DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module Instruction Manual
- June 8, 2024
- Delta
Table of Contents
- DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module
- Product Profile & Dimension
- External Wiring
- I/O Terminal Layout
- Electrical Specifications
- Functions Specifications
- Control Register
- 0
- 1| O| R| Firmware version| Display the current firmware version in hex.
- 2
- 3
- 4
- 5
- 16| X| R/W| CH1 output signal value| Voltage output range: K-32,000~K32,000.
- 17| X| R/W| CH2 output signal value
- 18| X| R/W| CH3 output signal value
- 19| X| R/W| CH4 output signal value
- 28| O| R/W| Adjusted Offset value of CH1| Set the adjusted Offset value of
- 29| O| R/W| Adjusted Offset value of CH2
- 30| O| R/W| Adjusted Offset value of CH3
- 31| O| R/W| Adjusted Offset value of CH4
- 34| O| R/W| Adjusted Gain value of CH1| Set the adjusted Gain value of CH1 ~
- 35| O| R/W| Adjusted Gain value of CH2
- 36| O| R/W| Adjusted Gain value of CH3
- 37| O| R/W| Adjusted Gain value of CH4
- 40| O| R/W| Function: Set value changing prohibited| Prohibit set value
- 41| X| R/W| Function: Save all the set values| Save all the set values.
- 43| X| R| Error status| Register for storing all error status. Refer to table
- 100
- 101
- 102| O| R/W| Set value of CH1 upper bound|
- 103| O| R/W| Set value of CH2 upper bound
- 104| O| R/W| Set value of CH3 upper bound
- 105| O| R/W| Set value of CH4 upper bound
- 108| O| R/W| Set value of CH1 lower bound|
- 109| O| R/W| Set value of CH2 lower bound
- 110| O| R/W| Set value of CH3 lower bound
- 111| O| R/W| Set value of CH4 lower bound
- 114| O| R/W| Output update time of CH1| Set value of CH1~CH4 lower bound.
- 115| O| R/W| Output update time of CH2| range:K0~K100. Default =H’0000.
- 116| O| R/W| Output update time of CH3
- 117| O| R/W| Output update time of CH4
- 118
- Explanation on Special Registers D9900~D9999
- Adjust D/A Conversion Curve
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module
Thank you for choosing Delta’s DVP series PLC. DVP02DA-E2 (DVP04DA-E2) analog output module receives 2 (4) groups of 16-bit digital data from the PLC MPU and converts the digital data into 2 (4) points analog output signals (voltage or current). In addition, you can access the data in the module by applying FROM/TO instructions or write the output value of channels directly by using MOV instruction (Please refer to allocation of special registers D9900 ~ D9999).
-
DVP02DA-E2 (DVP04DA-E2) is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP02DA-E2 (DVP04DA-E2), or to prevent an accident from damaging DVP02DA-E2 (DVP04DA-E2), the control cabinet in which DVP02DA-E2 (DVP04DA-E2) is installed should be equipped with a safeguard. For example, the control cabinet in which DVP02DA-E2
(DVP04DA-E2) is installed can be unlocked with a special tool or key. -
DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP02DA-E2 (DVP04DA-E2) is powered up. After DVP02DA-E2 (DVP04DA-E2) is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVP02DA-E2 (DVP04DA-E2) is correctly grounded in order to prevent electromagnetic interference.
Product Profile & Dimension
External Wiring
Note 1: Please isolate analog output and other power wiring.
Note 2: If noise interferes from loaded input wiring terminal is
significant, please connect a capacitor with 0.1 ~ 0.47μF 25V for noise
filtering.
Note 3: Please connect power module terminal and analog output module
terminal to system
I/O Terminal Layout
Electrical Specifications
Digital/Analog module (02D/A & 04D/A)
Power supply voltage| 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Digital/Analog module (02D/A & 04D/A)
Max. rated power consumption|
02DA: 1.5W, 04DA: 3W, supply by external power source.
Connector| European standard removable terminal block (Pin pitch: 5mm)
Protection
| Voltage output is protected by short circuit. Short circuit lasting for too long may cause damage on internal circuits. Current output can
be open circuit.
Operation/storage temperature
| Operation: 0°C~55°C (temperature), 5~95% (humidity), Pollution degree2
Storage: -25°C~70°C (temperature), 5~95% (humidity)
Vibration/shock immunity| International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)
Series connection to DVP-PLC MPU
| The modules are numbered from 0 to 7 automatically by their distance from MPU. Max. 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.
