Vivint Element CT200 Manual
- June 8, 2024
- vivint
Table of Contents
- Vivint
- Vivint Element
- SKU: CT200
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Communication to a Sleeping device (Wakeup)
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: Temperature Reporting Threshold
- Parameter 10: Temperature Reporting Filter
- Parameter 11: Simple UI Mode Enable/Disable
- Parameter 12: Multicast Enable/Disable
- Parameter 13: Main Display Selection (CT110)
- Parameter 14: Save Energy Mode Type (CT110)
- Parameter 15: Fan Timer (CT200)
- Parameter 16: Humidity Control Activation (CT200)
- Parameter 17: Temperature Calibration (CT200)
- Parameter 18: Display Units (CT200)
- Parameter 2: HVAC Settings
- Parameter 3: Utility Lock Enable/Disable
- Parameter 4: C-Wire / Battery Status
- Parameter 5: Humidity Reporting Threshold
- Parameter 6: Auxiliary/Emergency
- Parameter 7: Thermostat Swing Temperature
- Parameter 8: Thermostat Diff Temperature
- Parameter 9: Thermostat Recovery Mode
- Technical Data
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Vivint
Vivint Element
SKU: CT200
Quickstart
This is a ****
HVAC-Thermostat
for
U.S. / Canada / Mexico.
To run this device please connect it to your mains power supply.
To add this device to your network execute the following action:
Press and hold side button to enter menu screen.Navigate to Installer >
Network to selection option to include to a Z-Wave network.
Please refer to the
Manufacturers
Manual
for more information.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
The Vivint Element Smart Thermostat has an elegantly simple design making it easy for anyone to use.Its hidden display comes to life when you need it, providing clear information and simple controls.This simplicity purposefully masks Elements true intelligence.Element works in concert with the Vivint SkyControl system, leveraging an unmatched understanding of home routines and activity levels.Element automatically and dynamically adjusts to match home activities and ensure a personalized balance of comfort & energy savings.Because Element uses the latest in Z-Wave technology, it is compatible with all common heating & cooling systems without the need for any new wiring.It can also be wirelessly updated, ensuring it will continue to evolve to meet consumers ever-changing comfort & energy savings needs.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
Press and hold side button to enter menu screen.Navigate to Installer > Reset and select Yes to reset to factory default settings.Use this procedure only in the event that the network primary controller is missing or otherwise inoperable.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
Press and hold side button to enter menu screen.Navigate to Installer > Network to selection option to include to a Z-Wave network.
Exclusion
Press and hold side button to enter menu screen.Navigate to Installer > Network to select option to exclude from a Z-Wave network.
Communication to a Sleeping device (Wakeup)
This device is battery operated and turned into deep sleep state most of the
time
to save battery life time. Communication with the device is limited. In order
to
communicate with the device, a static controller C is needed in the
network.
This controller will maintain a mailbox for the battery operated devices and
store
commands that can not be received during deep sleep state. Without such a
controller,
communication may become impossible and/or the battery life time is
significantly
decreased.
This device will wakeup regularly and announce the wakeup
state by sending out a so called Wakeup Notification. The controller can then
empty the mailbox. Therefore, the device needs to be configured with the
desired
wakeup interval and the node ID of the controller. If the device was included
by
a static controller this controller will usually perform all necessary
configurations. The wakeup interval is a tradeoff between maximal battery
life time and the desired responses of the device. To wakeup the device please
perform
the following action:
Press any button to wake up thermostat.If Wake up on Approach is enabled, simply approach the thermostat to wake up.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1 | 2 | Z-Wave Plus Lifeline |
---|
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: Temperature Reporting Threshold
The Temperature Reporting Threshold Configuration Set Command sets the
reporting threshold for changes in the ambient temperature as detected by the
thermostat.
Size: 1 Byte, Default Value: 2
SettingDescription
0 – 4 | 0 disabled 1 0.5F |
---|
Parameter 10: Temperature Reporting Filter
The Temperature Reporting Filter configuration command sets upper and lower
bounds of the ambient temperature reporting. The thermostat will not report
ambient temperature changes if the ambient temperature is below the upper
bound or above the lower bound.
Size: 4 Byte, Default Value: 32000
SettingDescription
0| "Byte 1 is the lower bound and can be 0 to 124 Byte 2 is the upper
bound and can be 0 to 124 "
---|---
Parameter 11: Simple UI Mode Enable/Disable
The parameter is set the auxiliary Simple Mode.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1 | 0=Normal 1=Simple |
---|
Parameter 12: Multicast Enable/Disable
This parameter controls how the thermostat sends unsolicited reports.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1 | If set to 0, multicast is disabled, if set to 1, multicast is enabled. |
---|
Parameter 13: Main Display Selection (CT110)
This configuration Param on the CT110 sets what information is displayed in
the main thermostat display area (the largest central numbers on the
display).
Size: 1 Byte, Default Value: 1
SettingDescription
1 – 2 | 1=Temperatue 2=RH |
---|
Parameter 14: Save Energy Mode Type (CT110)
This configuration value is used to read/write what behavior Save Energy
Mode causes in the thermostat when the thermostat enters Save Energy Mode.
