homematic 1500190 IP Wireless Underfloor Heating Controller Instruction Manual
- June 9, 2024
- homematic
Table of Contents
- Information about this manual
- Hazard information
- Function and device overview
- General system information
- Mounting
- Start-up
- Configuration via the Homematic IP Wall Thermostat
- Manual operation
- Delete device connections
- Troubleshooting
- Maintenance and cleaning
- General information about radio operation
- Technical specifications
- Documents / Resources
Installation instruction and operating manual
Floor Heating Controller – 10 channels, 24 V
Information about this manual
Please read this manual carefully before beginning operation with your
Homematic IP component. Keep the manual so you can refer to it at a later date
if you need to. If you hand over the device to other persons for use, please
hand over this manual as well.
Symbols used:
Attention!
This indicates a hazard.
Please note:
This section contains important additional information.
Hazard information
Do not open the device. It does not contain any parts that can be
maintained by the user. If you have any doubts, have the device checked by an
expert.
For safety and licensing reasons (CE), unauthorized change and/or modification
of the device is not permitted.
The device may only be operated in dry and dustfree environment and must
be protected from the effects of moisture, vibrations, solar or other methods
of heat radiation, cold and mechanical loads.
The device is not a toy; do not allow children to play with it. Do not
leave packaging material lying around. Plastic films/bags, pieces of
polystyrene, etc. can be dangerous in the hands of a child.
We do not assume any liability for damage to property or personal injury
caused by improper use or the failure to observe the hazard information. In
such cases, any claim under warranty is extinguished! For consequential
damages, we assume no liability!
The device may only be used for fixed installations.
The device must be securely attached within a fixed installation.
When connecting to the device terminals, take the permissible cables and
cable cross sections into account.
Please take the technical data (in particular the maximum permissible
effective installed load of the floor heating controller and the type of load
to be connected) into account before connecting a load! All load data relates
to ohmic loads. Do not exceed the capacity specified for the device.
Exceeding this capacity could lead to the destruction of the device,
fires or electric shocks.
Before the actuator is connected, remove the fuse from the fuse box or
remove the plug from the socket.
The device has not been designed to support safety disconnection.
**** Observe the installation instructions for installa- tion in distribution
systems (DIN VDE 0100-410).
The device may only be operated within residential buildings.
Using the device for any purpose other than that described in this operating
manual does not fall within the scope of intended use and shall invali- date
any warranty or liability.
Function and device overview
The Homematic IP Floor Heating Controller offers comfortable and demand-based
room-by-room control of your floor heating system via smartphone app or the
omematic IP Wall Thermostat, according to your personal needs.
The floor heating controller can be used for controlling a floor heating
system with up to 10 heating zones/15 heating circuits as well as a heating
pump or circulation pump. Furthermore, the device offers operation in heating
or cooling mode (provided that your heating system offers these operating
modes).
You can flexibly mount the device using the supplied screws or a DIN rail.
With the secure radio communica- tion between the Homematic IP devices, the
wiring effort is kept to a minimum.
Device overview (see fig. 1):
(A) System button (pairing button and LED)
(B) Select button (channel button and LED)
(C) Slot for opening
(D) Cover
(E) Spring latch for DIN rail mounting
(F) 24 V transformer connecting terminals
(G) Heating valves or heating pump connecting terminals
(H) Heating valves connecting terminals
Cable bushings (see fig. 2):
(I) Cable bushing 1
(J) Cable bushing 2
(K) Cable bushing 3
General system information
This device is part of the Homematic IP smart home system and works with the Homematic IP radio protocol. All devices of the system can be configured comfortably and individually with the Homematic IP smartphone app. Alternatively, you can operate the Homematic IP devices via the Central Control Unit CCU3 or in connection with various partner solutions. The available functions provided by the system in combination with other components are described in the Homematic IP User Guide. All current technical documents and updates are provided at www.homematic-ip.com.
Mounting
For operation of the floor heating controller with 24 V, a 24 V/50 Hz power
supply is required. We recommend you to use the Homematic IP Transformer for
Floor Heating Controllers – 24 V (HmIP-FAL24-TR).
When using the floor heating controller in combination with the Homematic IP
Transformer for floor heating controllers – 24 V (HmIP-FAL24-TR), it is
recommended to install the device on the supplied DIN rail. For mounting the
floor heating controller and the transformer to a DIN rail, please proceed as
follows:
-
Please select a suitable mounting location close to your heating manifold.
