NOVUS N323RHT Temperature and Humidity Controller User Manual
- June 9, 2024
- Novus
Table of Contents
TEMPERATURE AND HUMIDITY CONTROLLER
N323RHT
OPERATING MANUAL – V2.0x
N323RHT Temperature and Humidity Controller
The N323RHT is a digital controller for relative humidity and temperature with
03 relay outputs configurable independently for control or alarm. Timer
functions are available to all three outputs
The humidity and temperature sensor, sold separately, is protected by a
polyamide capsule and have 3 or 6 meters long cables.
The electrical characteristics of each model are presented in the body of the
controller, according to the purchase order.
SPECIFICATIONS
INPUT SENSOR: Humidity measurement
Range: 0 and 100 % (RH) (see Fig. 1);
Accuracy: See Fig. 1; Repeatability: ± 1 % RH;
Hysteresis: ± 1 % RH;
Linearity error: << 1 % RH;
Stability: < 1 % RH / year;
Response time: Around 8 s to reach 63 % of a fast input change. Valid at
25 °C and 1 m/s airflow.
INPUT SENSOR: Temperature
Accuracy: Refer Fig. 1; Repeatability: ±0.1 °C;
Range: -20 and 100 °C (see Fig. 1);
Response time: Up 30 seconds in slow moving air;
WARM-UP: …………………………………. 15 minutes
MEASUREMENT RESOLUTION:
RH: ……………………. 1 %
T: …………….. 0.1º from –19.9 to 119.9º
Note: The equipment keeps its precision all over the range, despite the lack of display resolution in a part of the range does not allow its visualization.
OUTPUT1: ………………………… Relay SPDT; 1 HP 250 Vac / 1/3 HP 125 Vac (16 A Res.)
…………………………………. Optional: Pulse, 5 Vdc, 25 mA max.
OUTPUT2: …………………………………………………. Relay: 3 A / 250 Vac, SPST-NA
OUTPUT3:……………………………………………… Relay: 3 A / 250 Vac, SPST-NA
POWER SUPPLY:
Voltage: ………………………………….. 100 to 240 Vac/dc ± 10 %
Optional: ……………………………………………………. 12 to 30 Vdc
Frequency: …………………………………………………….. 50~60 Hz
Consumption: ………………………………………………………… 5 VA
Dimensions:
Width x Height x Depth: ………………………………………………… 75 x 33 x 75 mm.
Weight: ……………………………………………………………………………………… 100 g
Panel cut-out: ……………………………………………………………………… 70 x 29 mm
Electronic module operating environment: ………………………… 0 to 40 °C (32 to 104 ºF)
/ 20 to 85 % RH
Sensor module operating environment: ………………………… -20 to 100 °C (-4 to 212 ºF) /
0 to 100 % RH
Case: Polycarbonate UL94 V-2
Protection: Housing IP42, front panel IP65, sensors capsule IP40 (sold
separately)
Suitable wiring: Up to 4.0 mm²; RS-485 digital communication; RTU MODBUS
protocol (Optional) Serial interface not isolated from input circuitry.
Input circuitry isolated from power supply, except in the 24 V powered model.
IMPORTANT
The sensor used in this controller may be damaged or lose calibration if
exposed to aggressive atmospheres with high concentrations as Chloride Acid,
Nitride Acid, Sulphuric Acid or Ammonia.
Acetone, Ethanol and Propylene Glycol may cause reversible measurement drifts.
Fine trimming in the indication of RH and Temperature are available at the
parameters , in the configuration level of parameters.
ELECTRICAL WIRING
The figure below indicates the connection to the sensor, power supply and controller output, as well as a connection example.
RECOMMENDATIONS FOR INSTALLATION
- The humidity sensor Conductors shall go through the system plant separately from the control and feeding output conductors, if possible in grounded electrical ducts.
- The controller feeding shall be preferably provided from a proper instrumentation network with a phase different from the one used for the control output.
- It is recommendable to use RC FILTERS (47 R and 100 nF, series) in contactor coils, solenoids, etc.
WORKING WITH THE CONTROLLER
The controller operates on the outputs OUTPUT1, OUTPUT2 and OUTPUT3 to lead
the measured variable (temperature or humidity) to the intended value, defined
by the setpoint ( ).
