POTTER VSR-FEX Explosion Proof Vane Type Waterflow Alarm Switch With
Retard
Features
- NEMA 4/IP66 solid metal enclosure
- 0-90 second field replaceable retard
- Non-corrosive saddle bushing
- (2) ½” threaded conduit connections
- Assembled in USA
NOTICE
This document contains important information on the installation and operation
of VSR-FEX waterflow switches. Please read all instructions carefully before
beginning installation. A copy of this document is required by NFPA 72 to be
maintained on site.
General Information
The Model VSR-FEX is a vane type waterflow switch for use on wet sprinkler
systems located in hazardous locations as shown above. The unit may also be
used as a sectional waterflow detector on large systems.
The unit contains two single pole, double throw, snap action switches and an
adjustable, instantly recycling pneumatic retard. The switches are actuated
when a flow of 10 gallons per minute (38 Lpm) or more occurs downstream of the
device. The flow condition must exist for a period of time necessary to
overcome the selected retard period.
Enclosure
The unit is enclosed in a cast aluminum housing. The cover is held in place with six M6 x 1 mm-6g; 30 mm long socket head cap screws with a 5 mm hexagonal drive head and a property class of 8.8. These screws can only be replaced with identical ones. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin number 5401024 for installation instructions of this switch.
CAUTION
Waterflow switches that are monitoring wet pipe sprinkler systems shall not be
used as the sole initiating device to discharge AFFF, deluge, or chemical
suppression systems. Waterflow switches used for this application may result
in unintended discharges caused by surges, trapped air, or short retard times.
Technical Specifications
Dimensions | See Fig. 2 |
---|---|
Enclosure | Cover: Cast Aluminum Base: Cast Aluminum |
Minimum Flow Rate for Alarm | 10 GPM (38 Lpm) |
Maximum Surge | 18 FPS (10 m/s) |
Switch Contacts
| Two sets of SPDT (Form C)
15.0 Amps at 125/250 VAC
2.0 Amps at 30 VDC Resistive
environmental
Limitations
| • For use in hazardous locations, Classified as: Class I: Div. 1 & Div. 2, Groups C, D
Class II: Div. 1 & Div. 2, Groups E, F, G, Class III: Div. 1 & Div. 2
• Suitable for indoor or outdoor use with factory installed gasket and cast aluminum housing
• NEMA 4/IP66 Rated Enclosure – use with appropriate conduit fitting
• Temperature: 40°F/120°F (+4.5°C ≤ Ta ≤ +49°C)
• Non-corrosive sleeve factory installed in saddle
Conduit Entrances
| Two conduit entrances provided for ½” conduit with ½” NPT threaded
connections. Use an ATEX certified plug of protection “d”, “tb”, and IP66 for
all unused conduit openings.
Service Use| NFPA 13, 72
Maximum System Pressure| 450 PSI (31 BAR)
*Specifications subject to change without notice
Installation
These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6” (15 cm) of a fitting which changes the direction of the waterflow or within 24” (61 cm) of a valve or drain.
- Drain the system and cut a hole in the pipe using a hole saw in a slow speed drill. The 2” and 2 1/2” (50 mm and 65 mm) devices require a hole with a diameter of 1 1/4” + 1/8” – 1/16” (33 mm ±2 mm). All other sizes require a hole with a diameter of 2” ± 1/8” (50 mm ±2 mm). See chart below.
- Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole.
- Roll the vane so that it may be inserted into the hole, do not bend or crease it.
- Insert the vane so that the arrow on the saddle points in the direction of the waterflow.
- Install the saddle strap and tighten nuts alternately to an eventual 20 ft-lbs. (27 n-m) of torque. See Fig. 1 and chart below. The vane must not rub the inside of the pipe or bind in any way.
CAUTION
Do not trim the paddle. Failure to follow these instructions may prevent the
device from operating and will void the warranty. Do not obstruct or otherwise
prevent the trip stem of the flow switch from moving when water flows as this
could damage the flow switch and prevent an alarm. If an alarm is not desired,
a qualified technician should disable the alarm system.