**** Make sure that no electricity or similar lines run in the wall at this location! -
Use a pen to mark two bore holes for mounting the DIN rail on the wall.
-
Use an appropriate drill to make the holes as illustrated.
-
Fasten the screws and plugs supplied to mount the DIN rail.
-
Place the floor heating controller onto the DIN rail (see fig. 3).
-
Latch the floor heating controller by pressing the spring latches (E) upwards (see fig. 3).
-
Make sure that the spring latches are completely latched and that the device is seated solidly on the rail.
-
Place the transformer next to the floor heating controller onto the DIN rail (see fig. 4).
-
Latch the transformer by pressing the spring latch upwards (see fig. 4.
-
Make sure that the spring latch engages properly and that the device is securely seated on the rail.
Start-up
6.1 Installation instructions
Please read this entire section before starting to install the device.
Please note! Only to be installed by persons with the relevant electro-
technical knowledge and experience!*
Incorrect installation can put
- your own life at risk;
- and the lives of other users of the electrical system.
Incorrect installation also means that you are running the risk of serious
damage to property, e.g. because of a fire. You may be personally liable in
the event of injuries or damage to property.
Contact an electrical installer!
*Specialist knowledge required for installation:
The following specialist knowledge is particularly important during
installation:
-
The “5 safety rules” to be used: Disconnect from mains;
Safeguard from switching on again; Check that system is deenergised; Earth and short circuit; Cover or cordon off neighbouring live parts; -
Select suitable tool, measuring equipment and, if necessary, personal safety equipment;
-
Evaluation of measuring results;
-
Selection of electrical installation material for safeguarding shut-off conditions;
-
IP protection types;
-
Installation of electrical installation material;
-
Type of supply network (TN system, IT system, TT system) and the resulting connecting conditions (classical zero balancing, protective earthing, required additional meas- ures etc.).
For installing the floor heating controller into a power distribution
panel it has to be mounted in accordance with VDE 0603, DIN 43871 (low-voltage
sub-distribution oard), DIN 18015-x. In this case, the installation must be
made on a mounting rail (DIN rail) according to EN50022. Installation and
wiring have to be performed according to VDE 0100 (VDE 0100-410, VDE 0100510
etc.).
Please consider the technical connection requirements (TAB) of your energy
supplier.
Please observe the hazard information in section „2 Hazard information“
on page 47 during installation.
Permitted cable cross sections for the cable bushings of the floor heating
controller are:
Cable bushings | Cable cross section [mm²] |
---|---|
1 (I) (see fig. 2) | > 5.2 |
2 (J) (see fig. 2) | > 8.2 |
3 (K) (see fig. 2) | > 3.2 |
Permitted cable cross sections for connecting to the connecting terminals of the floor heating controller:
rigid cable [mm²] | flexible cable with/without ferrule [mm²] |
---|---|
0.75 – 1.50 | 0.75 – 1.50 |
6.2 Installation
To install the floor heating controller, please proceed as follows:
-
Open the cover (D). Therefore, release the catch under the slot for opening (C) by pushing it with a screwdriver. Remove the cover by pulling it upwards (see fig. 5).
-
Connect the transformer to the connecting terminals (F) of the floor heating controller.
**** Press the terminal down using an appropriate screw driver to open the connecting terminal. Thread the corresponding cable. Release the terminal to close it and to fix the cable (see fig. 6). -
Plug in the connecting cable of the valve actu- ators in your heating circuits to the connecting terminals (G-H). Connect a heating pump using connecting terminal (G).
-
Make sure that all connecting cables are fixed properly to the cable bushings before closing the cover.
-
Close the cover again. Therefore, push the latch- es of the cover into the openings provided and press it down.
-
Plug the mains plug of the transformer into a socket.
6.3 Behaviour after switching on the mains voltage
** After switching on the mains voltage, the LED (B) lights permanently
green.
If the device has not yet been connected, pairing mode will be activated
during the first 3 minutes after the mains voltage has been switched on. You
will find further information about connecting your device in the next
section.
During the first 10 minutes after the mains voltage has been switched on the
device remains in start mode. In this time, all heating zones are triggered
and the channel LED lights permanently. In the following 20 minutes,the
valves areoperated via two-point control. If the temperature falls below the
setpoint temperature, the valves are switched on. If the set- point
temperature is increased, the valves are switched off. After 20 minutes, the
valves are operated via PI control with WM output (normal operation).
