Warmup Multiple-Entry Power Connection With Junction Box Instruction Manual
- June 9, 2024
- Warmup
Table of Contents
Multiple-Entry Power Connection With Junction Box
Instruction Manual The world’s best-selling floor
heating brand”
MULTIPLE-ENTRY POWER CONNECTION WITH JUNCTION BOX
INSTALLATION INSTRUCTIONS
DESCRIPTION
This durable corrosion resistant enclosure is used in pipe freeze protection
applications to create a safe enclosure for electrical connection between the
power supply and max. 3 heating cable(s). It is approved by CSA for use in
hazardous and non-hazardous areas.
The PTBS-GET provides a silicone-free installation providing a waterproof
enclosure for cable connections. The stand provides guided entry into the
enclosure for the heating cable and positions the junction box clear of any
pipe insulation.
The spring clamp terminals provide safe, reliable, maintenance-free operation.
PTBS-GET contains all the necessary materials for a complete certified
installation.
SPECIFICATION
PRODUCT CODE | SR-SFIT-BOX-S (PTBS-GET) |
---|---|
OPERATING TEMPERATURES | -40°F to +212°F / -40°C to +50°C |
IP RATING | IP67 |
MATERIAL | Glass reinforced Polyester, Fire Retardant |
USAGE | Class1.Div2,Group A,B,C,D |
Class2.Div2,Group E,F,G Class3.Div2
DIMENSIONS
INSTALLATION
Push the heating cable(s) through
the lower bracket, leaving 300mm of heating cable exposed.
NOTE: Max. 3 heating cables.Measure 165mm in
from the end of the cable and carefully cut the outer sheath. Bend the cable
to break sheath. Next, gently slice the outer sheath up the centre between the
first cut mark and the end of cable. Bend the cable to break sheath and remove
the sheath from the heating cable.Move the
braid back toward the outer sheath. At the base of the braid where it meets
the outer sheath, gently separate the braid to make an opening.While bending the heating cable,
work the heating cable through the braid opening and then pull the braid tight
and twist.Separate the bus wires from the
self-regulating matrix material with a utility knife.
Peel back the exposed bus wires. DO NOT CUT THE BUS WIRES.Cut the exposed self-regulating matrix back to the heating cable
insulation. DO NOT CUT THE BUS WIRES.Cut the
exposed self-regulating matrix back to the heating cable insulation. DO NOT
CUT THE BUS WIRES.Insert the bus wires through
heat shrink tubes.
Insert the braiding through the ground tube.
NOTE: If there is a second or third cable, repeat step 2 to step
9.Insert the prepared cables into
the lower bracket ensuring they extend 132mm beyond the bracket, and then
tighten the 4 screws.
Insert the cables through the
base of the junction box. Secure the lower bracket to the junction box using
the lock ring.
Connect the bus wires (black) and ground wires (green) to the terminals as
shown.
Connect the power supply wires (black) and ground wires (green) to the
terminals as shown.
Warmup Inc.
25-A Francis Clarke
Circle, Bethel,
CT 06801
W: www.warmup.com
E: us@warmup.com
T: 888-927-6333
F: 888-927-4721
Warmup Canada
E: ca@warmup.com
T: 888-592-7687
F: 888-927-4721
WARMUP – IM – PTBS-GET – V1.1 2022-12-07_NAM-EN