POTTER PAD100-NAC Notification Module Instruction Manual

October 29, 2023
POTTER

Installation Manual: PAD100-NAC NAC Module

NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the PAD100-NAC module. This module is only compatible with addressable fire systems that utilize the PAD Addressable Protocol.
All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For further information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system operation.

Description

The PAD100-NAC module uses one (1) SLC loop address on an SLC loop. The module provides a programmable source of power to supervise and control one (1) Class B or Class A Notification or one (1) Class B Releasing circuit. The module requires and supervises a 24 VDC auxiliary power connection. The module mounts on either an UL Listed 2-1/2″ deep 2-gang box or 1-1/2″ deep 4″ square box.
The PAD100-NAC includes one red LED to indicate the module’s status. In normal condition, the LED flashes when the device is being polled by the control panel. If the LED blink has been disabled via the programming software, in a normal condition the LED of the device will be off.

Setting the Address

All PAD protocol detectors and modules require an address prior to connection to the panel’s SLC loop. Each PAD device’s address (i.e., detector and/or module) is set by changing the dip switches located on the device. PAD device addresses are comprised of a seven (7) position dip switch used to program each device with an address ranging from 1–127.

POTTER PAD100 NAC Notification Module-

Note: Each “gray” box indicates that the dip switch is “On,” and each “white” box indicates “Off.”
The examples shown below illustrate a PAD device’s dip switch settings: the 1st example shows a device not addressed where all dip switch settings are in the default “Off” position, the 2nd illustrates an addressed PAD device via the dip switch settings.

POTTER PAD100 NAC Notification Module-fig1

Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the SLC or device.

  • Power to the SLC is removed.
  • Field wiring on module is correctly installed.
  • Field wiring has no open or short circuits.

Technical Specifications

Operating Voltage 24.0V
Max SLC Standby Current 200 μ A
Max SLC Alarm Current 200 μ A
Aux Power Required 16-33 VDC
Output Ratings 24 VDC, 2A
EOL Resistor 5.1K Ω
EOL Resistor Diode Stock #3005012 Releasing Applications (Not Included)
Operating Temperature Range 32 to 120 F (0  to 49 C)
Operating Humidity Range 0 to 93% (non-condensing)
Max. no of PAD100-NAC 127 units
Dimensions 4.17″ L x 4.17″ W x 1.14″ D
Mounting Options UL Listed 2-1/2″ deep 2-gang box or

1-1/2″ deep 4″ square box
Shipping Weight| 0.6 lbs

Installation

The wiring diagrams shown below illustrate how to wire a PAD100-NAC module as Class B, Class A and as a Releasing application. Additionally, an installation diagram shows how to install the module using a compatible electrical box.

POTTER PAD100 NAC Notification Module-fig2

POTTER PAD100 NAC Notification Module-fig3

Notes:

  • SLC wiring style supports the Class A, Class X and Class B.
  • NAC wiring style supports Class A and Class B.
  • Wiring for terminals (PWR) are supervised.
  • SLC loop wiring (SLC+, SLC-) and NAC device wiring (RET, OUT) are power limited.
  • Wiring for terminals SLC+, SLC- are supervised.
  • Wiring for terminals (RET, OUT) are supervised.
  • All wiring is between #12 (max.) and #22 (min.).
  • Wire Preparation – Strip all wires 1/4 inch from their edges as shown here:
    – Stripping too much insulation may cause a ground fault.
    – Stripping too little may cause a poor connection and subsequently an open circuit.

NOTICE

It is possible that the internal relay in the PAD100-NAC may be shipped in the non-normal / activated state. To ensure that the internal relay is set to the normal state, connect the module to the SLC loop and reset the control panel before terminating the wiring to the module’s output.
These instructions do not purport to cover all the details or variations in the equipment described, nor provide for every possible contingency to be met in connection with installation, operation and maintenance.
Specifications subject to change without prior notification.
For Technical Assistance contact Potter Electric Signal Company at 866-956-1211.
Actual performance is based on proper application of the product by a qualified professional.
Should further information be desired or should particular problems arise, which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to a distributor in your region.

Potter Electric Signal Company, LLC • St. Louis, MO • Phone: (800) 325-3936 • www.pottersignal.com
Document 5406309-A 02/16
firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals