3.014083 Immergas External Probe Kit Instructions

June 9, 2024
IMMERGAS

3.014083 Immergas External Probe Kit
Instructions
EXTERNAL TEMPERATURE PROBE
FOR BOILERS WITH POWER < 35 KW

GENERAL WARNINGS

All products are protected with suitable transport packaging. The material must be stored in dry environments and protected against weathering. This instruction manual provides technical information for installing the kit. As for the other issues related to kit installation (e.g. safety in the work site, environment protection, injury prevention), it is necessary to comply with the provisions specified in the regulations in force and principles of good practice. Improper installation or assembly of the appliance and/or components, accessories, kit and devices can cause unexpected problems to people, animals and objects. Read the instructions provided with the product carefully to ensure a proper installation. Installation and maintenance must be performed in compliance with the regulations in force, according to the manufacturer’s instructions and by authorised professionally qualified staff, intending staff with specific technical skills in the plant sector, as envisioned by the Law.
The external probe connected to the boiler electrical system allows to automatically decrease or increase the max. flow temperature when the external temperature increases  or decreases, in order to adjust the heat supplied to the system according to the change in external temperature.
The external probe always acts when it is connected independently from the presence of the Immergas heat adjustment kit.

OPERATION.

Depending on the external temperature and the settings on the boiler, it latter adjusts the flow temperature depending on the external temperature (see boiler instruction book).

GENERAL FEATURES.

– The temperature probe is specifically realized for assembly in external environments.
– IP66 protection rating against atmospheric agents.
– Plastic container.
– Easy wall-mounting (horizontal or vertical) using plugs.
– PTC type probe with R 25 °C of 1 k ohm

ELECTRIC CONNECTION.
– The boiler is already prepared for the electric connection, which takes place using two wires connected to the relevant clamps (see wiring diagram in boiler instruction  book).
– Maximum length of the cables 50 metres (boiler-external probe distance).
– Cables section with horizontal application between 0.5 and 1.5 mm 2. The cable must have a protective sheath with diameter between Ø 5 – 7 mm
– Section of cables with vertical application between 0.5 and 1.5 mm2. The protective sheath is not indispensable in this application.

INSTRUCTIONS FOR THE INSTALLER.

N.B.: this external temperature probe is suitable for installation on Immergas boilers only.
– The external probe must be installed on the North or NorthWest wall of the building (if possible) at a height of at least 3 metres from the ground.
It must be in a position that is not exposed to sudden air currents, protected from the sun’s rays or other heat sources and also protected from blows and tampering.
– Figures 2 and 3 indicate the distance between the holes on the basis of the type of installation.
– Pass the connection cables through the rubber whipping on the bottom of the probe and fix it to the wall using the plugs (part. D).
– Block the connection cables to the small control board using the supplied straps (Part. E).
– Connect the two electric cables tot he probe terminal board.

MONTAGGIO ORIZZONTALE HORIZONTAL ASSEMBLY

PRODUCT SPECIFICATIONS.

In accordance with Regulation 811/2013 the temperature control device class is:

Class| Contribution to the environmental heating seasonal energy efficiency| Description
---|---|---
II| +2%| Boiler Outer Sensor Kit
VI| +4%| Boiler Outer Sensor Kit coupled to CAR V2 or Super CAR
VII| +3,5%| Boiler Outer Sensor Kit coupled to Crono 7

PROBE FUNCTIONING GRAPHICS.