OUTPUT1, OUTPUT2 and OUTPUT3 can operate either as control outputs, when they
operate directly on the system load (resistance, compressor, humidifier, etc.)
or as alarm outputs that operate notifying the operator about the occurrence
of any specific situation, defined by the user. The operation modes are
presented below and they can be defined on parameters a
0 Reverse control action
Activates the corresponding OUTPUT when the process variable (RH or
temperature) is below the setpoint of that output. Normally used for heating
control.
-
Direct control action
Activates the output whenever the process variable is above the setpoint for that output. The direct action is used for refrigeration control. -
Low Alarm
Minimum value alarm indicates that the process value is below the alarm setpoint defined for the output. -
High Alarm
Maximum value alarm indicates that the process is above the alarm setpoint defined for that output. -
Low alarm with Initial Blocking
Identical to the Low Alarm, with the addition of the initial blocking feature explained in Note 2 below. -
High alarm with Initial Blocking
Identical to the High Alarm, with the addition of the initial blocking feature explained in Note 2 below. -
Inside Range Alarm
Activates the output when the process variable is within the interval defined by:
-
Outside Range Alarm
Activates the output when the process variable is outside the interval defined by:
-
Inside the range alarm with Initial Blocking
Identical to the inside the range alarm with the addition of the initial blocking feature, describe in Note 2 below. -
Outside the Range Alarm with Initial Blocking
Identical to the outside the range alarm with the addition of the initial blocking feature, describe in Note 2 below.
Note 1: The action modes 6, 7, 8 and 9 are available to OUTPUT 2 and OUTPUT 3 only. For OUTPUT 2 when ( = 0, 1, 6 or 7. For OUTPUT 3 when ( = 0, 2, 5 or 7.
Note 2: The Initial Blocking feature inhibits the alarm from being
recognized if an alarm condition is present when the controller is first
energized. The alarm will be enabled only after the occurrence of a non-alarm
condition followed by a new occurrence for the alarm.
The Initial Blocking impedes (blocks) the alarm from being switched on in the
beginning of the control process. The alarm will only be unblocked after the
passage of the variable measured by a nonalarm condition. This feature is
useful when, for example, a minimum alarm is programmed in a heating process.
Without the blocking, the process would start with an enabled alarm until
thecontrol setpoint isachieved.
Output Timing
The controller allows for the Output Timing programming, where the user can
establish three conditions: output tripping delay, temporary activation and
sequential activation. The timing is available only for outputs 1, 2 and 3 and
is programmed by means of the
The figures below represent these functions; T1 and T2 can vary from 0 to 1999
seconds and their combinations determine the timing mode. For normal operation
of the alarms, without timing, program 0 (zero).
On the front panel, the controllers P1, P2 and P3 light when the
respective outputs are activated. During the delay, the respective signaler
remains flashing.
TIMER FUNCTION | T1 | T2 | ACTION |
---|---|---|---|
Normal operation | 0 | 0 | |
Delayed activation | 0 | 1 to 1999 s | |
Temporary activation | 1 to 1999 s | 0 | |
Sequential activation | 1 to 1999 s | 1 to 1999 s |
Table 1 – Timer alarm functions 1, 2 and 3
OPERATION
The controller shall be set up by the user before using. This consideration
consists in the definition of the values for the various parameters that
determine the equipment operation mode.
These set up parameters are organized in groups or Levels, called “parameter
levels”.
LEVEL | FUNCTION |
---|---|
0 | Measurement |
1 | Setpoints Adjustment |
2 | Configuration |
3 | Calibration |
Table 2 – Levels
Upon power-up controller, the controller display shows for 1 second its
firmware version. This information is useful when consulting the factory.
Then, the temperature measured by the sensor is shown on the display. This is
the parameter level 0 or Temperature Measurement level.
For access to level 1, press for 1 second till the “ ” parameter appears.
Press to go back to the temperature measurement level.
To access level 2 of parameters, press for 2 seconds until the “ ” message is
shown. Release the key to remain in this level. Press to access other
parameters from this level. After the last parameter, the controller goes back
to the temperature measurement level.
To change the parameters values, use the keys until the achievement of the desired values.
Notes:
- The programming is saved by the controller when the latter goes from one parameter to the other and only then it is considered valid. The programming is stored in a permanent memory, even if there is a power supply interruption.
- If no keyboard activity is detected for over 20 seconds, the controller saves the current parameter value and returns to the measurement level.
Level 1 – Setpoints Adjustment
This level contains the 3 setpoints: They define the RH and the temperature
for the process. The display shows the parameter name alternating with the
current value. Set the desired value by pressing the keys
| Setpoint adjustment for control OUTPUT 1. The setting range is limited by
the values in (this parameter belong to the Configuration level).
