POTTER SCM-4 Single Contact Module Instruction Manual
- June 9, 2024
- POTTER
Table of Contents
Installation Manual
SCM-4 Single Contact Module
SCM-4 Single Contact Module
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the
Single Contact Module (SCM-4).
This module is only compatible with addressable fire systems that utilize the
Potter/Nohmi addressable protocol.
All terminals are power limited and should be wired in accordance with the
requirements of NFPA 70 (NEC) and NFPA 72 (National Fire Alarm Code). Failure
to follow the wiring diagrams in the following pages will cause the system to
not operate as intended. For further information, refer to the control panel
installation instructions.
The module shall only be installed with listed control panels. Refer to the
control panel installation manual for proper system operation.
Description
The SCM-4 module is used to monitor the contact status of an initiating device
that contains a single normally open contact. The SCM-4 can be programmed in
the panel to supervise a Normally-open contact on the Fire Alarm Control Panel
(FACP). When the Normally-open contact is selected, and the contact is shorted
or closed, the SCM-4 reports its condition to FACP. The SCM-4 supervises an
open circuit of wiring connected to the terminal C and NO.
The SCM-4 employs one red LED to indicate the status. In normal condition, the
LED flashes. When the contact is activated, the LED will turn on constantly.
In case of open circuit, the LED will turn off.
The system allows maximum 13 points illuminating constantly therefore if
additional devices are in the alarm condition, the LED will flash rather than
latch on steady.
Setting the Address
Each addressable module, smoke sensor, heat detector and combination
sensor/detector must have the address set prior connecting the device to the
SLC loop. The address is set using the hand held device programmer.
Prior to connecting a device to the SLC loop, the following precautions should
be taken to prevent potential damage to SLC or device. Verify the following
before proceeding. Document discrepancies and notify appropriate personnel.
- Power in the Addressable Module is removed
- Field wiring on the module is correctly installed.
- Field wiring has no open or short circuits.
Wiring diagram
Note:
- SLC wiring style is applicable to the NFPA Class A (Style 6, 7) & Class B (Style 4).
- IDC wiring style is applicable to the NFPA Class B (Style B).
- SLC loop wiring (S+, S-) and initiating device wiring (C, NO) are power limited.
- Wiring for terminals S+, S- are supervised.
- Wiring for terminals C, NO are supervised.
- Z terminal is not used. (No connection)
- This addressable module does not support 2-wire detector.
- All wiring is between #14 (2.08 mm² ) (max.) and #22 (0.32 mm² ) (min.).
- Wire Preparation
Strip all wires 1/4 inch from their edges as follows:
Note:
a) Stripping too much insulation may cause ground fault
b) Stripping too little may cause a poor connection and subsequently an open
circuit
Installation Instructions
Specifications
No. | Item | Specification |
---|---|---|
1 | Rated voltage range of SLC input power (S+,S-) | 22.0 to 24.0V |
2 | Maximum SLC 24 VDC standby current (S+,S-) | 1mA |
3 | Maximum SLC 24 VDC alarm current (S+,S-) | 250pA |
4 | IDC input circuit wiring style | Class B (Style B) |
5 | End-of-line resistor for IDC | 5.1k0,1/2W |
6 | Maximum wiring resistance of IDC | 1000 |
7 | Maximum wiring capacitance of IDC | 1p F |
8 | Operating temperature range | 32 to 120°F (0 to 49°C) |
9 | Operating humidity range | 0 to 93% (non-condensing) |
10 | Maximum no. of module per loop | 127 units |
11 | Dimensions | 4.17″(106mm) (H) x 4.17″(106mm) (W) x 1.14″(29mm) (D) |
12 | Applicable electrical box for installation | 2-1/2″(64mm)deep 2-gang box |
Standard 4″square box 1-1/2″(38mm)deep box
These instructions do not purport to cover all the details or variations in
the equipment described, nor provide for every possible contingency to be met
in connection with instillation, operation and maintenance.
Specifications subject to change without prior notification
For Technical Assistance contact Potter Electric Signal Company at
800-325-3936
Actual performance is based on proper application of the product by a
qualified professional.
Should further information be desired or should particular problems arise,
which are not covered sufficiently for the purchaser’s purpose, the matter
should be referred to Nohmi or a distributor in your region.
Potter Electric Signal Company, LLC
1609 Park 370 Place, Hazelwood, MO 63042 USA
Telephone: (866)956 -1211
URL: http://www.pottersignal.com