EATON NZMB Thermal Magnetic Circuit Breaker Instruction Manual

June 9, 2024
EATON

IL01203004Z
NZMB Thermal Magnetic Circuit Breaker
Instruction Manual

NZMB(C)(N)(S)(H)1(-4)-A(M)(S)…
NZMB(N)1-A(AF)…-NA
NZMB(N)1-S…-CNA
(P)N1-… NS1-…-NA

NZMB Thermal Magnetic Circuit Breaker

Electric current! Danger to life!
Installation, commissioning and maintenance work must be carried out by qualified personnel only.

Minimum clearance/direction of blow-out

EATON NZMB Thermal Magnetic Circuit Breaker - 1

Terminals

EATON NZMB Thermal Magnetic Circuit Breaker - 2

1 x 10 – 70 mm²| 1 x 10 – 16mm²| ≧ 2 x 9 x 0.8 mm
(≧ 2 x 0.35“ x 0.03“)
---|---|---
2 x 6 – 25 mm²| 2 x 6 – 16 mm²|
1 x AWG 4 – AWG 2/0| 1 x AWG 12 – AWG 6|
2 x AWG 10 – AWG 4| 2 x AWG 10 – AWG 6|

UL/CSA = Cu only, Ampacity per 75° C Table.
Wiring terminations circuit breaker type NZM…1…-NA (CNA)
Wiring terminations molded case switch type N(S)1…-NA

Connector type| Wire size| Wire 75° C| Max. A-Rating| Tightening-Torque
---|---|---|---|---
1)NZM1-XKC| 1 x AWG 2/0 – 12 2xAWG 4 -10| Cu only| 125| 9 Nm (80 lb-in) 6 Nm (53 lb-in) (AWG 8 – 12)
NZM1-XKA| 1 x AWG 3/0 – 6| Cu only| 125| 15 Nm (133 lb-in)
NZM1-XKS| 1 x AWG 2/0 – 12 2xAWG 4 -10| Cu only| 125| 9 Nm (80 lb-in)
2)Integrated Auxiliary Terminal| 1 x AWG 12 – 18| Cu only| | 1.2 Nm (11 lb-in)

  1. Connector Type NZM1-XKC supplied standard on all NZM1 circuit breakers and switches.
  2.  Integrated Auxiliary Terminal on Connector Type NZM1-XKA only.

EATON NZMB Thermal Magnetic Circuit Breaker - 3

Settings

EATON NZMB Thermal Magnetic Circuit Breaker - 4

Note: On certain models with UL/CSA labeling the thermal trip setting is fixed and only the magnetic trip (instantaneous) setting is adjustable.

Accessories

EATON NZMB Thermal Magnetic Circuit Breaker - 5

Notes on mounting and wiring Auxiliary Switches for UL/CSA labeled models:

  • M22-K(10)(01) have screw terminals. M22-CK(10)(01)(20)(02)(11) have clamp terminals.
  • Switch modules are snapped into place at the locations shown in the diagrams that follow.
  • Switches will function as either “standard” or “trip/alarm” contacts depending on their mounting location.
  • Location “HIN” refers to standard operation. Location “HIA” refers to “trip/alarm” operation.
  • Follow the numbering and wiring scheme provided above depending on the contact location and function. (N.O. or N.C.)
  • Permissible contact configuration: 1 HIA and/or 2 HIN.

Note:
After mounting of the M22… switch is complete, check off the appropriate box on the auxiliary switch label provided on the side of the breaker or switch.
-NA -CNA (UL/CSA)

**** Ith = Ie
Ue (V) Ie (A)
600 AC 5 A
250 DC 1 A

Pilot Duty Ratings: B 600, Q 300 Above 300 V AC Same polarity

EATON NZMB Thermal Magnetic Circuit Breaker - 6

EATON NZMB Thermal Magnetic Circuit Breaker - 7

Test

EATON NZMB Thermal Magnetic Circuit Breaker - 8

EATON NZMB Thermal Magnetic Circuit Breaker - 9

EATON NZMB Thermal Magnetic Circuit Breaker - 10

Eaton Electric Ltd., P.O. Box 554, Abbey Park, Southampton Road, Titchfield, PO14 4QA, United Kingdom
USA:
Eaton.com/eatoncare
+1877-386-2273
Eaton.com/aftersales
07/22 IL01203004Z
Eaton.com/recycling
© 2002 Eaton Industries GmbH

Documents / Resources

| EATON NZMB Thermal Magnetic Circuit Breaker [pdf] Instruction Manual
NZMB Thermal Magnetic Circuit Breaker, NZMB, Thermal Magnetic Circuit Breaker, Magnetic Circuit Breaker, Circuit Breaker, Breaker
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals