TRANE DXHG Water Source Heat Pump Axiom User Guide

June 9, 2024
Trane

TRANE DXHG Water Source Heat Pump Axiom

TRANE-DXHG-Water-Source-Heat-Pump-Axiom-PRODUCT - Copy

Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

  • Updated EXHG009-0024 and 030-070 models general data table.
  • Updated DXHG024-070 model general data table.
  • Updated Clearance – EXHG/DXHG 0.75 to 6 tons.

Table 1. List of options

Factory Installed Options Field Installed Options
1-inch or 2-inch Ducted Filter Rack 2-inch or 4-inch Ducted Filter Rack
Air-Fi® Wireless Communications Ducted Panel
Deluxe 24V, UC400B Controls Hose Kits (or ship separate hoses and valves)
Factory-mounted Isolation Valve Low, Medium and High Electric Heat
Hot Gas Reheat Pump Module
Matte or Foil Face Insulation Pump Module Hose Kit
MERV 8 or 13 Filters Thermostats or Zone Sensors
Polymer or Stainless Steel IAQ Drain Pan Waterside Economizer
Recessed Unit Mounted Disconnect Switch

Standard or Deluxe Sound Package

Table 2. General data – models EXHG009-024

Model EXHG 009 012 015 018 024
Unit size width x depth x height (in.) 25.5 x 46 x 17.75 25.5 x 46 x 17.75
25.5 x 49 x 18.75 25.5 x 55 x 19.75 25.5 x 55 x 19.75
Compressor type Rotary Rotary Rotary Rotary Scroll
Net weight (lbs.) 173 173 173 269 269
Ship weight (lbs.) 297 297 297 393 393
Filter size nominal (in.) 16 x 19 17 x 19 17 x 20 18 x 23 19 x 23
Water in/out size (FPT) 1/2 1/2 1/2 3/4 3/4
Condensate size (NPTI) 3/4 3/4 3/4 3/4 3/4
Blower wheel Size (in.) 9 x 8 9 x 8 10 x 8 10 x 9 10 x 9

Table 3. General data – models EXHG030-070

Model EXHG 030 036 042 048 060 070
Unit size width x depth x height (in.) 28 x 68 x 21.75 28 x 68 x 21.75
29.38 x 77.75 x 22.13 29.38 x 77.75 x 22.13 29.38 x 86.75 x 22.13 29.38 x

86.75 x 22.13
Compressor type| Scroll| Scroll| Scroll| Scroll| Scroll| Scroll
Net weight (lbs.)| 313| 313| 381| 381| 434| 434
Ship weight (lbs.)| 458| 458| 560| 560| 613| 613
Filter size nominal (in.)| 20 x 30| 20 x 30| 20 x 20 (qty-2)| 20 x 20 (qty-2)| 30 x 20

20 x 20

| 30 x 20

20 x 20

Water in/out size (FPT)| 3/4| 3/4| 1.00| 1.00| 1.00| 1.00
Condensate size (NPTI)| 3/4| 3/4| 3/4| 3/4| 3/4| 3/4
Blower wheel Size (in.)| 11 x 11| 11 x 11| 11 x 11| 11 x 11| 11 x 11| 11 x 11

Table 4. General data – models EXVG009-030

Model EXVG 009 012 015 018 024 030
Unit size width x depth x height (in.) 21.5 x 21.5 x 34 21.5 x 21.5 x 34
21.5 x 23 x 36 21.5 x 26 x 38 21.5 x 26 x 38 24 x 32.5 x 42
Compressor type Rotary Rotary Rotary Rotary Scroll Scroll
Net weight (lbs.) 152 152 188 222 236 280
Ship weight (lbs.) 207 207 246 282 296 343
Filter size nominal (in.) 16 X 19 16 X 19 17 X 20 18 X 23 18 X 23 20 X

30
Water in/out size (FPT)| 0.50| 0.50| 0.75| 0.75| 0.75| 1.00
Model EXVG| 009| 012| 015| 018| 024| 030
---|---|---|---|---|---|---
Condensate size (NPTI)| 0.75| 0.75| 0.75| 0.75| 0.75| 0.75
Blower wheel Size (in.)| 9 x 8| 9 x 8| 10 x 8| 10 x 9| 10 x 9| 11 x 11