6.4 Pairing
** Please read this entire section before starting the pairing procedure.
To integrate the floor heating controller into your system and enable it to
communicate with other devices, you must add it first.
You can either pair the floor heating controller directly with other Homematic
IP devices (e.g. the wall thermostat or the Multi IO Box) or add it in to the
Homematic IP Access Point. After pairing, the device is configured at the wall
thermostat. After adding to the Access Point, the device is configured via the
Homematic IP app.
6.4.1 Pairing with a Homematic IP Wall Thermostat
Please make sure you maintain a distance of at least 50 cm between the
devices.
You can cancel the pairing procedure by briefly pressing the system
button (A) again. This will be indicated by the device LED (A) lighting red.
**** If no pairing operations are carried out, pairing mode is exited
automatically after 3 seconds.
If you want to pair the floor heating controller with a Homematic IP Wall
Thermostat, the pairing mode of both devices has to be activated first. To do
this, proceed as
follows:
- Select the channel for pairing a device by pressing the select button (B) briefly (see fig. 7). Press once for channel 1, twice for channel 2 etc. The channel LED lights permanently for the corresponding channel.
- Press and hold down the system button (A) for 4 seconds until the LED quickly starts flashing or-ange (see fig. 7). The pairing mode of the selected channel remains activated for 3 minutes.
- Press and hold down the system button of the wall thermostat for at least 4 seconds to activate the pairing mode. The device LED flashes orange.
The device LED (A) lights up green to indicate that pairing has been
successful.
If pairing failed, the device LED (A) lights up red. Please try again.
6.4.2 Pairing with a Homematic IP Multi IO Box
If you want to pair the floor heating controller with a Homematic IP Multi IO
Box, the pairing mode of both devices has to be activated first. To do this,
proceed as follows:
- Briefly press the select button (B) until the LEDs of all channels light up green (see fig. 7).
- Press and hold down the system button (A) for 4 seconds until the LED quickly starts flashing orange (see fig. 7). Pairing mode remains activated for 3 minutes.
- Press and hold down the system button of the Multi IO Box for at least 4 seconds to activate the pairing mode. The device LED flashes orange.
The device LED (A) lights up green to indicate that pairing has been
successful. If pairing failed, the device LED (A) lights up red. Please try
again.
6.4.3 Adding a new floor heating controller
To add a new floor heating controller to the system or to the existing
devices, please proceed as follows:
-
First pair the new floor heating controller with an existing one. Activate the pairing mode of the existing floor heating controller. Therefore, press and hold down the system button (A) for at least 4 seconds.
-
Activate the pairing mode of th new floor heating controller. Press and hold down the system button (A) for at least 4 seconds.
**** The device LED (A) lights up green to indicate that pairing has been successful. If pairing failed, the device LED (A) lights up red. Please try again. -
You can add the new floor heating controller to other devices such as the wall thermostat or the Multi IO Box. Simply activate the pairing mode of the floor heating controller first and of the device you want to pair afterwards. For further information, please refer to the user manualof the corresponding device.
6.4.4 Adding to the Homematic IP Access Point
First set up your Homematic IP Access Point via the Homematic IP app
to enable operation of other Homematic IP devices within your system. For
further information, please refer to the operating manual of the Access Point.
You can connect the device either to the Access Point or to the
Homematic Central Control Unit CCU3. For detailed information, please refer to
the Homematic IP User Guide, available for download in the download area of
www.homematic-ip.com.
To add the floor heating controller to the Access Point, please proceed as
follows:
-
Open the Homematic IP app on your smartphone.
-
Select the menu item “Add device”.
-
Briefly press the system button (A) until the LED quickly starts flashing orange (see fig. 7). The pairing mode of the selected channel remains activated for 3 minutes.
**** You can manually start the pairing mode for another 3 minutes by pressing the system button (A) briefly (see fig. 7). -
Your device will automatically appear in the Homematic IP app.
-
To confirm, please enter the last four digits of the device number (SGTIN) in your app or scan the QR code. Therefore, please see the sticker supplied or attached to the device.
-
Please wait until pairing is completed.
-
If pairing was successful, the LED lights up green. The device is now ready for use.
