Nexia Remote Temperature and Humidity Sensor TH100NX Manual

June 8, 2024
NEXIA

Nexia

Remote Temperature and Humidity Sensor

SKU: TH100NX

Quickstart

This is a ****

Alarm Sensor
for
U.S. / Canada / Mexico
.

Please make sure the internal battery is fully charged.

To add this device to your network execute the following action:
Set your primary controller into inclusion mode.Press and release the “Install” button on the sensor.The “Status” LED will blink rapidly for 3 seconds indicating successful inclusion into the network.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The Remote Temperature and Humidity sensor is a Z-Wave Plus multilevel, battery-powered, routing sensor that measures and reports indoor temperature and relative humidity.The reporting intervals and thresholds for the indoor temperature, indoor humidity and battery are configurable.The wakeup interval is also configurable. This sensor cannot be used with Trane/American Standard thermostats for HVAC control.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

Press and hold Install button for 10 seconds.Factory Reset should only be used if the primary controller is missing or inoperable.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

Set your primary controller into inclusion mode.Press and release the “Install” button on the sensor.The “Status” LED will blink rapidly for 3 seconds indicating successful inclusion into the network.

Exclusion

Set your primary controller into exclusion mode.Press and release the “Install” button on the sensor.The “Status” LED will blink rapidly for 3 seconds indicating successful exclusion from the network.

Communication to a Sleeping device (Wakeup)

This device is battery operated and turned into deep sleep state most of the time
to save battery life time. Communication with the device is limited. In order to
communicate with the device, a static controller C is needed in the network.
This controller will maintain a mailbox for the battery operated devices and store
commands that can not be received during deep sleep state. Without such a controller,
communication may become impossible and/or the battery life time is significantly
decreased.

This device will wakeup regularly and announce the wakeup
state by sending out a so called Wakeup Notification. The controller can then
empty the mailbox. Therefore, the device needs to be configured with the desired
wakeup interval and the node ID of the controller. If the device was included by
a static controller this controller will usually perform all necessary
configurations. The wakeup interval is a tradeoff between maximal battery
life time and the desired responses of the device. To wakeup the device please perform
the following action:

A triple press of the “Install” button wakes the device up, and it will send a WAKE_UP_NOTIFICATION and a Battery Report (if on a network).A single press of “Install” button will wake the device up, and it will send out a Node Information Frame.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 1| Z-Wave Plus Lifeline:COMMAND_CLASS_BATTERY, BATTERY_REPORTCOMMAND_CLASS_SENSOR_MULTILEVEL, SENSOR_MULTILEVEL_REPORTCOMMAND_CLASS_DEVICE_RESET_LOCALLY, DEVICE_RESET_LOCALLY_NOTIFICATION
---|---|---
2| 5| Temperature reports from:COMMANDCLASS SENSOR_MULTILEVEL, SENSOR_MULTILEVEL_REPORT
3| 5| Humidity reports from:COMMANDCLASS SENSOR_MULTILEVEL, SENSOR_MULTILEVEL_REPORT
4| 5| Temperature driven BASIC_SETs from:COMMAND_CLASS_BASIC, BASIC_SET
5| 5| Humidity driven BASIC_SETs from:COMMAND_CLASS_BASIC, BASIC_SET
6| 5| BATTERY_REPORT sent when sent to Lifeline:COMMAND_CLASS_BATTERY, BATTERY_REPORT

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Battery Report Interval

Time between Battery Reports in hours
Size: 1 Byte, Default Value: 0

SettingDescription

1 – 127 Hours, unsigned
0 Disabled

Parameter 10: Group2 Temp Threshold

Group2 – temperature delta auto-send threshold (how many degrees change from the last auto-send)
Size: 1 Byte, Default Value: 10

SettingDescription

1 – 50 Tenths of degrees, unsigned

Parameter 11: Group2 Temp Interval

Group2 – periodic temperature send interval (minutes)
Size: 1 Byte, Default Value: 0