Table 5. General data – models EXVG036-070

Model EXVG 036 042 048 060 070
Unit size width x depth x height (in.) 24 x 32.5 x 42 25.4 x 32.5 x 49 25.4
x 32.5 x 49 25.4 x 32.5 x 55 25.4 x 32.5 x 55
Compressor type Scroll Scroll Scroll Scroll Scroll
Net weight (lbs.) 281 329 345 367 432
Ship weight (lbs.) 344 394 410 436 501
Filter size nominal (in.) 20 X 30 27 X 30 27 X 30 30 X 33 30 X 33
Water in/out size (FPT) 1.00 1.00 1.00 1.00 1.00
Condensate size (NPTI) 0.75 0.75 0.75 0.75 0.75
Blower wheel Size (in.) 11 x 11 11 x 11 11 x 11 11 x 11 11 x 11

Table 6. General data – models DXHG024-070

Model DXHG 024 036 048 060 070
Unit size width x depth x height (in.) 25.5 x 55 x 19.75 28 x 68 x 21.75
29.38 x 77.75 x 22.13 29.38 x 86.75 x 22.13 29.38 x 86.75 x 22.13
Compressor type Two-Stage Scroll Two-Stage Scroll Two-Stage Scroll Two-
Stage Scroll Two-Stage Scroll
Net weight (lbs.) 269 313 381 434 434
Ship weight (lbs.) 393 458 560 613 613
Filter size nominal (in.) 18 x 23 20 x 30 20 x 20 (qty-2) 30 x 20

20 x 20

| 30 x 20

20 x 20

Water in/out size (FPT)| 3/4| 3/4| 1.00| 1.00| 1.00
Condensate size (NPTI)| 3/4| 3/4| 3/4| 3/4| 3/4
Blower wheel Size (in.)| 10 x 9| 11 x 11| 11 x 11| 11 x 11| 11 x 11

Table 7. General data – models DXVG024-070

Model DXVG 024 036 048 060 070
Unit size width x depth x height (in.) 21.5 x 26 x 38 24 x 32.5 x 42 25.4 x
32.5 x 49 25.4 x 32.5 x 55 25.4 x 32.5 x 55
Compressor type Two-Stage Scroll Two-Stage Scroll Two-Stage Scroll Two-
Stage Scroll Two-Stage Scroll
Net weight (lbs.) 236 279 354 371 437
Ship weight (lbs.) 296 342 419 440 506
Filter size nominal (in.) 18 x 23 23 x 30 27 x 30 30 x 33 30 x 33
Water in/out size (FPT) 0.75 1.00 1.00 1.00 1.00
Condensate size (NPTI) 0.75 0.75 0.75 0.75 0.75
Blower wheel Size (in.) 10 x 9 11 x 11 11 x 11 11 x 11 11 x 11

Table 8. ANSI/AHRI/ASHRAE/ISO13256-1 WLHP, GWHP and GLHP performance – 0.75 to 6 tons

Model

|

Rated GPM

|

Rated CFM

| Water Loop Heat Pump| Ground Water Heat Pump| Ground Loop Heat Pump
---|---|---|---|---|---
Cooling 86°F| Heating 68°F| Cooling 59°F| Heating 50°F| Full Cool 77°F| Full Heat 32°F
Capacity Btuh|

EER

| Capacity Btuh|

COP

| Capacity Btuh|

EER

| Capacity Btuh|

COP

| Capacity Btuh|

EER

| Capacity Btuh|

COP

EXV/H009| 2.25| 285| 7900| 16.10| 9900| 5.6| 8800| 25.0| 8200| 4.8| 8300| 18.8| 6100| 3.7
EXV/H012| 3.00| 380| 11600| 16.40| 15200| 5.8| 13700| 27.9| 12300| 5.0| 12300| 19.5| 9300| 4.0
EXV/H015| 3.75| 475| 15100| 16.10| 18700| 5.3| 17000| 25.8| 15300| 4.6| 15800| 19.0| 12100| 3.8
EXV/H018| 4.50| 570| 18800| 17.60| 23600| 5.7| 21100| 28.7| 18800| 4.9| 19600| 20.6| 14600| 4.1
EXV/H024| 6.00| 760| 24600| 17.40| 32100| 5.7| 27400| 27.2| 25900| 5.0| 25600| 20.3| 19500| 3.9
EXV/H030| 7.50| 950| 31400| 17.80| 38400| 5.8| 35000| 27.2| 31000| 5.0| 32800| 20.7| 23600| 4.1
EXV/H036| 9.00| 1140| 35500| 17.60| 43100| 5.8| 39400| 26.5| 35000| 5.0| 37100| 20.4| 27200| 4.1
EXV/H042| 10.50| 1330| 38400| 18.00| 48000| 6.4| 43300| 27.5| 38500| 5.5| 40500| 21.1| 29400| 4.3
EXV/H048| 12.00| 1520| 45400| 17.70| 55600| 6.1| 50400| 26.4| 44800| 5.3| 47100| 20.3| 34600| 4.3
EXV/H060| 15.00| 1900| 55700| 17.50| 69000| 5.9| 60800| 25.7| 55900| 5.1| 57700| 20.1| 42900| 4.1
EXV/H070| 17.50| 2215| 63800| 17.30| 82100| 5.40| 68900| 24.9| 66900| 4.8| 66100| 19.80| 52000| 4.1

Note: Rated in accordance ANSI/AHRI/ASHRAE/ISO13256-1. Certified conditions are 80.6°F DB/66.2°F WB EAT in cooling and 68°F DB/59°F WB EAT in heating. Entering liquid temperature in cooling is 86°F for Water Loop, 77°F for Ground Loop (full load), 68°F for Ground Loop (part load), and 59°F for Ground Water. Entering liquid temperature in heating is 68°F for Water Loop, 32°F for Ground Loop (full load), 41°F for Ground Loop (part load), and 50°F for Ground Water.

Table 9. ANSI/AHRI/ASHRAE/ISO13256-1 WLHP, GWHP and GLHP performance – 2 to 6 tons

Model

|

Load

|

Rated GPM

|

Rated CFM

| Water Loop Heat Pump| Ground Water Heat Pump| Ground Loop Heat Pump
---|---|---|---|---|---|---
Cooling 86°F| Heating 68°F| Cooling 59°F| Heating 50°F| Full Cool 77°F| Full Heat 32°F
Capacity Btuh|

EER

| Capacity Btuh|

COP

| Capacity Btuh|

EER

| Capacity Btuh|

COP

| Capacity Btuh|

EER

| Capacity Btuh|

COP

DXV/H024| Full| 6.0| 760| 24700| 16.8| 32100| 5.5| 27500| 24.4| 25700| 4.9| 25900| 19.2| 19400| 3.9
DXV/H024| Part| 6.0| 608| 18500| 17.7| 24100| 5.9| 20500| 28.3| 18900| 4.9| 20000| 24.5| 16300| 4.3
DXV/H036| Full| 9.0| 1140| 33000| 17.3| 40900| 5.9| 37100| 25.1| 32900| 5.1| 34500| 19.7| 25500| 4.1
DXV/H036| Part| 9.0| 912| 24500| 18.3| 30500| 6.3| 27600| 29.3| 24300| 5.2| 26600| 25.2| 21100| 4.5
DXV/H048| Full| 12.0| 1520| 45200| 17.9| 55200| 6.1| 50400| 26.4| 44400| 5.3| 46600| 20.6| 34500| 4.3
DXV/H048| Part| 12.0| 1216| 32800| 18.7| 40000| 6.6| 36900| 31.2| 31900| 5.3| 35700| 26.7| 28000| 4.7
DXV/H060| Full| 15.0| 1900| 52100| 17.6| 63900| 6.0| 56600| 24.8| 51700| 5.2| 53900| 19.9| 39800| 4.2
DXV/H060| Part| 15.0| 1520| 38300| 18.7| 47300| 6.6| 42000| 29.9| 37800| 5.4| 41000| 25.8| 32400| 4.6
DXV/H070| Full| 17.5| 2215| 64400| 17.3| 82700| 5.4| 69100| 23.8| 67400| 4.8| 66800| 19.6| 52900| 4.0
DXV/H070| Part| 17.5| 1772| 47100| 18.9| 59700| 6.0| 51100| 29.7| 48000| 5.0| 50000| 25.6| 42000| 4.4

Note: Performance data EXVG 0.5 Ton or 0.75 Ton Rated in accordance with ANSI/AHRI/ASHRAE/ISO13256-1. Certified conditions are 80.6°F DB/66.2°F WB EAT in cooling and 68°F DB/59°F WB EAT in heating. Entering liquid temperature in cooling is 86°F for Water Loop, 77°F for Ground Loop (full load), 68°F for Ground Loop (part load), and 59°F for Ground Water. Entering liquid temperature in heating is 68°F for Water Loop, 32°F for Ground Loop (full load), 41°F for Ground Loop (part load), and 50°F for Ground Water.

