BEKA AG334 Externally Powered Pulse Input Rate Totalizer User Guide
- June 9, 2024
- BEKA
Table of Contents
AG334 Externally Powered Pulse Input Rate Totalizer
User Guide APPLICATION GUIDE AG334
Externally powered pulse input Rate Totalisers
For models with an ‘E’ or ‘G’ suffix
Externally powered pulse input Rate Totalisers
Introduction
This Application Guide is intended to aid the selection of the most suitable
pulse input Rate Totaliser from the extensive range of models manufactured by
BEKA associates. The guide also contains flow measurement background
information and configuration examples.
This guide does not contain detailed system design or stepby-step
configuration information which are contained in the instruction manual for
each model. Detailed installation and certification information for use in
hazardous areas is also contained in the instruction manual for each model
which can be viewed on the BEKA website at
www.beka.co.uk
Each output pulse from a flowmeter or flow transducer represents a defined
volume that has passed through the flowmeter. The total number of pulses
therefore represents the total volume and the pulse frequency represents the
rate of flow passing through the flowmeter. All BEKA pulse input Rate
Totalisers have similar functions and are able to calculate and display the
total flow and the rate of flow of most pulse output flowmeters.
The BEKA Rate Totaliser range includes field and panel mounting models for
general purpose applications and for use in gas and dust hazardous areas. All
models can be supplied with a wide range of factory fitted options including
display backlights, alarm outputs and isolated pulse and current outputs for
retransmission applications. Some models have two pulse inputs enabling the
instrument to calculate and display the sum or difference of the total flow
and rate of flow passing through two flowmeters.
All models are configured and calibrated via four push buttons using a common
configuration menu. Although easy to configure on-site without the need for
test equipment, Rate Totalisers can be supplied configured and ready for
installation with a printed slide-in scale card showing customer specified
information for no additional charge.
BEKA also manufacture loop powered 4/20mA Rate Totalisers which have similar
functions and are described in a separate Application Guide.
Model | BA334E | BA334G | BA384E | BA384G |
---|---|---|---|---|
Some shown with optional backlight | ||||
Enclosure material, size and IP rating | Field GRP 141 x 212mm IP66 | Field | ||
GRP 122 x 120mm IP66 | Field GRP 141 x 212mm IP66 | Field GRP 122 x 120mm IP66 | ||
Number of M20 cable entries | 3 | 2 | 3 | 2 |
Separate terminal compartment | Yes | No | Yes | No |
Display | Primary: 8 digits 18mm high Secondary: 6 digits 12mm high | |||
Number of inputs | 1 | 2 |
Certification International IECEx
Gas| Ex ia IIC T5 Ga
-40°C ≤ Ta ≤ +70°C| Ex ia IIC T5 Ga
-40°C ≤ Ta ≤ +70°C| Ex ia IIC T5 Ga
-40°C ≤ Ta ≤ +70°C| Ex ia IIC T5 Ga
-40°C ≤ Ta ≤ +70°C
Dust| N/A| Ex ia IIIC T80°C Da
-40°C ≤ Ta ≤ +60°C| N/A| Ex ia IIIC T80°C Da
-40°C ≤ Ta ≤ +60°C
Certification Europe ATEX
Gas| Group II Category 1G Ex ia IIC T5 Ga
-40°C ≤ Ta ≤ +70°C| Group II Category 1GD Ex ia IIC T5 Ga
-40°C ≤ Ta ≤ +70°C| Group II Category 1G Ex ia IIC T5 Ga
-40°C ≤ Ta ≤ +70°C| Group II Category 1G Ex ia IIC T5 Ga
-40°C ≤ Ta ≤ +70°C
Dust| N/A| Ex ia IIIC T80°C Da
-40°C ≤ Ta ≤ +60°C| N/A| Group II Category 1D Ex ia IIIC T80°C Da
-40°C ≤ Ta ≤ +60°C
Certification USA ETL| Class I Div 1 Gp A, B, C, D T5 Class II Div 1 Gp
E, F, G. Class III Div 1
Class I Zone 0 AEx ia IIC T5 Ga -40°C ≤ Ta ≤ 70°C
Certification Canada cETL| Class I Div 1 Gp A, B, C, D T5 Class II Div 1
Gp E, F, G. Class III Div 1
Ex ia IIC T5 Ga
-40°C ≤ Ta ≤ 70°C
Options – must be specified when indicator is ordered|
Backlight Alarms| Included Included| Yes Yes| Included Included| Yes Yes
4/20mA output Pulse output| Included Included| Yes Included| Included
Included| Yes Included
Accessories|
Pipe mounting kit
Panel mounting kit
Unsealed
Sealed| BA393
N/A
N/A| BA393G
BA394G
BA494G| BA393
N/A
N/A| BA393G
BA394G
BA494G
BA334NG| BA384NG| BA534G| BA584G
---|---|---|---
| | |
Field GRP 122 x 120mm IP66| Field GRP 122 x 120mm IP66
2
No| No
Primary: 8 digits 18mm high Secondary: 6 digits 12mm high
1| 2| 1| 2
Ex nA ic IIC T5 Gc
-40°C ≤ Ta ≤ +60°C|
Ex ic tc IIIC T80°C Dc
-40°C ≤ Ta ≤ +60°C
Ex ic codes only refer to push button contacts|
Group II Category 3G Ex nA ic IIC T5 Gc
-40°C ≤ Ta ≤ +60°C|
Group II Category 3D Ex ic tc IIIC T80°C Dc
-40°C ≤ Ta ≤ +60°C
Ex ic codes only refer to push button contacts| Not Certified
General purpose applications only
Class I Zone 2 AEx nA ic IIC T5 Gc Zone 22 AEx ic tc IIIC T80°C Dc -40°C ≤ Ta
≤ 60°C
Ex ic codes only refer to push button contacts|
Ex nA ic IIC T5 Gc Ex n IIC T5 Gc
Ex ic tc IIIC T80°C Dc
Class III Div 2 Class II Div 2 Gp F, G
-40°C ≤ Ta ≤ 60°C
Ex ic codes only refer to push button contacts|
|
Yes Yes| Yes Yes| Yes Yes| Yes Yes
Yes Included| Yes Included| Yes Included| Yes Included
|
BA393G
BA394G
N/A| BA393G
BA394G
N/A| BA393G
BA394G
BA494G| BA393G
BA394G
BA494G
Model| BA337E| BA338E| BA388E| BA337E-SS
---|---|---|---|---
Some shown with optional backlight| | | |
Enclosure material & size| Panel Noryl 96 x 48 mm| Panel Noryl 144 x 72 mm|
Rugged panel
316 S/S 105 x 60 mm
Protection| Front IP66, rear IP20
Display| Primary: 8 digits 9mm high Secondary: 6 digits 6mm high| Primary: 8
digits 18mm high Secondary: 6 digits 12mm high| Primary:
8 digits 9mm high Secondary: 6 digits 6mm high
Number of inputs| 1| 2| 1
Certification International IECEx Gas| Ex ia IIC T5 Ga -40°C
≤ Ta ≤ +70°C| Ex ia IIC T5 Ga -40°C ≤ Ta ≤ +60°C
Dust| N/A| Ex ia IIIC T80°C Da -40°C ≤ Ta ≤ +60°C *
Certification Europe ATEX Gas| Group II Category 1G
Ex ia IIC T5 Ga -40°C ≤ Ta ≤ +70°C| Group II Category 1G Ex ia IIC T5 Ga
-40°C ≤ Ta ≤ +60°C
Dust| N/A| Group II Category 1D Ex ia IIIC T80°C Da -40°C ≤ Ta ≤ +60°C *
Certification USA ETL| Class I Div 1 Gp A, B, C, D T5 Class II Div 1 Gp
E, F, G. Class III Div 1 Class I Zone 0 AEx ia IIC T5 Ga-40°C ≤ Ta ≤ 70°C
| Zone 20 AEx ia IIIC T80°C Da
-40°C ≤ Ta ≤ 60°C *
Certification Canada cETL| Class I Div 1 Gp A, B, C, D T5 Class II Div
1 Gp E, F, G. Class III Div 1 Ex ia IIC T5 Ga
-40°C ≤ Ta ≤ 70°C| Ex ia IIIC T80°C Da
-40°C ≤ Ta ≤ 60°C *
Options – must be specified when indicator is ordered|
Backlight Alarms
4/20mA output
Pulse output| Yes Yes
Yes #
Yes| Yes Yes
Yes
Included| Yes Yes
Yes
Included| Yes Yes
Yes #
Yes
Accessories|
Rear sealing kit| BA495| N/A| N/A| BA495
BA337NE| BA537E| BA538E| BA588E| BA537E-SS
---|---|---|---|---
| | | |
Rugged panel 316 S/S 105 x 60 mm| Panel Noryl 96 x 48 mm| Panel Noryl 144 x 72
mm| Rugged panel 316 S/S105 x 60 mm
Front IP66, rear IP20| Front IP66, rear IP20
Primary: 8 digits 9mm high
Secondary: 6 digits 6mm high| Primary: 8 digits 9mm high
Secondary: 6 digits 6mm high| Primary: 8 digits 18mm high
Secondary: 6 digits 12mm high| Primary: 8 digits 9mm high
Secondary: 6 digits 6mm high
1| 1| 2| 1
Ex nA ic IIC T5 Gc -40°C ≤ Ta ≤ +60°C| __
__
Not Certified
General purpose applications only
Ex ic tc IIIC T80°C Dc IP66 -40°C ≤ Ta ≤ +60°C
Ex ic codes only refer to push button contacts
Group II Category 3G Ex nA ic IIC T5 Gc-40°C ≤ Ta ≤ +60°C
Group II Category 3D Ex ic tc IIIC T80°C Dc -40°C ≤ Ta ≤ +60°C
Ex ic codes only refer to push button contacts
Class I Zone 2 AEx nA ic IIC T5 Gc Zone 22
AEx ic tc IIIC T80°C Dc -40°C ≤ Ta ≤ 60°C
Ex ic codes only refer to push button contacts
Ex nA ic IIC T5 Gc Ex n IIC T5 Gc -40°C ≤ Ta ≤ 60°C
Ex ic codes only refer to push button contacts
|
Yes Yes
Yes#
Yes| Yes Yes
Yes#
Yes| Yes
Yes
Yes
Included| Yes
Yes
Yes
Included| Yes Yes ] Yes #
Yes
|
BA495| BA495| N/A| N/A| BA495
Selecting a model
When selecting a model the following requirements should be considered:
Mounting | Field or panel |
---|---|
Location | Safe area |
Gas Hazardous area
Zone 0, 1 or 2
Type of protection
Certification authority
Dust hazardous area
Zone 20, 21 or 22
Type of protection
Certification authority
Number of inputs| 1 or 2 flowmeter inputs
Options| Display backlight
Dual alarm outputs
Pulse output
4/20mA output
To simplify selection Table 1 summarises the specifications of all the field mounting Rate Totalisers and Table 2 contains similar information for the panel mounting models. Detailed specifications, datasheets, instruction manuals and third party safety and ingress certificates for each model are available from the BEKA website www.beka.co.uk.
