HEALTHCARE LIGHTING HST LED Surgical Suite Recessed Lighting Instruction Manual

June 9, 2024
HEALTHCARE LIGHTING

HEALTHCARE LIGHTING HST LED Surgical Suite Recessed Lighting

Healthcare LED TROFFER GRID
(HSTLED Family)
Healthcare Lighting 3 Kilmer Rd, Edison, NJ 08817
1-855-868-6980
www.healthcare-lighting.com

IMPORTANT SAFETY INSTRUCTIONS

READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards please read all warnings and instructions included with and on the fixture box and all fixture labels. Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions. Installation and service of luminaires should be performed by a qualified licensed electrician. Maintenance of the luminaires should be performed by person(s) familiar with the luminaires’ construction and operation and any hazards involved. Regular fixture maintenance programs are recommended. It will occasionally be necessary to clean the outside of the refractor/lens. Frequency of cleaning will depend on ambient dirt level and minimum light output which is acceptable to user. Refractor/lens should be washed in a solution of warm water and any mild, non-abrasive household detergent, rinsed with clean water and wiped dry. Should optical assembly become dirty on the inside, wipe refractor/lens and clean in above manner, replacing damaged gaskets as necessary.

DO NOT INSTALL DAMAGED PRODUCT! This luminaire has been properly packed so that no parts should have been damaged during transit. Inspect to confirm. Any part damaged or broken during or after assembly should be replaced. If the lamp is marked (Hg) it contains Mercury. Follow all disposal laws. See www.lamprecycle.org. These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meet in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s or owner’s purposes, this matter should be referred to Acuity Brands Lighting, Inc.

WARNING
RISK OF ELECTRIC SHOCK 

  • Disconnect or turn off power before installation or servicing.
  • Verify that supply voltage is correct by comparing it with the luminaire label information.
  • Make all electrical and grounded connections in accordance with the National Electrical Code (NEC) and any applicable local code requirements.
  • All wiring connections should be capped with UL approved recognized wire connectors.

CAUTION RISK OF INJURY

  • Wear gloves and safety glasses at all times when removing luminaire from carton, installing, servicing or performing maintenance.
  • Avoid direct eye exposure to the light source while it is on.

WARNING RISK OF BURN

  • Allow lamp/fixture to cool before handling. Do not touch enclosure or light source.
  • Do not exceed maximum wattage marked on luminaire label.
  • Follow all manufacturer’s warnings, recommendations and restrictions for: driver type, burning position, mounting locations/methods, replacement and recycling.

CAUTION RISK OF FIRE

  • Keep combustible and other materials that can burn, away from lamp/lens.
  • Do not operate in close proximity to persons, combustible materials or substances affected by heat or drying.

CAUTION: RISK OF PRODUCT

  • Never connect components under load.
  • Do not mount or support these fixtures in a manner that can cut the outer jacket or damage wire insulation.
  • Unless individual product specifications deem otherwise: Never connect an LED product directly to a dimmer packs, occupancy sensors, timing devices, or other related control devices. LED fixtures must be powered directly off a switched circuit.
  • Unless individual product specifications deem otherwise: Do not restrict fixture ventilation. Allow for some volume of airspace around fixture. Avoid covering
  • LED fixtures with insulation, foam, or other material that will prevent convection or conduction cooling.
  • Unless individual product specifications deem otherwise: Do not exceed fixtures maximum ambient temperature.
  • Only use fixture in its intended location.
  • LED products are Polarity Sensitive. Ensure proper Polarity before installation.
  • Electrostatic Discharge (ESD): ESD can damage LED fixtures. Personal grounding equipment must be worn during all installation or servicing of the unit.
  • Do not touch individual electrical components as this can cause ESD, shorten lamp life, or alter performance.
  • Some components inside the fixture may not be serviceable. In the unlikely event your unit may require service, stop using the unit immediately and contact an ABL representative for assistance.
  • Always read the fixtures complete installation instructions prior to installation for any additional fixture specific warnings.

Failure to follow any of these instructions could void product warranties.
For a complete listing of product Terms and Conditions, please visit www.acuitybrands.com. HEALTHCARE-LIGHTING-
HST-LED-Surgical-Suite-Recessed-Lighting-FIG-1Acuity Brands Lighting, Inc. assumes no responsibility for claims arising out of improper or careless installation or handling of its products.

HSTLED GRID INSTALLATION INSTRUCTIONS

WARNING: THIS LIGHT FIXTURE IS DESIGNED FOR INSTALLATION IN A T-GRID-TYPE SUSPENDED CEILING. THE FIXTURE MUST BE SUSPENDED FROM STRUCTURAL MEMBERS OF THE BUILDING ABOVE THE CEILING GRID. IT IS THE RESPONSIBILITY OF THE PERSON INSTALLING THE LIGHT FIXTURE TO ENSURE THAT THE MATERIALS, HARDWARE AND BUILDING STRUCTURAL MEMBERS THAT ARE SELECTED WILL SUPPORT THE LIGHT FIXTURE(S) AND THAT THEY MEET ALL APPLICABLE BUILDING AND SAFETY CODES. MUST be installed by certified electrician.
The HSTLED can mount in standard grids ranging from 9/16” to 1 ½” wide (Figure 1). Grid spacing MUST BE 48” x 24” center to center for HSTLED24 and 24”x 24” center to center for HSTLED22.
Note hinge side of fixture should be facing away from bedHEALTHCARE-
LIGHTING-HST-LED-Surgical-Suite-Recessed-Lighting-FIG-2 The HSTLED Troffer cannot be supported by grid alone. Tie wire or threaded rods MUST BE USED to support the
weight of the fixture.

Ensure end flanges of fixture are properly secured to housing with nuts before lifting into place. For ease of installation remove door by opening door perpendicular to housing, unscrew nuts holding safety cable to housing, then lift and remove from hinge. The fixture can be secured to plenum by two methods, threaded rod or suspension wire.

Threaded Rod
Step 1
Remove the four thumb nuts that retain side covers (Figure 2).

Step 2
With side covers removed knock out the four 13/32” diameter knockouts at the four corners of the housing (Figure 3).
Step 3
Threaded rod up to 3/8” diameter may be used to hang fixture. Secure threaded rod to floor of fixture with a washer and nut on the inside and outside of the fixture floor (Figure 4). Tighten nuts against each other. Repeat in all four corners. Secure upper ends of threaded rods to building structure with suitable attachment means. For spacing between knockouts see Table 1 and Figure 5.HEALTHCARE-LIGHTING-HST-LED-Surgical-Suite-Recessed-
Lighting-FIG-4

Fixture Length Spacing Width Spacing
HSTLED24 38” 17 1/4”
HSTLED22 17 1/2” 17 1/4”

Step4
With fixture secured to ceiling reinstall side covers and install door on housing hinge. Attach the two safety cables and one ground wire from the door to the housing before screwing door close.

Suspension Wire
Step 1
Knock out the eight (two in each corner) 0.25”x0.50” oblong knockouts. For spacing between knockouts see Table 2 and Figure 6.

Fixture Length Spacing Width Spacing
HSTLED24 44 1/4” 18 1/4”
HSTLED22 20 1/4” 18 1/4”

Step 2
Pass suitable sized wire through oblongs from the outside and return it though the adjacent oblong from the inside. Wrap the end of the wire around the supporting length to secure fixture to building support (Figure 7)

Care should be taken to avoid trapping an electrical wire in the suspension wire loop inside the fixtureHEALTHCARE-LIGHTING-HST-LED-
Surgical-Suite-Recessed-Lighting-FIG-7

Step 3
With fixture secured to ceiling reinstall side covers and install door on housing hinge. Attach the two safety cables and one ground wire from the door to the housing before screwing door close.
Swing Arms
This fixture comes with four Swing Arms that can be used to level fixture. To bring the arms down screw clockwise from below using a flat head screw driver (Figure 8). The swing arm can travel roughly 1.25” to accommodate various ceiling support systems (Figure 9). Healthcare Lighting 3 Kilmer Rd, Edison, NJ 08817 www.healthcare-lighting.com