---|---
| Setpoint adjustment for control OUTPUT 2. The setting range is limited by
the values in
| Setpoint adjustment for control OUTPUT 3. The setting range is limited by
the values in
Level 2 – Configuration Level
Presents a sequence of other parameters that shall be defined by the user. The
parameters are shown alternately with the respective values. In order to
obtain the desired values, use the keys .
| Defines how the variables, relative humidity and temperature, will be
displayed:
Humidity;
Temperature;
Toggles the indications of relative humidity and temperature every 2 seconds;
Toggles the indications of relative humidity and temperature every 3 seconds;
Toggles the indications of relative humidity and temperature every 4 seconds;
Toggles the indications of relative humidity and temperature every 5 seconds.
For options , a fast click on the , key forces the other variable to be
displayed for 10 seconds.
---|---
| Temperature Unit – Allows the user to choose the measured temperature
presentation unit.
Temperature in degrees Celsius;
Temperature in degrees Fahrenheit
| Correction value for humidity indication. Allows the user to perform small
adjustments on the relative humidity indication, trying to correct measurement
errors that appear, for example, in the sensor replacement. Adjustment range:
between –10.0 and 10.0 % of RH. Default value: 0.0
| Correction value for Temperature indication. Allows the user to perform
small adjustments on the relative temperature indication, trying to correct
measurement errors that appear, for example, in the sensor replacement.
Adjustment range: between –10.0 and 10.0 % of RH. Default value: 0.0
| Lower limit value for (minimum value with which can be configured). must be
programmed with a lower value than .
SP High Limit 1| Upper limit for (maximum allowed value for ). must be
programmed with
a higher value than the one configured in .
| Lower limit value for (minimum value with which can be configured). must be
programmed with a lower value than
| Upper limit for (maximum allowed value for ). must be programmed
with a value higher than the one in .
| Lower limit value for (minimum value with which can be configured).
must be programmed with a lower value than
| Upper limit for (maximum allowed value for ). must be programmed with a
value higher than the one in .
| Control action for OUTPUT 1:
Reverse: For heating or humidification;
Direct: For cooling or dehumidification ();
Low (minimum value) alarm;
High (maximum value) alarm;
Low alarm with initial blocking;
High alarm with initial blocking.
| Control OUTPUT 2 and OUTPUT 3 action:
Reverse control action (heating or humidification);
Direct control action (cooling or dehumidification) ();
Low (minimum value) alarm;
High (maximum value) alarm;
Low alarm with initial blocking;
High alarm with initial blocking;
Alarm inside the range;
Alarm outside the range;
Inside the range alarm with initial blocking;
Outside the range alarm with initial blocking;
Free Timer (available only for .
The section Working With The Controller describes how these functions work.
| Defines the outputs positioning in relation to the variables.
OUTPUT 1 = RH; OUTPUT 2 = RH and OUTPUT 3 = RH
OUTPUT 1 = RH; OUTPUT 2 = RH and OUTPUT 3 = Temperature
OUTPUT 1 = RH; OUTPUT 2 = Temperature and OUTPUT 3 =RH
OUTPUT 1 = RH; OUTPUT 2 = Temperature and OUTPUT 3 =Temperature
OUTPUT 1 = Temperature; OUTPUT 2 = RH and OUTPUT 3 = RH
OUTPUT 1 = Temperature; OUTPUT 2 = RH and OUTPUT 3 = Temperature
OUTPUT 1 = Temperature; OUTPUT 2 = Temperature and OUTPUT 3 = RH
OUTPUT 1 = Temperature; OUTPUT 2 = Temperature and OUTPUT 3 = Temperature
| Control hysteresis: Differential between the point of switching on and off
the relay of the output, set up as a control output. Adjustable between 0.1
and 50.0.
| Time of delay for starting the control. After the controller has been
switched on, the output (1, 2 or 3) will only be switched on when the time
programmed in this parameter has passed. Used in large refrigeration systems
to impede simultaneous routing of compressors upon recovery of power supply
interruption. Value in seconds, 0 to 250 s.
| Level available when
Defines the minimum off time for control OUTPUT. Once OUTPUT 1 is turned off,
it remains so for at least the time programmed in This parameter is useful in
extending compressor life in refrigeration systems. For heating systems,
program to zero.
Value in seconds, 0 to 999 s.
| Level available when
Defines the minimum on time for control OUTPUT 1. Once turned on, OUTPUT 1
remains so for at least the time programmed in This parameter is intended for
refrigeration systems where increased compressor life is desired. For heating
systems, program to zero. Value in seconds, 0 to 999 s. Value in seconds, 0 to
999 s.
| Time interval for alarm temporization. Defines the temporization mode and
intervals, as shown in Table 1.
Not available when outputs 1 and 2 are configured as direct action. Adjustable
from 0 to 1999 seconds.
| Time interval T1 for temporization. Defines the temporization mode and
intervals for OUTPUT 3 (see Table 1). Not available when OUTPUT 3 is
configured as direct action.
Adjustable from 0 to 1999 seconds. If is configured as Free Timer, the unit of
time is given in minutes. Timer output activation duration (timer).
| Time interval T2 for alarm temporization. Defines the temporization mode
and intervals, as shown in Table 1. Not available when outputs 1 and 2 are
configured asdirect action. Adjustable from 0 to 1999 seconds.
| Time interval T2 for temporization. Defines the temporization mode and
intervals, as shown in Table 1. Not available when OUTPUT 3 is configured as
direct action. Adjustable from 0 to 1999 seconds. If is configured as Free
Timer, the unit of time is given in minutes. Interval between the timer output
activation operations.
| The controllers with incorporated serial communication interface RS485
present the parameter in their programming level. In this parameter, the user
defines a communication address for each network element. The defined address
shall be between 1 and 247.
Note 3: The correct use of the delays and contributes to a smooth start-
up following a energy fail; the compressors will be turned on in sequence,
according to the programmed temporization, reducing the energy demand after
power-up.
Level 3 – Calibration Level
The controller is factory adjusted and calibrated using traceable standards.
The following parameters should be accessed only by experienced personnel. To
enter this cycle, the key must be kept pressed for 3 seconds.
In case of accidental access, the keys shall not be pressed; Just pass through
all parameters, till the controller goes back to the measuring screen.
| Password – Enter the correct password to unlock write operations on the
parameters in the following levels.
---|---
| RH Calibration low. Offset calibration for RH.
| T Calibration low. Offset calibration for Temperature.
| Protection – Defines the levels of parameters that will be password
protected.
| Password Change. Allows changing the current password. Values from 1 to 999
are allowed.
| Shows the first two digits of the controller electronic serial number.
| Shows the three central digits of the controller electronic serial number.
| Shows the three last digits of the controller electronic serial number.
ERROR MESSAGES
The controller shows messages on the display that correspond to the problems related to the humidity measurement. The control output relay is immediately switched off, when they are shown.
| It indicates that the measurement has exceeded the upper limit of the sensor
range. Possible sensor problem.
---|---
| It indicates that the measurement has exceeded the lower limit of the sensor
range. Possible sensor problem.
| Sensor problem. Check the sensor connections with the controller. If the
problem persists, contact technical assistance.
CONFIGURATION PROTECTION
A protection system to avoid unwanted changes to the controller parameters is
implemented. The level of protection can be selected from partial to full. The
following parameters are part of the protection system:
When this parameter is presented, the correct password must be entered to
allow changes of parameters in the following levels.
Defines the level of parameters that will be password protected:
1 – Only calibration level is protected (factory configuration);
2 – Calibration and Configuration levels are protected;
3 – All levels are protected – calibration, configuration and setpoints.
( Parameter for definition of a new password. Since it is located in the
calibration level, can only be changed by a user that knows the current
password. Valid passwords are in the range 1 to 999.
CONFIGURATION PROTECTION USAGE
The PAS parameter is displayed before entering a protected level. If the correct password is entered, parameters in all following levels can be changed. If wrong or no password is entered, parameters in the following levels will be read only.
Important notes:
- After 05 consecutive attempts to enter a wrong password, new tentative will be blocked for the next 10 minutes. If the current valid password is unknown, the master password can be used only to define a new password for the controller.
- The factory default password is 111.
MASTER PASSWORD
The master password allows user to define a new password for the controller,
even if the current password is unknown. The master password is based in the
serial number of the controller, and calculated as following:
[ 1 ] + [higher digit of SN2 ] + [higher digit of SN1 ] + [higher digit of SN0
]
For example the master password for the device with serial number 97123465 is:
1 9 3 6c As follows:
How to use the master password:
- Enter the master password value at prompt.
- Go to the parameter and enter the new password, which must not be zero (0).
- Now you can use this new password to access all controller parameters with modify rights.
WARRANTY
Warranty conditions are available on our website www.novusautomation.com/warranty.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>