2.1 Mounting
The BEKA range of pulse input Rate Totalisers includes models for field and
panel mounting.
2.1.1 Field mounting
Field mounting Rate Totalisers with a ‘G’ model number suffix have a robust
glass reinforced polyester (GRP) enclosure with an 8mm thick toughened glass
window. The enclosure has IP66 ingress protection which will not be degraded
by 7J impacts to the GRP case or 4J impacts to the window at temperatures
between -40°C and +70°C. The enclosure’s ingress and impact protection has
been independently assessed by a third party UKAS accredited test house. The
resulting test certificate is shown on the BEKA website.
The enclosure material is carbon loaded to prevent the accumulation of static
charges. The thermoset GRP is very strong and will not corrode or degrade when
used for Rate Totaliser installations in marine and waste water environments.
For installations in hazardous areas, GRP overcomes the restrictions limiting
the use of aluminium in potentially explosive atmospheres.
Field mounting instruments with a ‘G’ model number suffix have two M20 x 1.5
tapped cable entries. To maintain the integrity of the Rate Totaliser
enclosure both cable entries should be fitted with impact resistant M20 x 1.5
IP66 glands, conduit entries or blanking plugs.
The instrument’s units of measurement and tag information can be marked onto a
slide-in scale card clearly visible above and below the display. Although easy
to configure on-site, Rate Totalisers can be supplied configured and
calibrated with this scale card printed with customer specified units of
measurement for no additional charge.
A 316 stainless steel legend plate which can be supplied laser engraved with
customer specified information is available as an option.
Field mounting Rate Totalisers are surface mounting, but can be be pipe or
panel mounted using one of the BEKA accessory kits.
BA393G 316 stainless steel kit, attaches instrument to any vertical or
horizontal pipe with outside diameter between 40 and 73mm.
Fig 1 BA393G Pipe mounting kit
BA394G 316 stainless steel panel mounting kit secures field mounting instrument into a panel aperture, but does not seal panel aperture. Fig 2 BA394G Panel mounting kit
BA494G GRP panel mounting kit secures fieldmounting instrument into a panel aperture and provides IP66 seal between front and rear of the panel. Not certified for fieldmounting instruments with an ‘NG’ suffix.
Fig 3 BA494G Sealed panel mounting kit
In addition to the ‘G’ suffix Intrinsically safe field mountingmodels, ‘E’ suffix intrinsically safe Rate Totalisers arealso available. The ‘E’ suffix models have a separatefield terminal enclosure and three tapped M20 x 1.5 cableentries. These models have display backlights, dual alarms and isolated pulse and 4/20mA outputs.
2.1.2 Panel mounting
Panel mounting Rate Totalisers are available in 96 x 48mm and 144 x 72mm glass
loaded Noryl (modified PPE) DIN enclosures with toughened scratch resistant
glass display windows. The enclosure size depends upon the display size and
the number of pulse inputs. Both enclosures have IP66 front of panel ingress
protection, and when correctly installed provide an IP66 seal between the
instrument and the instrument panel.
The ingress protection of the enclosures have been independently assessed at
temperatures between -40°C and +70°C by a third party UKAS accredited test
house.
The resulting test certificate is shown on the BEKA website. The instrument’s
units of measurement can be marked onto a slide-in scale card clearly visible
at the right hand side of the display. The scale card can be fitted without
opening the instrument enclosure or removing the Rate Totaliser from the
instrument panel. Although easy to configure on-site, Rate Totalisers can be
supplied configured with the scale card printed with customer specified units
of measurement for no additional charge.
For panel mounting applications in marine environments, or where the front of
the instrument is likely to be impacted, single input rugged models are
available in a 316 stainless steel enclosure. These models, which are
identified by an ‘-SS’ model number suffix, have identical features as the
other models including a slide-in scale card.
The enclosure has IP66 front of panel ingress protection, and when correctly
installed provide an IP66 seal between the instrument and the instrument
panel. The ingress protection of the enclosure has been independently assessed
at temperatures between -40°C and +70°C by a third party UKAS accredited test
house. The resulting test certificate is shown on the BEKA website.
Intrinsically safe Rate Totalisers with an ‘-SS’ suffix have been certified
for installation in Ex e and Ex p enclosures without invalidating the
certification of the panel enclosure in which they are mounted at temperatures
between -40°C and +60°C. For applications in Zone 2 or 22 without the need for
Zener barriers or galvanic isolators, the BA337NE Rate Totaliser has Ex nA
non-sparking and Ex tc dust ignition protection by enclosure. Please see BEKA
Application Guide AG310 for more information on how to install this Rate
Totaliser.
The rear of panel ingress protection of all 96 x 48mm and 105 x 60mm rugged
stainless steel Rate Totalisers can be increased to IP66 with a BA495 rear
cover sealing kit. Manufactured from 316 stainless steel the cover
incorporates two M20 entries for cable glands, allowing these Rate Totalisers
to be installed in open panels.
Fig 4 BA495 rear cover
2.2 Location
Having decided how the Rate Totaliser is to be mounted, the location of the
installation will help to determine the required model.
2.2.1 General purpose application
If the Rate Totaliser is to be installed in an area which does not have a
flammable gas or combustible dust hazard, one of the following general purpose
Rate Totalisers should be selected.
Field mounting see Table 1
BA534G | 1 input |
---|---|
BA584G | 2 input |
Panel mounting models are available in two alternative DIN enclosure sizes
plus a rugged impact resistant instrument in a 316 stainless steel enclosure.
Panel mounting see Table 2
BA537E | 1 input 96 x 48mm |
---|---|
BA538E | 1 input 144 x 72mm |
BA537E-SS | 1 input Rugged 105 x 60mm |
BA588E | 2 input 144 x 72mm |
2.2.2 Explosive atmosphere applications
To select a Rate Totaliser for a hazardous area installation, the Zone or
Division in which it is to be installed and the hazard must be known, together
with the required certification authority i.e. IECEx, ATEX or ETL.
The range includes intrinsically safe Ex ia models for installation in most
gas and dust Zones. For installations in Zone 2 or 22 without the need for
Zener barriers or galvanic isolators, models with non-sparking Ex nA
certification for gas hazards and dust ignition protection by enclosure Ex tc
are included.
Field mounting see Table 1
BA334E | 1 input | 1G | Ex ia | Separate terminal compartment. |
---|---|---|---|---|
BA334G | 1 input | 1GD | Ex ia | Separate terminal compartment. |
BA384E | 2 input | 1G | Ex ia | |
BA384G | 2 input | 1GD | Ex ia | |
BA334NG | 1 input | 3GD | Ex nA and Ex tc | |
BA384NG | 2 input | 3GD | Ex nA and Ex tc |
Panel mounting see Table 2
BA337E | 1 input | 96 x 48mm | 1G Ex ia |
---|---|---|---|
BA338E | 1 input | 144 x 72mm | 1G Ex ia |
BA337E-SS | 1 input | Rugged 105 x 60mm | 1GD Ex ia |
BA388E | 2 input | 144 x 72mm | 1G Ex ia |
BA337NE | 1 input | Rugged 105 x 60mm | 3GD Ex nA and Ex tc |
When selecting a Rate Totaliser for installation in a hazardous area, the instrument’s hazardous area certificate should be consulted to ensure that the instrument has approval for the required area, hazard and temperature range.
2.3 Two input models
The two input Rate Totalisers are primarily intended for use with two
flowmeters. Each Rate Totaliser input is individually configurable and the
instrument can display either input, or the sum or difference of the two flow
rates and totals.
The two input models enable the total flow and flow rate from two sources to
be calculated and displayed. If it is required to add more than two flow
sources, multiple Rate Totalisers can be linked using the instrument’s
synchronous pulse output.
2.4 Operating temperature
All the field and panel mounting Rate Totalisers except models with an ‘E-SS’,
‘NG’ and ‘NE’ suffix have a specified operating temperature of -40°C to +70°C.
Between these temperatures the Rate Totalisers will function normally, however
at temperatures below -20°C the display digits will gradually change more
slowly and contrast will be reduced. At some temperature below -20° the
display will stop functioning, but totalisation will continue normally and the
instrument will not be damaged.
Models with an ‘E-SS’, ‘NG’ and ‘NE’ suffix have a maximum certification
temperature of +60°C but performance is the same as the other models at low
temperatures.
Rate Totaliser function
All BEKA externally powered pulse input Rate Totalisers have similar
functions, although the number of inputs and the output options may differ.
Fig 5 shows a simplified block diagram of a one input instrument.
All models can accept pulses from a widevariety of flowmeter transducers or
outputs. To enable a Rate Totaliser to count pulses from transducers such as a
switch contact, open collector transistor or a two wire proximity detector,
the transducer has to be powered which is achieved by fitting an external link
between two of the Rate Totaliser’s field terminals.
Fig 5 Simplified diagram of single input Rate Totaliser
Rate Totalisers can calculate and display the rate of flow and the total flow
from most pulse output flowmeters including non-linear flowmeters such as a
turbine meter operating over a wide range of flows. All models include a
sixteen segment lineariser which can be configured to minimise non-linearity
errors. Rate Totalisers with two inputs have separate configuration functions
and a separate lineariser for each input.
All the Rate Totaliser models have separate rate and total displays as shown
in Fig 6 with independent calibration allowing the rate of flow and the total
flow to be displayed in different units of measurement. e.g. rate of flow
could be shown in litres per hour and the total flow could be in cubic metres.
The display digit size depends upon the model as shown below.
Display size
6 digits 8 digits
Field mounting
Field mounting | 12mm | 18mm |
---|
Panel mounting
96 x 48mm | 6mm | 9mm |
---|---|---|
144 x 72mm | 12mm | 18mm |
Rugged 105 x 60mm | 6mm | 9mm |
Rate of flow and total flow may be shown on either the 6 or8 digit displays. If only one variable is required, the lower six digit display may be disabled.
Fig 6 Rate Totaliser display
The total display may be reset to zero by operating two of the Rate
Totaliser’s push buttons, or remotely by connecting the instruments external
reset terminals together for more than one second.
The Rate Totaliser also maintains a protected Grand Total which is not reset
when the total display is zeroed. Both the total display and the grand total
are retained when the Rate Totaliser is not powered.
Rate Totaliser Configuration
All models are configured and calibrated using a common intuitive menu
structured in the same way as all BEKA instruments. The menu is accessed via
the four instrument push buttons and can be protected by a user defined four
digit access code. The calibration structure of all single input Rate
Totalisers is shown in Fig 7. This allows a Rate Totaliser to be configured
and calibrated on-site without the need for external test equipment.
The configuration menu uses English language names to describe functions and
variables such as code and debounce. When the function name has more than
eight characters a simple abbreviation is used such as di5p-1 (Display 1) and
t-re5et (Total reset). In this Application Guide these function and variable
names are shown in a seven segment font, exactly as they appear on the Rate
Totaliser’s display.
BEKA rate Totalisers are easy to calibrate as there are only four basic
variables to adjust.
Flowmeter K-factor | factor |
---|---|
Total scale factor | 5cale t |
Rate scale factor | 5cale r |
Timebase | t-ba5e |
The first three variables, factor, 5cale t and 5cale r divide the number of input pulses from the flowmeter to convert them to meaningful engineering units, such as gallons or litres. As shown in Fig 7 they are arranged so that the total flow and the rate of flow can be shown in different engineering units. Each variable is adjustable between 0.0001 and 99999 and is described separately in the following sections.
Fig 7 Single input Rate Totaliser Configuration structure
4.1 Flowmeter K-factor
Each output pulse from a flowmeter or flow transducer represents a defined
flow volume that has passed through the flowmeter. For most flowmeters this is
small compared with the total flow volume that is to be measured. The
performance of flowmeters and flow transducers is therefore defined by the
number of output pulses they produce for each unit of flow volume passing
through them e.g. 200 pulses per gallon of flow. This is known as the K-factor
of the meter or transducer. Most flowmeters and transducers are supplied with
a test certificate showing the average K-factor over a range of flow rates.
To convert the pulse output from a flowmeter or flow transducer into
engineering units, the number of output pulses must be divided by the K-factor
of the flowmeter or flow transducer.
This can be illustrated with a simple example. To calculate the total flow in
engineering units measured by a flowmeter having a K-factor of 70 pulses per
litre after it has output 1075 pulses.
Number of output pulses | 1075 | = 15.36 litres |
---|---|---|
Flowmeter K-factor | 70 |
All BEKA pulse input Rate Totalisers achieve this conversion using a
configurable dividing constant called factor which can be adjusted between
0.0001 and 99999 as shown in Fig 7.
For the flowmeter in this example having a K-factor of 70 pulses per litre,
the dividing constant factor in the Rate Totaliser should be set to 70. After
the Rate Totaliser
has received 70 pulses from the flowmeter it will transferone pulse,
representing 1 litre of flow, to the following Rate Totaliser adjustable
functions Scale Factor 5cale r and the Total Scale Factor 5cale t as shown in
Fig 8.
Unless a resolution greater than one K-factor unit of measurement is required,
i.e. 1 litre in the above example, for most applications factor should be set
to the K-factor of the flowmeter. Section 4.3.1 contains additional
information about Rate Totaliser resolution.
Fig 8 factor set to flowmeter K-factor
4.2 Total Scale Factor 5cale t
As shown in the previous section the Rate Totaliser function factor is used to
convert the number of input pulses received into engineering units such as
litres or gallons.
If the Rate Totaliser’s total display is required in the engineering units
produced by factor no further scaling is required. However, to enable the
total display to be in different engineering units, or in multiples of the
engineering units produced by factor such as thousand of litres or gallons, an
additional scaling factor 5CALE t is included.
5CALE t is a dividing factor adjustable between 0.0001 and 99999 that divides
the output of the factor function to produce the total display in the required
engineering units. Fig 9 illustrates how 5CALE t can be used to extend the
example shown in Fig 8 to produce a total display in m³. Each pulse output
from factor represent one litre of total flow. There are 1,000 litres in a
cubic metre, therefore the output from factor requires dividing by 1000 to
convert it to cubic metres m³.
