STEGO Type STO-STS 011 Mechanical Thermostat Instruction Manual
- June 9, 2024
- STEGO
Table of Contents
STEGO Type STO-STS 011 Mechanical Thermostat
INTRODUCTIONS
|
---|---
There is a risk of personal injury and equipment damage if the connection
values are not observed or polarity is incorrect
WIRING DIGRAM
250V AC, 10(2)A 120V AC, 15(2)A
max. 90%rH
20 … +80°C (-4 … +176°F)
0.05kg
USAGE
The temperature controllers are used for controlling heaters, coolers, filter
fans and heat exchangers in stationary, sealed housings for electrical
devices. In addition, they can also be used as switching contacts(min. 24V,
20mA) for signal devices used as low- or high-temperature alarms.
Versions
- Normally closed contact (switching contact opens at rising temperature)
- Normally open contact (switching contact closes at rising temperature)
Safety considerations
- Installation must only be performed by qualified electrical technicians in observation of the respective national power-supply guidelines (IEC 60364).
- The safety measures according to VDE 0100 are to be ensured.
- The technical specifications on the type plate must be strictly observed!
- No changes or modifications must be made to the device.
- In case of apparent damage or malfunction, the device may not be repaired or put into operation. (Dispose of device.)
- The contact system of the regulator is exposed to environmental influences. This can result in a change in the contact resistance, which can lead to a drop in voltage and/or self-warming of the contacts.
- Notice: From an ambient temperature in the electric cabinet of 70°C (158°F), a heat-resistant cable must be used to connect the thermostat.
Installation guidelines
- The regulator should be installed in the upper area of the electric cabinet as far as possible from heaters or other heat-generating components.
- The device must not be covered.
- The device must not be operated in environments with aggressive atmospher
- Mode of operation: 1.B
- The device must only be operated in an environment that ensures contamination class 2 (or better) in accordance with IEC 61010. Contamination class 2 means that only non-conductive contamination may occur. However, it is likely that there will occasionally be temporary conductivity caused by condensation.
Technical Data
- Sensor: thermo bimetal
- Type of contact: snap-action contact
- Overvoltage category III.
Setting recommendations
Hysteresis: 4K (± 3K tolerance). When setting the temperature of the
thermostat, the largest possible hysteresis must be allowed for.
Example
- Normally closed contact: Set value minus max. hysteresis (7K) = switch on point for heater.
- Normally open contact: Set value minus max. hysteresis (7K) = switch off point for fan.
Notice
The manufacturer accepts no liability in the case of failure to observe this
brief instruction, improper use and changes or damage to the device.