Compatible Pipe/ Installation Requirements
Model| Nominal Pipe Size| Nominal Pipe O.D.| Pipe Wall Thickness| Hole Size| U-Bolt Nuts
Torque
Lightwall| Schedule 10 (UL)| Schedule 40 (UL)| BS-1387 (LPC)| DN (VDS)
| inch| mm| inch| mm| inch| mm| inch| mm| inch| mm| inch| mm| inch| mm| inch|
mm| ft-lb| n-m
VSR-FEX (2”)| 2| DN50| 2.375| 60.3| .065| 1.651| 0.109| 2.77| 0.154| 3.91|
0.142| 3.6| 0.091| 2.3|
1.25 + .125/-
.062
|
33.0 ± 2.0
|
20
|
27
VSR-FEX (2.5”)| 2.5| –| 2.875| 73.0| .084| 2.134| 0.120| 3.05| 0.203| 5.16| –|
–| –| –
VSR-FEX (2.5”)| –| DN65| 3.000| 76.1| –| –| –| –| –| –| 0.142| 3.6| 0.102| 2.6
VSR-FEX (3”)| 3| DN80| 3.500| 88.9| .083| 2.108| 0.120| 3.05| 0.216| 5.49|
0.157| 4.0| 0.114| 2.9|
2.00 ± .125
|
50.8 ± 2.0
VSR-FEX (4”)| 4| DN100| 4.500| 114.3| .084| 2.134| 0.120| 3.05| 0.237| 6.02|
0.177| 4.5| 0.126| 3.2
VSR-FEX (6”)| 6| DN150| 6.625| 168.3| .115| 2.921| 0.134| 3.40| 0.280| 7.11|
0.197| 5.0| 0.157| 4.0
VSR-FEX (8”)| 8| DN200| 8.625| 219.1| –| –| 0.148| 3.76| 0.322| 8.18| 0.248|
6.3| 0.177| 4.5
WARNING
When this device is to be installed in an area that is classified as
“HAZARDOUS”, the person responsible for safety in the area shall be contacted
to determine if the tools and operations required for the installation of the
device and associated components are permitted in the area. To reduce the risk
of ignition of hazardous atmospheres, disconnect supply circuits before
opening cover. Keep cover tight while circuits are live.
The mating surfaces of the cover and housing are designed and machined to meet
the hazardous location requirements of the applicable listing agencies. These
surfaces shall be protected from any damage and shall be clean and free of all
foreign matter. No gasket or sealant of any type is allowed on these surfaces.
The use of any type of gasket, sealant, or damage to these surfaces will void
the hazardous rating of the device and can lead to explosion and death. These
surfaces are not repairable and the cover is not replaceable. If any damage
has occurred to either surface or a gasket or sealant has been applied to
either surface, the entire device must be immediately removed from service and
replaced. All foreign matter must be removed. If mating surfaces are damaged,
do not place the device in service.
Important: When reinstalling the cover during installation or maintenance,
wipe the mating cover and housing surfaces with a soft clean lint free cloth.
Carefully inspect the surfaces for any damage or foreign matter. Install the
cover on the housing to fully seat the mating surfaces. Initially tighten each
of the (6) cover screws evenly to 5 in-lbs (.56 n-m) to ensure that the cover
is fully seated. Next, torque each cover screw to a final torque of 20 in-lbs
(2.3 n-m). Failure to follow these instructions may result in injury or death.
Mounting Dimensions
Typical Electrical Connections
Switch Clamping Plate Terminal
WARNING
An uninsulated section of a single conductor should not be looped around the
terminal and serve as two separate connections. The wire must be severed,
thereby providing supervision of the connection in the event that the wire
becomes dislodged from under the terminal.
Testing
The frequency of testing for the model VSR-FEX and its associated protective
monitoring system should be in accordance with applicable NFPA Standards
and/or the authority having jurisdiction (manufacturer recommends quarterly or
more frequently).
If provided, the inspector’s test valve, that is usually located at the end of
the most remote branch line, should always be used for test purposes. If there
are no provisions for testing the operation of the flow detection device on
the system, application of the VSR-FEX is not recommended or advisable.
A minimum flow of 10 gpm (38 Lpm) is required to activate this device.
NOTICE
Please advise the person responsible for testing of the fire protection system
that this system must be tested in accordance with the testing instructions.
Engineer/Architect Specifications Vane Type Waterflow Switch
The Model VSR-FEX is a vane type waterflow switch for use on wet sprinkler
systems located in hazardous locations. The unit may also be used as a
sectional waterflow detector on large systems.
The unit contains two single pole, double throw, snap action switches and an
adjustable, instantly recycling pneumatic retard. The switches are actuated
when a flow of 10 gallons per minute (38 Lpm) or more occurs downstream of the
device. The flow condition must exist for a period of time necessary to
overcome the selected retard period.
WARNING
- Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances.
- Shock hazard. Disconnect power source before servicing. Serious injury or death could result.
- Read all instructions carefully and understand them before starting installation. Save instructions for future use. Failure to read and understand instructions could result in improper operation of device resulting in serious injury or death.
- Risk of explosion. Not for use in hazardous locations. Serious injury or death could result.
CAUTION
- Failure to install properly could damage the switch and cause improper operation resulting in damage to equipment and property.
- To seal threads, apply Teflon tape to male threads only. Using joint compounds or cement can obstruct the pressure port inlet and result in improper device operation and damage to equipment.
- Do not over tighten the device, standard piping practices apply.
Ordering Information
Nominal Pipe Size | Model | Part Number |
---|---|---|
2″ | DN50 | VSR-FEX (2”) |
2 1/2″ | DN65 | VSR-FEX (2.5”) |
3″ | DN80 | VSR-FEX (3”) |
4″ | DN100 | VSR-FEX (4”) |
6″ | DN150 | VSR-FEX (6”) |
8″ | DN200 | VSR-FEX (8”) |
Description | Part Number | |
--- | --- | |
Hex Key-5mm | 5250074 | |
Cover Tamper Switch Kit for VSR-FEX | 0090139 |
Potter Electric Signal Company, LLC
St. Louis, MO
Phone: 800-325-3936
www.pottersignal.com