Functions Specifications
Digital/Analog module | Voltage output | Current output |
---|---|---|
Range of analog output | -10V ~ 10V | 0 ~ 20mA |
Range of digital conversion |
-32,000 ~ +32,000
|
0 ~ +32,000
|
0 ~ +32,000
Max./Min. range of digital data|
-32,768 ~ +32,767
|
0 ~ +32,767
|
-6,400 ~ +32,767
Hardware Resolution| 14 bits| 14 bits| 14 bits
Max. output current| 5mA| -
Tolerance load impedance|
1KΩ ~ 2MΩ
|
0 ~ 500Ω
Analog output channel| 2 channels or 4 channels / each module
Output impedance| 0.5Ω or lower
Overall accuracy
| ±0.5% when in full scale (25°C, 77°F)
±1% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F)
Response time| 400μs / each channel
Digital data format| 2’s complement of 16 bits
Isolation method
| Optical coupler isolation between analog circuits and digital circuits. No isolation among analog channels.
500VDC between digital circuits and Ground 500VDC between analog circuits and Ground 500VDC between analog circuits and digital circuits
500VDC between 24VDC and Ground
Control Register
CR# | Attrib. | Register name | Explanation |
---|
0
|
O
|
R
|
Model name
| Set up by the system, model code:
DVP02DA-E2 = H’0041; DVP04DA-E2 = H’0081
1| O| R| Firmware version| Display the current firmware version in hex.
2
|
O
|
R/W
|
CH1 output mode setting
| Output mode: Default = H’0000. Take CH1 for example:
CR#| Attrib.| Register name| Explanation
---|---|---|---
3
|
O
|
R/W
|
CH2 output mode setting
| Mode 0 (H’0000): Voltage output (±10V) Mode 1 (H’0001): Current output (0~+20mA)
Mode 2 (H’0002): Current output (+4~+20mA)
Mode -1 (H’FFFF): All channels are unavailable
4
|
O
|
R/W
|
CH3 output mode setting
5
|
O
|
R/W
|
CH4 output mode setting
16| X| R/W| CH1 output signal value| Voltage output range: K-32,000~K32,000.
Current output range: K0~K32,000.
Default: K0.
CR#18~CR#19 of DVP02DA-E2 are
reserved.
17| X| R/W| CH2 output signal value
18| X| R/W| CH3 output signal value
19| X| R/W| CH4 output signal value
28| O| R/W| Adjusted Offset value of CH1| Set the adjusted Offset value of
CH1 ~ CH4. Default = K0
Definition of Offset:
The corresponding voltage (current) input value when the digital output value = 0
29| O| R/W| Adjusted Offset value of CH2
30| O| R/W| Adjusted Offset value of CH3
31| O| R/W| Adjusted Offset value of CH4
34| O| R/W| Adjusted Gain value of CH1| Set the adjusted Gain value of CH1 ~
CH4. Default = K16,000.
Definition of Gain:
The corresponding voltage (current) input value when the digital output value = 16,000
35| O| R/W| Adjusted Gain value of CH2
36| O| R/W| Adjusted Gain value of CH3
37| O| R/W| Adjusted Gain value of CH4
Adjusted Offset Value, Adjusted Gain Value:
Note1: When using Mode 2, the channel do NOT provide setups for adjusted Offset or Gain value.
Note2: When input mode changes, the adjusted Offset or Gain value automatically returns to defaults.
40| O| R/W| Function: Set value changing prohibited| Prohibit set value
changing in CH1 ~ CH4. Default= H’0000.
41| X| R/W| Function: Save all the set values| Save all the set values.
Default =H’0000.
43| X| R| Error status| Register for storing all error status. Refer to table
of error status for more information.
100
|
O
|
R/W
| Function: Enable/Disable limit detection| Upper and lower bound detection, b0~b3 corresponds to CH1~CH4 (0: Disable/ 1: Enable). Default= H’0000.
101
|
X
|
R/W
|
Upper and lower bound status
| Display the upper and lower bound status. (0: Not exceed /1: Exceeds upper or lower bound value), b0~b3 corresponds to Ch1~Ch4 for lower bound detection result; b8~b11 corresponds to CH1~CH4 for upper
bound detection result..
