresources.com
References
- Fire Alarm Resources | Download fire alarm documents
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>