Fig 9 5cale . t set to 1000 to produce total flow display in cubic metres m³
4.3 Rate scale factor 5cale r
Function 5CALE r is similar to 5cale t described in the previous section. As
shown in section 4.1 the Rate Totaliser function factor is used to convert the
number of input pulses received from the flowmeter into engineering units
such as litres or gallons.
If the Rate Totaliser’s rate display is required in the engineering units
produced by factor no further scaling is required. However, to enable the rate
display to be in different engineering units, or in multiples of the
engineering units produced by factor, such as thousands of litres or gallons,
an additional scaling factor 5CALE r is included.
Functions 5cale r and 5cale t receive their inputs from factor. Both are
independently adjustable which enables the Rate Totaliser to have rate and
total displays with different units of measurement.
5cale r is a dividing factor adjustable between 0.0001 and 99999 that enables
rate of flow to be displayed in the required engineering units. It is used in
conjunction with the Rate Totalisers timebase t-ba5e which determines whether
the flow rate is displayed per second, per minute or per hour.
Continuing the example shown in Fig 8 and assuming that the flow rate display
is required in gallons per minute.
Fig 10 illustrates how 5cale r is set to produce a rate display in gallons.
Each pulse output from the factor function represent one litre of total flow.
There are 4.5461 litres in an imperial gallon, therefore the output from
factor requires dividing by 4.5461 to convert it to imperial gallons. This is
achieved by setting 5cale r to 4.5461.
4.3.1 Resolution
The output from factor will determine the resolution of the Rate Totaliser. If
increments of flow smaller than one K-factor unit of measurement are
significant, factor should be reduced.
The effect of reducing factor for a flowmeter having a K-factor of 200 pulses
per litre are shown below.
Factor | Instrument resolution |
---|---|
200 | 1 litre |
20 | 0.1 litre |
2 | 0.01 litre |
Total and Rate are displayed simultaneously and can have different units of measurements
Fig 10 5cale r and t-ba5e set to provide a Rate Display in Gallons / minute
4.4 Timebase: t-bA5E
As described in the previous section, the rate scale factor 5cale r defines
the engineering units of the rate display.
The Rate Totaliser can display rate of flow per second, per minute or per
hour.
The Rate Totaliser timebase t-ba5e enables the output from 5cale r to be
multiplied by 1, 60 or 3,600 to produce a rate display per second, per minute
or per hour as shown below: t-ba5e menu
options
tb-1 | x 1 for flow / second |
---|---|
tb-60 | x 60 for flow / minute |
tb-3600 | x 3600 for flow / hour |
For this example the rate display is required in gallons per minute, therefore t-ba5e is set to tb-60 as shown in Fig 6.
Linearisation
Flowmeters are usually supplied with a calibration certificate specifying their average K-factor and the flow range over which it applies. For use over extended flow ranges and for non-linear flowmeters, multiple K-factors will be specified each at a different flow rate. For these devices the calibration certificate is likely to contain a table similar to the one shown below.
Flow Rate Litres/min | K-factor Pulses/litre |
---|---|
5 | 200 |
10 | 230 |
15 | 239 |
20 | 242 |
Table 3 Typical flowmeter calibration certificate
To minimise display errors resulting from flowmeter non-linearity, all BEKA
Rate Totalisers incorporate a 16 segment straight line lineariser which when
correctly configured will compensate for the flowmeter non-linearity. When
the Rate Totaliser’s lineariser is enabled up to 16 values of the flowmeter’s
K-factor may be entered in the l-factor unction, each at a specified input
pulse frequency pul5e fre.
The output frequency of the flowmeter, which is required for calibrating the
Rate Totaliser lineariser, can be calculated from the information in the
flowmeter calibration certificate.
Output frequency Hz = (Flow rate per min) x (K-factor) 60
Or if the flow rate is specified per second.
Output frequency Hz = (Flow rate per second) x (K-factor)
Flow Rate Litres/min| K-factor Pulses/litre| Output frequency
Hz
---|---|---
0| 0| 0
5| 200| 16.666
10| 230| 38.333
15| 239| 59.750
20| 242| 80.666
Table 4 Calculated lineariser calibration information
Pulse output
All field mounting BEKA Rate Totalisers and the 144 x 72mm panel mounting
models have an optically isolated open collector pulse output. This pulse
output is available as a factory fitted option for the smaller 96 x 48mm and
the rugged 105 x 60mm panel mounting models.
The output pulse may be a synchronous duplicate of the input pulse for re-
transmission applications, or it may be derived from incrementation of the
least significant digit of the total display, irrespective of the decimal
point position. When derived from the total display the output pulse frequency
may be divided and the output pulse width defined.
Selecting dirECt in the pulse output configuration menu produces a synchronous
duplicate of the Rate Totaliser input pulse at frequencies up to 5kHz.
When 5CALEd is selected in the pulse output configuration menu, the pulse
output is derived from the incrementation of the least significant digit of
the total display, irrespective of the position of the displayed decimal
point. When 5CALEd is selected the Rate Totalisers pulse output frequency may
be divided by:
and the pulse output width (duration) may be selected from eleven options:
If configured such that the output pulse frequency with the specified pulse
width can not be output in real time, the number of pulses will be stored and
transmitted at the maximum possible speed, but will not be stored if the
total display is reset to zero or the Rate Totaliser is disconnected or
switched off.
To prevent misleading or dangerous pulse outputs after any changes are made to
the Rate Totaliser configuration, the pulse output must be manually re-enabled
before it will function.
The pulse output of a two input Rate Totaliser may be a synchronous duplicate
of either pulse input, or it may be derived from incrementation of the least
significant digit of the composite total display (input A + input b)
irrespective of which total is being displayed by the instrument.
A pulse output can not be derived from a composite total display of (input A –
input b).
Optional 4/20mA output
All BEKA Rate Totalisers can be supplied with a factory fitted galvanically
isolated 4/20mA current sink output which can be used for retransmission to
other instrumentation. This output appears as a 4/20mA loop powered
transmitter requiring an external power supply between 5 and 28V. The output
can be configured to represent any part of the instrument’s rate or total
display.
To prevent a misleading or dangerous current output after any changes to the
Rate Totaliser configuration, the 4/20mA output must be manually re-enabled
before it will function.
Optional dual Alarm outputs
All BEKA Rate Totalisers can be supplied with factory fitted dual alarms. Each
alarm has a galvanically isolated, solid state single pole, voltage free
output that may be independently configured as a high or low, rate or total
alarm with a normally open or normally closed output. Configurable functions
for each alarm include the setpoint, alarm delay and silence time. Hysteresis
may be applied to rate alarms.
When the Rate Totaliser’s power supply is turned off or disconnected, alarm
outputs will open irrespective of whether normally open or normally closed
outputs have been selected. When designing a system it is recommended that an
open output should be selected for the alarm condition.
Alarm annunciators on the instrument display indicate the status of each
alarm. If an alarm delay or silence time has been selected the annunciator
will flash during the delay or silence period.
Slide-in scale card
All Rate Totaliser’s, except the ‘E’ suffix field mounting models, have a
slide-in scale card which can be printed to show the instruments units of
measurement. The scale card is mounted on a flexible strip that is inserted
into a slot at the rear of panel mounting Rate Totalisers and adjacent to the
terminals on field mounting instruments.
New Rate Totalisers can be supplied with a printed scale card showing
requested units of measurement for no additional charge. If this information
is not supplied when the instrument is ordered a blank card will be fitted
which can easily be marked on-site.
Inserting scale card in panel Rate Totaliser
Configuration examples
This section contains some examples of Rate Totaliser configurations requested by BEKA customers. Step-bystep instructions are not included nor are non- calibration configuration functions.
Example 1
In this example a user required a BEKA Rate Totaliser to display total flow in
Gallons with a resolution of 0.1 and theflow rate in Gallons per Minute with a
resolution of 1.
An output pulse is required for each gallon of total flow.
The flowmeter has a K-factor of 10 pulses per Gallon.
Summary
Flowmeter K-factor | 10 pulses / gallon |
---|---|
Required total display | 0.0 gallons |
Required rate display | 0 gallons / minute |
Pulse output | 1 pulse / 1 gallon of flow |
Rate Totaliser Configuration
Flowmeter K-factor
Converts output from flowmeter into engineering units gallons.
Total display
Display is required in gallons, therefore 5cale t is set to 1 as Factor has converted pulse input into gallons. Total display resolution of 0.1 gallons is required, hence decimal point is positioned before the least significant digit.
Rate display
Display is required in gallons, therefore 5cale r is set to 1 as Factor has
converted pulse input into gallons. Rate display resolution of 1 gallon is
required, hence decimal point is positioned after least significant display
digit where it is not visible.
Selecting a timebase of tb-60 multiplies the rate display by 60 to show flow
rate per minute.
Pulse output
The Rate Totaliser outputs a pulse each time the least significant digit of the total display is incremented. The least significant digit represents 0.1 gallons so this rate has to be divided by 10 to produce one output pulse per gallon of total flow.
Example 2
This example illustrates a Rate Totaliser with the rate and total displays
having different engineering units. Total flow is required in m³ with a
resolution of 0.1 and the flow rate in litres per Minute with a resolution of
- An output pulse is required for each 0.1m³ of total flow.
The flowmeter has a K-factor of 1 pulse per litre.
Summary
Flowmeter K-factor | 1 pulse / litre |
---|---|
Required total display | 0.0 m³ |
Required rate display | 0 litres / minute |
Pulse output | 1 pulse / 0.1 litres of flow |
Rate Totaliser Configuration Flowmeter K-factor
Each output pulse from the flowmeter represents 1 litre therefore no
further conversion is required.
Total display
Display is required in m³, therefore 5cale t is set to 1000 as there are 1000 litres in a m³. Total display resolution of 0.1 m³ is required, hence decimal point is positioned before the least significant digit.
Rate display
Display is required in litres / minute. Each pulse already represents 1 litre
so no further scaling is required and 5cale r is set to 1.0 Rate display
resolution of 1 litre is required, hence decimal point is positioned after
the least significant display digit where it is not visible.
Selecting a timebase of tb-60 multiplies the rate display by 60 to show the
flow rate per minute.
Pulse output
The Rate Totaliser outputs a pulse each time the least significant digit of the total display is incremented. The least significant digit of the total display represents 0.1 m³ which is the required output pulse resolution,therefore no further division is required.
Example 3
The requirements of this example are identical to those for example 2 except
for the pulse output. In this example an output pulse is required for each
litre of flow. which is the same as that being produced by the flowmeter.
Pulse output
The required output pulse from the Rate Totaliser is the same as pulse output from the flowmeter i.e. 1 pulse per litre. Selecting direct in the pulse output configuration menu, results in the output pulse being a synchronous duplicate of the Rate Totaliser input pulse.
Example 4
This example illustrates how a Rate Totaliser can display total flow and the
rate of flow from a stroke sensor on a reciprocating pump.
A display of the total oil flow is required in barrels of oil with a
resolution of 0.1. The Rate Totaliser is also required to display the pump
stroke rate in pump strokes per Minute.
An output pulse is required for each barrel of total flow.
Each pulse from the pump represents one stroke which is equivalent to 0.6247
US Gallons.
Summary
Flowmeter K-factor | 1 pulse / 0.6247 USG |
---|---|
Required total display | 0.0 Barrels |
Required rate display | 0 Strokes / minute |
Pulse output | 1 pulse / Barrel |
Rate Totaliser Configuration Flowmeter K-factor
Each output pulse from the pump represents 1 stroke therefore no further conversion is required.
Total display
The display is required in Barrels, therefore 5cale t has to convert pump
strokes to Barrels.
Each pump stroke displaces 0.6247 US Gallons and there are 42 US Gallons in a
barrel.
5Cale t = 42 / 0.6247 = 67.232
Total display resolution of 0.1 barrels is required, hence decimal point is
positioned before the least significant digit of the display.
Rate display
Display is required in pump strokes / minute. Each pulse already represents 1
pump stroke so no further scaling is required and 5cale r is set to 1. Rate
display resolution of 1 Stroke is required, hence decimal point is positioned
after least significant display digit where it is not visible.
Selecting a timebase of tb-60 multiplies the rate display by 60 to show pump
strokes rate per minute.
Pulse output
The Rate Totaliser outputs a pulse each time the least significant digit of the total display is incremented. The least significant digit represents 0.1 barrels so this rate has to be divided by 10 to produce one output pulse per barrel of total flow.
Example 5
This example illustrates how a BEKA two input Rate Totaliser can be used to
display the rate of flow and the total flow of two reciprocating mud pumps and
their composite rates and totals i.e. pump 1 + pump 2. Each pump has a
displacement of 1 litre per stroke and a sensor outputs one pulse per stroke.
The rate display is required in pump strokes per minute and the total mud flow
is to be displayed in m³ with a resolution of 0.1 m³. Operating the Rate
Totalisers front panel * or & push button while the instrument is functioning
scrolls the display through pump 1, pump 2 or the composite output of both
pumps, but it does not affect the instruments performance or output.
A pulse is to be transmitted by the Rate Totaliser for each 0.1 m³ of
composite mud pumped i.e. pump 1 + pump 2.
Summary
Pump K-factor | 1 pulse / stroke which is equivalent to 1 litre. |
---|---|
Required total display | 0.0 m³ |
Required rate display | 0 strokes / minute |
Pulse output | 1 pulse / 0.1m³ of composite total flow. |
Rate Totaliser Configuration K-factor
Each output pulse from pump 1 and pump 2 represents 1 stroke which is equivalent to 1 litre of flow therefore no further conversion is required.
Total display
The display is required in m³, therefore 5CALE t has to convert litres to m³. Each pump stroke displaces 1 litre and there are 1000 litres in each m³.
Rate Display
The rate display is required in strokes per minute. Each pulse from pumps 1 and 2 represents 1 pump stroke so no further scaling is required for either input. Therefore both 5CALE r-A and 5CALE r-b are set to 1. Rate display resolution of 1 stroke is required, hence decimal point is positioned after the least significant display digit where it is not visible. Selecting a timebase of tb-60 multiplies the rate display by 60 to show pump stroke rate per minute.
Pulse output
An output pulse is required for each composite 0.1 m³ of mud pumped. The Rate
Totaliser outputs a pulse each time the least significant digit of the
composite total (pulse input A + pulse input b) is incremented, irrespective
of whether the composite total is being displayed. In this example the least
significant digit of the composite total represents 0.1m³ so scaling is not
required.
However, if an output pulse was required for every 1.0m³ of composite total
that was pumped, diVidE would have to be set to 10 i.e. 10 increments of the
least significant digit (0.1m³ per increment) would occur before an output
pulse was produced.
Additional information
If additional information or help is required with Rate Totaliser
configuration, please call one of our sales engineers who will be pleased to
help.
Although Rate Totalisers are easy to configure on-site, they can be supplied
configured to customer specified requirements with a printed slide-in scale
card for no additional charge.
BEKA associates Ltd.
Old Charlton Road., Hitchin, Herts. SG5 2DA
UK Tel: (01462) 438301
Fax: (01462) 453971
e-mail sales@beka.co.uk
www.beka.co.uk