102| O| R/W| Set value of CH1 upper bound|
Set value of CH1~CH4 upper bound. Default
= K32000.
103| O| R/W| Set value of CH2 upper bound
104| O| R/W| Set value of CH3 upper bound
105| O| R/W| Set value of CH4 upper bound
108| O| R/W| Set value of CH1 lower bound|
Set value of CH1~CH4 lower bound. Default
= K-32000.
109| O| R/W| Set value of CH2 lower bound
110| O| R/W| Set value of CH3 lower bound
111| O| R/W| Set value of CH4 lower bound
114| O| R/W| Output update time of CH1| Set value of CH1~CH4 lower bound.
Setting
CR#| Attrib.| Register name| Explanation
---|---|---|---
115| O| R/W| Output update time of CH2| range:K0~K100. Default =H’0000.
116| O| R/W| Output update time of CH3
117| O| R/W| Output update time of CH4
118
|
O
|
R/W
|
LV output mode setting
| Set the output mode of CH1~CH4 when the power is at LV (low voltage) condition.
Default= H’0000.
Symbols:
O: When CR#41 is set to H’5678, the set value of CR will be saved. X: set value will not be saved.
R: able to read data by using FROM instruction.
W: able to write data by using TO instruction.
Description
bit0
|
K1 (H’1)
|
Power supply error
|
bit11
|
K2048(H’0800)
| Upper / lower bound setting error
bit1
|
K2 (H’2)
|
Reserved
|
bit12
|
K4096(H’1000)
| Set value changing prohibited
bit2
|
K4 (H’4)
|
Upper / lower bound error
|
bit13
|
K8192(H’2000)
| Communication breakdown on next module
bit9| K512(H’0200)| Mode setting error|
$ Note: Each error status is determined by the corresponding bit (b0 ~
b13) and there may be more than 2 errors occurring at the same time. 0 =
normal; 1 = error
Module Reset (available for firmware V1.12 or above): When modules need reset, write H’4352 to CR#0, then wait for one second and then power off and restart. The instruction initializes all parameter setups. To avoid the resetting process affecting the normal operation of other modules, it is recommended to connect only one module at a time.
Explanation on Special Registers D9900~D9999
When DVP-ES2 MPU is connected with modules, registers D9900~D9999 will be
reserved for storing values from modules. You can apply MOV instruction to
operate values in D9900~D9999.
When ES2 MPU is connected with DVP02DA-E2/DVP04DA-E2, the configuration of
special registers is as below:
Module #0| Module #1| Module #2| Module #3| Module #4| Module #5| Module #6| Module #7|
Description
---|---|---|---|---|---|---|---|---
D1320| D1321| D1322| D1323| D1324| D1325| D1326| D1327| Model Code
D9900| D9910| D9920| D9930| D9940| D9950| D9960| D9970| CH1 output value
D9901| D9911| D9921| D9931| D9941| D9951| D9961| D9971| CH2 output value
D9902| D9912| D9922| D9932| D9942| D9952| D9962| D9972| CH3 output value
D9903| D9913| D9923| D9933| D9943| D9953| D9963| D9973| CH4 output value
Adjust D/A Conversion Curve
Users can adjust the conversion curves according to the actual needs by
changing the Offset value (CR#28 ~ CR#31) and Gain value (CR#34 ~ CR#37).
Gain: The corresponding voltage/current input value when the digital
output value = 16,000.
Offset: The corresponding voltage/current input value when the digital
output value = 0.
- Equation for voltage output Mode0: 0.3125mV = 20V/64,000
Mode 0 (CR#2 ~ CR#5) | -10V ~ +10V,Gain = 5V (16,000),Offset = 0V (0) |
---|---|
Range of digital data | -32,000 ~ +32,000 |
Max./Min. range of digital data | -32,768 ~ +32,767 |
- Current output – mode 1:
Mode 1 (CR#2 ~ CR#5) | 0mA ~ +20mA,Gain = 10mA (16,000),Offset = 0mA (0) |
---|---|
Range of digital data | 0 ~ +32,000 |
Max./Min. range of digital data | 0 ~ +32,767 |
Current output – mode 2:
Mode 2 (CR#2 ~ CR#5) | 4mA ~ +20mA,Gain = 12mA (19,200),Offset = 4mA (6,400) |
---|---|
Range of digital data | 0 ~ +32,000 |
Max./Min. range of digital data | -6400 ~ +32,767 |