-
If the LED lights up red, please try again.
-
Select the desired solution for your device.
-
In the app, give the device a name and allocate it to a room.
Configuration via the Homematic IP Wall Thermostat
**** The Homematic IP Floor Heating Controller can be configured via the
Homematic IP Wall Ther- mostat (HmIP-WTH-2), via the Homematic IP Access Point
together with thesmartphone appor via the WebUI of the Homematic Central
Control Unit CCU3.
To configure the floor heating controller using the wall thermostat, please
proceed as follows:
-
Press and hold down the control wheel of the wall thermostat to open the configuration menu.
-
Select the symbol by turning the control wheel and confirm by pressing the control wheel briefly.
-
If the wall thermostat is connected to more than one floor heating controller, please select the required floor heating controller using the control wheel.
-
Please define if you want to configure the device parameters (”UnP1/UnP2”) or the channel parameters (”ChAn”).
**** All the settings that are made under “UnP1/UnP2” will be applied to the entire device. All settings that are made under “ChAn” will be applied to the single channels of the device. -
You can individually adjust the line-up time/follow-up time, eco temperatures, intervals etc. according to the following table.
Device parameter UnP1:
Parameter | Index | Value | Meaning |
---|---|---|---|
Frost protection tempera- ture | P024 | 3 |
4
5
…
16
…
19
20| Frost protection activated
2.0 °C
2.5 °C
…
8.0 °C (default)
…
9.5 °C
10.0 °C
Pump control activated/ deactivated, Load balancing 1 /
Load collection 2 Drive type (NO/ NC) 3| P025| 0
1
2
3
4
5
6
7| Pump control activated 4 Load alancing NC Pump control activated 4
Load balancing NO Pump control ctivated 4 Load collection NC
Pump control activated *4 Load collection NO Pump control deactivated
(default) Load balancing NC Pump control deactivated Load balancing NO Pump
control deactivated Load collection NC Pump control deactivated Load
collection NO
Emergency operation in heating mode| P026| 0
1
…
25
…
99
100| 0%
1 %
…
25 % (default)
…
99 %
100 %
Emergency operating in cooling mode| P032| 0
1
…
99
100| 0 % (default)
1 %
…
99 %
100 %
1: Heating zones will be controlled in a staggered way (if possible)
2: Heating zones will be controlled collectively (if possible)
3: Normally open/normally closed
4: If heating zone 1 is used as pump control, it is necessary to add a wall thermostat to this heating zone, if an adaptation of the pump parameters shall be performed.
Device parameter UnP2:
Parameter | Index | Value | Meaning |
---|---|---|---|
Duration | P007 | 128 | 0 minutes |
of valve protection function | 129 | ||
133 | 1 minute |
5 minutes (default)
| | 138| 10 minutes
Invertal| P051| 224| 0 days
time for valve protection function| | 225
238| 1 day
14 days (default)
| | 251| 27 days
| | 252| 28 days
Channel parameter ChAn:
Parameter | Index | Value | Meaning |
---|---|---|---|
Switch on delay for pump (only for channel 1) | P006 | 128 |
129
130
…
147
148| 0 minutes
1 minute
2 minutes (default)
…
19 minutes
20 minutes
Duration of pump protection function
(only for channel 1)| P007| 128
129
…
137
138| 0 minutes
1 minute (default)
…
9 minutes
10 minutes
Switch off delay for pump (only for channel 1)| P008| 128
129
130
…
147
148| 0 minutes
1 minute
2 minutes (default)
…
19 minutes
20 minutes
Minimum floor temperature in connection with a floor temperature sensor| P045|
10
11
…
38
…
59
60| 5.0 °C
5.5 °C
…
19.0 °C (default)
…
29.5°C
30.0°C
Humidity limit| P050| 40
…
80
…
168
…
188
…
208| 40 %: humidity limit deactivated
…
80 %: humidity limit deactivated
…
40 %: humidity limit activated
…
60 %: humidity limit activated (default)
…
80 %: humidity limit activated
Time interval for pump protection function
(only for channel 1)| P051| 225
226
…
238
…
251
252| 1 day
2 days
…
14 days (default)
…
27 days
28 days
Cooling in cooling mode| P052| 0
1| Cooling in cooling mode deactivated
Cooling in cooling mode activated (default)
Heating in heating mode| P053| 0
1| Heating in heating mode deactivated
Heating in heating mode activated (default)
Selection of heating system| P055| 0
1
2
3
4| Standard floor heating (default)
Low energy floor heating
Radiator
Passive convector
Active convector
Pre-humidity limit| P178| 40
…
80
…
168
…
188
…
208| 40 %: humidity limit deactivated
…
80 %: humidity limit deactivated
…
40 %: humidity limit activated
…
60 %: humidity limit activated (default)
…
80 %: humidity limit activated
**** For further information regarding the configuration, please refer to the user manual of the Homematic IP Wall Thermostat (HmIP-WTH-2).
Manual operation
8.1 Switch heating zones on/off
For installation and tests you can manually switch single heating zones on
or off. To switch single heating zones on or off, please proceed as follows:
- Select the required channel using the select button (B) (see fig. 7).
- Press the select button until the LED (B) flashes green three times.
The channel will be switched on or off for 15 minutes.
Afterwards, normal operation will be continued for the heating zone.
8.2 Activating/deactivating the pump control
If you want to use connection terminal (H) for controlling a heating pump, the
heating zone can be switched to pump control directly via the device. To do
this, proceed as follows:
-
Press the select button (B) until the LED of channel 1 starts flashing green (see fig. 7).
**** If the LED of channel 1 starts flashing slowly, the pump control is activated. If the LED of channel 1 starts flashing quickly, the pump control is deactivated. -
If you do not want to change any parameters, you can exit the menu by pressing the select button (B) briefly.
-
To switch the parameter from activated to deactivated or from deactivated to activated, press and hold down the select button (B) for at least 4 seconds.
Delete device connections
To delete the device connections between the floor heat- ing controller and the wall thermostat, please proceed as follows:
- Select the channel of the floor heating controller to which the wall thermostat is connected using the select button (B) (see fig. 7).
- Press the system button (A) and the select button (B) of the floor heating simultaneously until the LED flashes green.
- Restore the factory settings of the wall thermostat (for further information, please refer to the user manual of the wall thermostat).
Troubleshooting
10.1 Command not confirmed
If at least one receiver does not confirm a command, the device LED lights up
red at the end of the failed transmission process. The failed transmission may
be caused by radio interference (see „13 General information about radio
operation“ on page 77). This may be caused be the following:
- Receiver cannot be reached.
- Receiver is unable to execute the command (load failure, mechanical blockade, etc.).
- Receiver is defective.
10.2 Duty cycle
The duty cycle is a legally regulated limit of the transmission time of
devices in the 868 MHz range. The aim of this regulation is to safeguard the
operation of all devices working in the 868 MHz range. In the 868 MHz
frequency range we use, the maximum transmission time of any device is 1% of
an hour (i.e. 36 seconds in an hour). Devices must cease transmission when
they reach the 1% limit until this time restriction comes to an end. Homematic
IP devices are designed and produced with 100% conformity to this regulation.
During normal operation, the duty cycle is not usually reached. However,
repeated and radio-intensive pairing processes mean that it may be reached in
solated instances during start-up or initial installation of a system.
If the duty cycle is exceeded, this is indicated by three long flashes of the
device LED, and may manifest itself in the device temporarily working
incorrectly. The device starts working correctly again after a short period
(max. 1 hour).
10.3 Error codes and flashing sequences
10.3.1 Flashing sequences of the system LED (A)
Flashing code | Meaning | Solution |
---|---|---|
Short orange flashing | Radio transmission/ attempting to transmit/ data | |
transmission | Wait until the transmission is completed. | |
1x long green lighting | Transmission confirmed | You can continue operation. |
1x long red lighting | Transmission failed | Please try again (s. „10.1 Command |
not confirmed“
on page 72).
Short orange flashing (every 10 s)| Pairing mode active| Please enter the last
four numbers of the device
serial number to confirm (see „6.4 Pairing“ on page37).
1x long red lighting| Transmission failed or duty cycle limit is reached|
Please try again (see sec. „10.1 Command notconfirmed“ on page 72 or „10.2
Duty cycle“ on page 72).
6x long red flashing| Device defective| Please see your app for error message
or contact your retailer.
1x orange and 1 x green lighting| Test display| Once the test display has
stopped, you can continue.
