POTTER PFC-8500 Analog Addressable Fire Alarm Control Panel
Features
- Max No. of Addressable Devices 508 addresses
- AC Input Rated Voltage 120/230 VAC
- AC input voltage frequency 50 / 60 HZ
- Auxiliary Power ratings 0.5 A at 24VDC (20.4 to 26.4 VDC)
- Dry contact output ratings 2 A at 30 VDC (resistive)
- 24 VDC output wiring style NFPA Style Y or Z
- 24 VDC maximum output current 1.5 A per output×4 outputs 3.0 A per output×2 outputs 3.0 A per output×1, 1.5 A per output×2 outputs
- Addressable Loop Wiring Style NFPA Style 4, 6 or 7
- Max No. of Devices per Loop 127 addresses
- Max Loop Circuit Resistance 50 ohms
- Annunciator buss wiring style NFPA Style 4
- Max remote annunciator 31 units
Description
The PFC-8500 Fire Control Panel has the capability of storing setpoints,
adding and removing devices as well as defining operational behavior. All
changes are stored in a configuration data file, which enables the user to
easily configure the systfrom either the FACP or at a remote computer. This
flexibility allows ongoing system upgrades and modifications to support building
expansion and increased safety objectives. The panel can be programmed to
communicate with addressable modules and supports a total of 127 devices on a
single SLC. The PFC-8500 may be expanded to support up to 508 devices when
three (3) ALE-127 modules are configured. The panel also contains all the
necessary terminals to communicate with all other system components directly,
including smoke sensors, heat detectors, and modules. The operator interface
consists of a LCD display, system status LEDs, a local status buzzer, system
control switches and a numeric keypad. The 80 character LCD display and system
status LED’s communicate the latest system status information to the operator.
The local buzzer audibly attracts the operator’s attention during status
change occurrences. The remote annunciator output provides the panel with the
ability to interface to remote annunciators. The annunciator connection is a
proprietary protocol operating over an RS-485 style communications bus.
The PFC supervises and maintains the 24 VDC batteries that supply secondary
power for the system. The PFC has dedicated outputs for the ALE-127. The PFC
also supplies 24 VDC output on auxiliary output terminal blocks for use by
external devices such as option components (such as Remote Annunciator and
Sounder Base), addressable output devices and 4-wire smoke detectors.
SLC Loop Accessories
The control panel may be connected with up to 127 addressable devices or modules in any combination. The SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. Additional loop expanders (ALE-127) may be added to increase the total number of devices to 508.
SLC Loop Devices
Device | Description |
---|---|
PSA | Analog Photo Electric Smoke Detector is a smoke detector with a listed |
obscuration of 1.02 to 3.83 percent per foot.
PSHA| Combination Analog Photo Electric Smoke/Heat Detector – a smoke detector
with a listed obscuration of 1.02 to
3.83 percent obscuration and a fixed temperature 135° Fahrenheit heat detector
FHA| Analog Fixed Temperature Heat Detector that is selectable from 135° F to
185°F
RHA| Analog Rate or Rise Heat Detector that has a fixed temperature selection
from 135°F and 174°F and also will alarm if the temperature increase 12-15°F
in one minute
AB-6| 6” round base that is mounted to an electrical box and wired for
connection of one of the above sensors
AB-4| 4” round base that may be mounted to an electrical box and wired for
connection to the above sensors
AIB| Isolater base that interrupts a short in a SLC and prevents the short
from affecting protected devices on the loop
ARB| Addressable Relay Base that contains two relays controlled by the SLC.
One relay is rated at 8 amps at 240 VAC/30VDC and the other is rated at 2 amps
240 VAC/30 VDC
ASB| Addressable Sounder Base that contains and addressable sounder module
that may be configured for local, group and all call. The sounder follows the
pattern sent to the device.
modules
Device | Description |
---|---|
MCM | Miniature Contact Module provides a small foot print contact module for |
mounting inside an enclosure, typically used to monitor a pull station
SCM-4| Single Contact Module is a standard contact module with an LED that
mounts into a 4” square electrical box. The contact monitors normally open
contacts and the LED will provide an indication when the device has activated.
DCM-4| Dual Contact Module is a device that can monitor two distinct inputs
with a single device or in a Class A mode. The DCM-4 mounts into a 4” square
electrical box and has a cover plate with an LED as a status indication.
TRM-4| Twin Relay Module provides two form C relays that simultaneously active
when the module is triggered by the control panel. Each relay is rated for 2
amps at 24VDC or 0.5 amps at 125VAC.
MOM-4| Monitored Output Module is a power switching module that monitors the
circuit that is controlled by the control
panel.
CIZM-4| Conventional Input Zone Module is used to connect conventional smoke
detectors to the system that receive their power from the module. This module
is like a conventional zone on the SLC.
SCI| Short Circuit Isolater interrupts a short on the SLC and prevents the
short from affecting protected devices on the loop. These or the AIB are
required in Class A, Style 7 installations.
SLC Circuit Diagram