*Table 10. Electrical data – 0.75 to 6 tons, EX009-070**

Model No.| Unit Volts| Blower Motor HP| Minimum Circuit Ampacity| Maximum Overcurrent Protective Device
---|---|---|---|---
DXH/DXV024| 208-230/60/1| 1/2| 17/17| 25/25
DXH/DXV024| 265/60/1| 1/2| 13| 20
DXH/DXV024| 208-230/60/3| 1/2| 10/10| 15/15
DXH/DXV024| 460/60/3| 1/2| 6| 15
DXH/DXV036| 208-230/60/1| 3/4| 19/19| 30/30
DXH/DXV036| 265/60/1| 3/4| 15| 20
DXH/DXV036| 208-230/60/3| 3/4| 13/13| 20/20
DXH/DXV036| 460/60/3| 1| 7| 15
DXH/DXV048| 208-230/60/1| 1| 25/25| 40/40
DXH/DXV048| 208-230/60/3| 1| 21/21| 30/30
DXH/DXV048| 460/60/3| 1| 10| 15
DXH/DXV060| 208-230/60/1| 1| 31/31| 50/50
DXH/DXV060| 208-230/60/3| 1| 22/22| 35/35
DXH/DXV060| 460/60/3| 1| 10| 15
DXH/DXV070| 208-230/60/1| 1| 39/39| 60/60
DXH/DXV070| 208-230/60/3| 1| 26/26| 40/40
DXH/DXV070| 460/60/3| 1| 12| 15
Model No.| Unit Volts| Blower Motor HP| Minimum Circuit Ampacity| Maximum Overcurrent Protective Device
---|---|---|---|---
EXH/EXV018| 208-230/60/1| 1/2| 12/12| 20/20
EXH/EXV018| 265/60/1| 1/2| 10| 15
EXH/EXV024| 208-230/60/1| 1/2| 19/19| 30/30
EXH/EXV024| 265/60/1| 1/2| 13| 20
EXH/EXV024| 208-230/60/3| 1/2| 11/11| 15/15
EXH/EXV024| 460/60/3| 1/2| 6| 15
EXH/EXV030| 208-230/60/1| 3/4| 20/20| 30/30
EXH/EXV030| 265/60/1| 3/4| 16| 25
EXH/EXV030| 208-230/60/3| 3/4| 13/13| 20/20
EXH/EXV030| 460/60/3| 3/4| 7| 15
EXH/EXV036| 208-230/60/1| 3/4| 23/23| 35/35
EXH/EXV036| 265/60/1| 3/4| 17| 25
EXH/EXV036| 208-230/60/3| 3/4| 15/15| 20/20
EXH/EXV036| 460/60/3| 1| 7| 15
EXH/EXV042| 208-230/60/1| 3/4| 25/25| 40/40
EXH/EXV042| 208-230/60/3| 3/4| 17/17| 25/25
EXH/EXV042| 460/60/3| 1| 9| 15
EXH/EXV048| 208-230/60/1| 1| 25/25| 40/40
EXH/EXV048| 208-230/60/3| 1| 20/20| 30/30
EXH/EXV048| 460/60/3| 1| 9| 15
EXH/EXV060| 208-230/60/1| 1| 31/31| 50/50
EXH/EXV060| 208-230/60/3| 1| 22/22| 35/35
EXH/EXV060| 460/60/3| 1| 10| 15
EXH/EXV070| 208-230/60/1| 1| 39/39| 60/60
EXH/EXV070| 208-230/60/3| 1| 26/26| 40/40

Clearances – EXHG/DXHG 0.75 to 6 tons

TRANE-DXHG-Water-Source-Heat-Pump-Axiom-FIG-1

A minimum 14-inch clearance for servicing the unit is required for all EXH 0.75 to 6 tons configurations from other mechanical and electrical equipment (where shown) to enable panel removal from the unit for service/maintenance ability. The optimum clearance required is 20 inches.

TRANE-DXHG-Water-Source-Heat-Pump-Axiom-FIG-2

A 24-inch clearance from other mechanical and electrical equipment (where shown) is recommended for most unit configurations. This will enable panel removal from the unit for service/maintenance. The 24-inch side clearance on EXVG/DXVG 0.75-6T models is for optimal access only. Side clearance is not a requirement as most components can be accessed from the front of the unit.

A 1-inch minimum clearance between the filter rack and any obstacle is required for units in a free return application to provide proper air flow to the air-to-refrigerant coil. A 12-inch minimum clearance between the filter rack and any obstacle should be provided to properly attached ductwork.The 1-inch dimension shown in the back of the unit represents the supply duct collar for the back supply option. This clearance is needed to clear these flanges.

Trane – by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

WSHP-PRC030C-EN 01 Mar 2023 Supersedes WSHP-PRC030B-EN (Oct 2021)

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Trane User Manuals

Related Manuals