10.3.2 Flashing sequences of the channel LED
Flashing code | Meaning | Solution |
---|---|---|
Slow flashing | Emergency operation activated | Change batteries of the wall |
thermostat, perform a
communication test, re-position the wall thermostat (if required), replace
wall thermostat if defective
Short double flashing| Radio connection to wall thermostat failed| Re-position
wall thermostat or add a repeater (see sec.
„10.1 Command not confirmed“ on page 72).
11 Restore factory settings
**** The factory settings of the device can be restored. If you do this, you
will lose all your settings.
To restore the factory settings of the floor heating controller, please proceed as follows:
- Press and hold down the system button (A) for 4 seconds until the LED quickly starts flashing orange (see fig. 7).
- Release the system button again.
- Press and hold down the system button again for 4 seconds, until the status LED lights up green.
- Release the system button to finish the procedure.
The device will perform a restart. After the restart, you can again integrate your device into your Homematic IP system.
Maintenance and cleaning
**** The product does not require any maintenance.
Enlist the help of an expert to carry out any maintenance or repairs.
Clean the device using a soft, lint-free cloth that is clean and dry. Do not
use any detergents containing solvents, as they could corrode the plastic
housing and label.
General information about radio operation
Radio transmission is performed on a non-exclusive transmission path, which
means that there is a possibility of interference occurring. Interference can
also be caused by witching operations, electrical motors or defective
electrical devices.
**** The range of transmission within buildings can differ greatly from that
available in the open air. Besides the transmitting power and the reception
characteristics of the receiver, environmental factors such as humidity in the
vicinity have an important role to play, as do on-site structural/ screening
conditions.
Hereby, eQ-3 AG, Maiburger Str. 29, 26789 Leer/Germany declares that the radio
equipment type Homematic IP HmIP-FAL24-C10 is in compliance with Directive
2014/53/EU. The full text of the EU declaration of conformity is available at
the following internet address: www.homematic-ip.com
Technical specifications
Device short description: | HmIP-FAL24-C10 |
---|---|
Construction of the regulation and control device: | independently mounted |
electronic regulationand control device, surface mount
Number of heating zones:| 10
Number of actuators:| 15 / (14)
Number of pumps:| 1
Supply voltage:| 24 V/50 Hz
Current consumption:| 1.25 A max.
Switching capacity per heating zone:| 1 A max.
Nominal load of all actuators:| 24 W
Cable type and cross section:| rigid and flexible cable, 0.75 – 1.5 mm²
Cable cross section of cable bushing 1:| > 5.2 mm
Cable cross section of cable bushing 2:| > 8.2 mm
Cable cross section of cable bushing 3:| > 3.2 mm
Degree of protection:| IP20
Protection class:| III
Ambient temperature:| 0 – 50°C
Type:| 1
Withstand voltage:| 2500 V
Temperature glow wire test:| 850 °C
Temperature ball pressure test:| 125 °C
PTI value of housing:| IIIb with 100 < CTI < 175
Dimensions (W x H x D):| 225 x 75 x 52 mm
Weight:| 282 g
Radio frequency band:| 868.0–868.6 MHz/
869.4–869.65 MHz
Maximum radiated power:| 10 dBm
Receiver category:| SRD category 2
Typ. open area RF range:| 270 m
Duty cycle:| < 1% per h/< 10% per h
Subject to technical changes.
Instructions for disposal
Do not dispose of the device with regular domestic waste! Electronic equipment
must be disposed of at local collection points for waste electronic equipment
in compliance with the Waste Electrical and Electronic Equipment Directive.
Information about conformity
The CE sign is a free trading sign addressed exclusively to the
authorities and does not include any warranty of any properties.
For technical support, please contact your retailer.
Kostenloser Download der Homematic IP App! Free download of the Homematic
IP app!
| https://itunes.apple.com/de/app/homematic-ip/id1012842369?mt=8
---|---
|
https://play.google.com/store/apps/details?id=de.eq3.pscc.android&hl=de
Bevollmächtigter des Herstellers:
Manufacturer’s authorised representative: eQ-3 AG
Maiburger Straße 29
26789 Leer / GERMANY
www.eQ-3.de
Documents / Resources
|
homematic 1500190 IP Wireless Underfloor Heating
Controller
[pdf] Instruction Manual
1500190, IP Wireless Underfloor Heating Controller, Underfloor Heating
Controller, IP Wireless Heating Controller, Heating Controller, Controller
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>