POTTER PAD100-DIM Dual Input Module Instruction Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER PAD100-DIM Dual Input Module Instruction Manual
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the
PAD100-DIM module.
This module is only compatible with addressable fire systems that utilize the
PAD Addressable Protocol.
All terminals are power limited and should be wired in accordance with the
requirements of NFPA 70 (NEC) and NFPA 72 (National
Fire Alarm Code).
Failure to follow the wiring diagrams in the following pages will cause the
system to not operate as intended.
For further information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the
control panel installation manual for proper system operation
Description
The PAD100-DIM uses one (1) SLC loop address when monitoring two (2) Class B
circuits or one (1) Class A circuit.
The module mounts on either an UL Listed 2-1/2″ deep 2-gang box or 1-1/2″ deep
4″ square box.
The PAD100-DIM is capable of monitoring two (2) separate Class B circuits
making it ideal for monitoring sprinkler waterflow and valve tamper switches
when they are located in the same proximity.
The PAD100-DIM includes one red LED to indicate the module’s status.
In normal condition, the LED flashes when the device is being polled by the
control panel.
When an input is activated, the LED will flash at a fast rate. If the LED
blink has been disabled via the programming software, in a normal condition
the LED of the device will be off.
All other conditions remain the same.
Setting the Address
All PAD protocol detectors and modules require an address prior to connection
to the panel’s SLC loop.
Each PAD device’s address (i.e., detector and/or module) is set by changing
the dip switches located on the device.
PAD device addresses are comprised of a seven (7) position dip switch used to
program each device with an address ranging from 1–127.
Figure 1. PAD Device Dip Switch Addresses Table (Addresses 1–127)
Note: Each “gray” box indicates that the dip switch is “On,” and each “white” box indicates “Off.”
The examples shown below illustrate a PAD device’s dip switch settings: the
1st example shows a device not addressed where all dip switch settings are in
the default “Off” position, the 2nd illustrates an addressed PAD device via
the dip switch settings.
Figure 2. Examples of PAD Device Showing Default Dip Switch Setting
(Unaddressed) & Addressed PAD Device
All dip switches are shown in the “Off” position.
Example shows this PAD device’s address = 42. Dip switches #2, 8 & 32 are
in the “On” position.
When the PAD100-DIM is used to monitor two individual Class B circuits a
single device address is assigned; each input is then identified as a sub-
point of the module address.
For example, if the address number is assigned as “8”, the first input will be
“8.1”, and the second input will be “8.2.”
Before connecting a device to the SLC loop, take the following precautions to
prevent potential damage to the SLC or device.
- Power to the SLC is removed.
- Field wiring on module is correctly installed.
- Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage | 24.0V |
---|---|
Max SLC Standby Current | 240 μ A |
Max SLC Alarm Current | 240 μ A |
Max Wiring Resistance of IDC | 100 Ω |
Max Wiring Capacitance of IDC | 1μF |
Max IDC Voltage | 2.05 VDC |
Max IDC Current | 120 μ A |
EOL Resistor | 5.1K Ω |
Operating Temperature Range | 32̊ to 120̊ F (0̊ to 49̊ C) |
Operating Humidity Range | 0 to 93% (non-condensing) |
Max no. of Module Per Loop | 127 units |
Dimensions | 4.17″ L x 4.17″ W x 1.14″ D |
Mounting Options | UL Listed 2-1/2″ deep 2-gang box or 1-1/2″ deep 4″ square |
box
Shipping Weight| 0.6 lbs
Wiring Diagrams
The two wiring diagrams shown below illustrate how to wire a PAD100-DIM module
as a Class A and Class B circuit. Additionally,
an installation diagram shows how to install the module using a compatible
electrical box.
Figure 3. Example of Installing a PAD100-DIM Using a Compatible Electrical
Box
Figure 4. Example of Wiring a PAD100-DIM with One Class A Circuit
Figure 5. Example of Wiring a PAD100-DIM with Two Class B Circuits
Notes:
-
SLC wiring style supports the Class A, Class B and Class X.
-
IDC wiring style supports Class A and Class B.
-
SLC loop wiring (SLC+, SLC-) and initiating device wiring (IN1, IN2) are power limited.
-
Wiring for terminals SLC+, SLC- are supervised.
-
Wiring for terminals (IN1, IN2) are supervised.
-
This addressable module does not support 2-wire detectors.
-
All wiring is between #12 (max.) and #22 (min.).
-
Wire Preparation – Strip all wires 1/4 inch from their edges as shown here:
- Stripping too much insulation may cause a ground fault.
- Stripping too little may cause a poor connection and subsequently an open circuit.
These instructions do not purport to cover all the details or variations in
the equipment described, nor provide for every possible contingency to be met
in connection with installation, operation and maintenance.
Specifications subject to change without prior notification.
For Technical Assistance contact Potter Electric Signal Company at
866-956-1211.
Actual performance is based on proper application of the product by a
qualified professional.
Should further information be desired or should particular problems arise,
which are not covered sufficiently for the purchaser’s purpose, the matter
should be referred to a distributor in your region.
CUSTOMER SUPPORT
Potter Electric Signal Company, LLC
St. Louis, MO
Phone:800-325-3936
Web:www.pottersignal.com
References
- Fire Alarm Resources | Download fire alarm documents
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>