SettingDescription

0 Disabled
1 – 120 Minutes, unsigned

Parameter 12: Basic Set ON Above RH

Send Basic Set ON above humidity
Size: 1 Byte, Default Value: 0

SettingDescription

1 – 100 %, unsigned
0 Disabled

Parameter 13: Basic Set ON Below RH

Send Basic Set ON below humidity
Size: 1 Byte, Default Value: 0

SettingDescription

0 Disabled
1 – 100 %, unsigned

Parameter 14: Basic Set OFF Above RH

Send Basic Set OFF above humidity
Size: 1 Byte, Default Value: 0

SettingDescription

0 Disabled
1 – 100 %, unsigned

Parameter 15: Basic Set OFF Below RH

Send Basic Set OFF below humidity
Size: 1 Byte, Default Value: 0

SettingDescription

1 – 100 %, unsigned
0 Disabled

Parameter 16: Group1 RH Threshold

Group1 – humidity delta auto-send threshold (how much % change from the last auto-send)
Size: 1 Byte, Default Value: 5

SettingDescription

1 – 50 %, unsigned

Parameter 17: Group1 RH Interval

Group1 – periodic humidity send interval (minutes)
Size: 1 Byte, Default Value: 0

SettingDescription

0 Disabled
1 – 120 Minutes, unsigned

Parameter 18: Group3 RH Threshold

Group3 – humidity delta auto-send threshold (how much % change from the last auto-send)
Size: 1 Byte, Default Value: 5

SettingDescription

1 – 30 %, unsigned

Parameter 19: Group3 RH Interval

Group3 – periodic humidity send interval (minutes)
Size: 1 Byte, Default Value: 0

SettingDescription

1 – 120 Minutes, unsigned
0 Disabled

Parameter 2: Basic Set ON Above Temp

Send Basic Set ON above temp
Size: 1 Byte, Default Value: 121

SettingDescription

121 Disabled
-40 – 120 Fahrenheit

Parameter 20: Basic Set Option

Basic Set options for Temp and Humidity
Size: 1 Byte, Default Value: 1

SettingDescription

2 Enabled Registers 2, 5, 13, 14
3 Enable Registers 3, 4, 12, 15
4 Enabled Registers 3, 4, 13, 14
1 Enable Registers 2, 5, 12, 15

Parameter 21: Temp Offset

Temperature offset
Size: 1 Byte, Default Value: 0

SettingDescription

-7 – 7 Degrees

Parameter 22: Humidity Offset

Humidity Offset
Size: 1 Byte, Default Value: 0

SettingDescription

-7 – 7 %

Parameter 23: Humidity Filter Time Constant

Humidity Filter Time Constant in minutes
Size: 1 Byte, Default Value: 30

SettingDescription

1 – 60 Minutes

Parameter 3: Basic Set ON Below Temp

Send Basic Set ON below temp
Size: 1 Byte, Default Value: 121

SettingDescription

121 Disabled
-40 – 120 Fahrenheit

Parameter 4: Basic Set OFF Above Temp

Send Basic Set OFF above temp
Size: 1 Byte, Default Value: 121

SettingDescription

121 Disabled
-40 – 120 Fahrenheit

Parameter 5: Basic Set OFF Below Temp

Send Basic Set OFF below temp
Size: 1 Byte, Default Value: 121

SettingDescription

121 Disabled
-40 – 120 Fahrenheit

Parameter 6: Basic Set Attempts

Make multiple attempts for all Basic Set Commands.Number of extra attempts sent every minute after first send.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Disabled
1 – 5 Number of extra attempts, unsigned

Parameter 7: Temp Units

Temperature Units
Size: 1 Byte, Default Value: 1

SettingDescription

0 Celsius
1 Fahrenheit

Parameter 8: Group1 Temp Threshold

Group1 – temperature delta auto-send threshold (how many degrees changed from the last auto-send)
Size: 1 Byte, Default Value: 10

SettingDescription

1 – 200 Tenths of degrees, unsigned

Parameter 9: Group1 Temp Interval

Group1 – periodic temperature send interval (minutes)
Size: 1 Byte, Default Value: 0

SettingDescription

1 – 120 Minutes, unsigned
0 Disabled

Technical Data

Hardware Platform ZM5202
Device Type Notification Sensor
Network Operation Reporting Sleeping Slave
Firmware Version HW: 2 FW: 1.47
Z-Wave Version 6.51.07
Certification ID ZC10-17075709
Z-Wave Product Id 0x0178.0x5448.0x3130
Color White
Sensors Air TemperatureHumidity
Firmware Updatable Updatable by Consumer by RF
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Battery
  • Configuration
  • Device Reset Locally
  • Firmware Update Md V2
  • Manufacturer Specific V2
  • Powerlevel
  • Sensor Multilevel V5
  • Version V2
  • Wake Up V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals