DESCRIPTION
The BA588E is a two-input, general-purpose panel mounting Rate Totaliser which
can operate with a wide variety of pulse output flowmeters. The instrument can
display the output from each flowmeter and, depending upon how it has been
configured, the sum or difference between them.
This abbreviated instruction sheet is intended to assist with installation, a
comprehensive instruction manual describing system design and configuration
may be downloaded from the BEKA website or may be requested from the BEKA
sales office.
The BA588E is CE marked to show compliance with the EMC Directive 2014/30/EU.
INSTALLATION
The BA588E Rate Totaliser has IP66 front of panel protection but it should be shielded from direct sunlight and severe weather conditions. The rear of the instrument has IP20 protection.
Cut-out dimensions
Recommended for all installations. Mandatory to achieve IP66 seal between
instrument and panel.
Support panel wiring to prevent vibration damage Fig 1 Cut-out dimensions and
terminals
Abbreviated instructions for BA588E Two input General purpose Rate
Totaliser
Issue 3
18th July 2017
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire,
SG5 2DA, UK Tel: +44(0)1462 438301 Fax: +44(0)1462 453971
e-mail: sales@beka.co.uk web:
www.beka.co.uk
1. Align foot and body of panel mounting clamp by turning screw anticlockwise4. Insert panel clamp into recess and gently pull it onto the dovetail. Engage screw & turn clockwise to tighten the clamp, fit the other clamps. Recommended tightening torque 22cNm (1.95lbf.in) Equivalent to finger tight plus one-half turn. DO NOT OVERTIGHTEN
EMC
For specified immunity, all wiring should be in screened twisted pairs with
screens earthed at one point.
Scale card
The Rate Totalisers units of measurement are shown on a printed scale card
visible through a window at the right-hand side of the display. The scale card
is mounted on a flexible strip that is inserted into a slot at the rear of the
instrument as shown below
Fig 4 Inserting flexible strip carrying scale card into the slot at the rear
of Rate Totaliser.
Thus the scale card can easily be changed without removing the Rate Totaliser
from the panel or opening the instrument enclosure. New Rate Totalisers are
supplied with a printed scale card showing the requested units of measurement,
if this information is not supplied when the Rate Totaliser is ordered a blank
card will be fitted.
A pack of self-adhesive scale cards printed with common units of measurement
is available as an accessory from BEKA associates. Custom printed scale cards
can also be supplied.
To change a scale card, unclip the protruding end of the flexible strip by
gently pushing it upwards and pulling it out of the enclosure. Peel the
existing scale card from the flexible strip and replace it with a newly
printed card, which should be aligned as shown below. Do not fit a new scale
card on top of an existing card.
Align the self-adhesive printed scale card onto the flexible strip and insert the strip into the Rate Totaliser as shown.
OPERATION
The Rate Totaliser is controlled by four front panel pushbuttons.
When in the operating mode they have the following functions:
Access to the configuration menu.
If the Local Total Reset function tot in the instrument configuration menu is enabled, operating the & and buttons simultaneously for more than 3 seconds allows total A, total b, or both totals and any stored pulses in the pulse output to be reset to zero by operating the push button.
Grand total – shows **Lo**
followed by the least significant 8 digits.
Grand total – shows Hi followed by the most significant 8 digits. If buttons
are pressed for longer than 10 seconds the grand total will be reset to zero
if the grand total reset function got is enabled. To reset the grand total to
zero from the operating mode press the buttons for ten seconds until r. no is
displayed. Using the & button change the display to YE5 and press which will
reset the grand total and restore the original display.
If the Local Total Reset function tot in the instrument configuration menu is enabled, operating the buttons simultaneously for more than 3 seconds allows total A, total b or both totals and any stored pulses in the pulse output to be reset to zero by operating the push button.
Shows each for 2 seconds: Firmware number The function of instrument: 2chtotal
Options fitted:
Provides direct access to the alarm setpoints when the Rate Totaliser is fitted with optional alarms and the AC5P (access setpoints) has been enabled.
CONFIGURATION
Rate Totalisers are supplied configured as requested at the time of order, if
not specified default configuration will be supplied but can easily be changed
on-site.
Fig 6 shows the location of each function within the configuration menu with a
brief summary of the function. Please refer to the full instruction manual for
detailed configuration information and for a description of the linearizer and
optional outputs.
Access to the configuration menu is obtained by pressing the **P**
( and )
buttons simultaneously. If the Rate Totaliser’s security code is set to
default **0000**
the first parameter function will be displayed. If the
instrument is protected by a security code, code will be displayed. The four-
digit code must be entered to gain access to the menu.
Manuals, certificates and data-sheets can be downloaded
fromhttp://www.beka.co.uk/ba588e
Fig 6 Configuration menu