Size: 1 Byte, Default Value: 2
SettingDescription
1 – 255| "1 = Adjust target by delta (see 0x50, 58) 2 = Least consuming
point in the running program 3 = Save energy absolute setpoint (Radio must
adjust setpoint) 255 = Save Energy not supported by thermostat (read-only
value) "
---|---
Parameter 15: Fan Timer (CT200)
This configuration is used to activate the fan with an automatic shut-off
timer.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 60 | 0, 15 min, 30 min, 60 min |
---|
Parameter 16: Humidity Control Activation (CT200)
This parameter is a pass-through. All the logic is handled by the thermostat
based on the A terminal assignment.
Size: 2 Byte, Default Value: 1
SettingDescription
0 | "Byte 1 can be 0 or 1 Byte 2 can be 1 or 3" |
---|
Parameter 17: Temperature Calibration (CT200)
This configuration is used to set the temperature offset of the thermostat.
Size: 1 Byte, Default Value: 0
SettingDescription
-6 – 6 | The valid values are from -6 to 6. |
---|
Parameter 18: Display Units (CT200)
This configuration is used to set units used by the device to display
temperature.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1 | 0=Fahrenheit 1=Celsius |
---|
Parameter 2: HVAC Settings
This parameter is used to set and retrieve the current HVAC settings of the
thermostat..
Size: 4 Byte, Default Value: 0
SettingDescription
0| "Cooling Type (0, 1, 2, 3) Heating Type (0, 1, 2, 3) Heating Fuel (1,
2, 3, 4, 5) Number of Heat Stages (not Heat Pump) / Number of Aux Stages (Heat
Pump) (1, 2)A Terminal Assignment (0, 1, 2, 3, 4) Number of Heat Pump Stages
(1, 2)O/B Wire Selection (1,2)Cooling Stages (1, 2)"
---|---
Parameter 3: Utility Lock Enable/Disable
The Utility Lock Configuration Set command enables or disables the utility
lock. If the utility lock is enabled, the setpoint cannot be modified directly
via the thermostat screen.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 255| If set to 0, the utility lock is disabled, all other values will
enable the utility lock.
---|---
Parameter 4: C-Wire / Battery Status
The C-Wire / Battery Status Configuration Report Command returns the status
of the thermostat power source. The power state is fixed when the thermostat
joins the network.
Size: 1 Byte, Default Value: 0
SettingDescription
1 – 2 | C-Wire (0x01) or Battery (0x02) |
---|
Parameter 5: Humidity Reporting Threshold
The Humidity Threshold Configuration Set Command sets the reporting
threshold for changes in the relative humidity as detected by the thermostat.
Size: 1 Byte, Default Value: 2
SettingDescription
0 – 3 | 0=disabled 1=3%RH 2=5%RH 3=10%RH |
---|
Parameter 6: Auxiliary/Emergency
The Auxiliary/Emergency configuration command enables or disables auxiliary
/ emergency heating in the thermostat.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1 | 0=disabled 1=enabled |
---|
Parameter 7: Thermostat Swing Temperature
The Thermostat Swing Temperature configuration command sets swing
temperature on the thermostat.
Size: 1 Byte, Default Value: 2
SettingDescription
1 – 8| The thermostat swing temperature is in units of 0.5 degrees Fahrenheit.
A value of 0x01 is 0.5F and 0x02 is 1.0F. The supported values may vary from
thermostat to thermostat but typically the allowed values are 0.5F (0x01) to
4.0F (0x08).
---|---
Parameter 8: Thermostat Diff Temperature
The Thermostat Differential Temperature configuration command sets the
differential temperature for multi-stage HVAC systems.
Size: 2 Byte, Default Value: 1028
SettingDescription
0| "The Thermostat Differential Mode determines which differential
temperature to set. Valid values are 0x00 (Heat) or Cool (0x01)The thermostat
differential temperature is in units of 0.5 degrees Fahrenheit. A value of
0x04 is 2.0F and 0x06 is 3.0F. The differential temperature must be an integer
value. Non-integer values, such as 1.5F (0x03), should not be used. The
supported values may vary from thermostat to thermostat but typically, the
allowed values are 2.0F (0x04) to 6.0F (0x0C). "
---|---
Parameter 9: Thermostat Recovery Mode
The Thermostat Recovery Mode configuration command sets the HVAC recovery
mode type. The recovery mode determines when additional HVAC stages are turned
off as the ambient temperature returns to the target temperature.
Size: 1 Byte, Default Value: 2
SettingDescription
1 – 2| The Thermostat Recovery Mode can be either fast (0x01) or economy
(0x02).
---|---
Technical Data
Hardware Platform | ZM5202 |
---|---|
Device Type | Thermostat – HVAC |
Network Operation | Listening Sleeping Slave |
Firmware Version | HW: 0 FW: 11.18:00.12:00.05 |
Z-Wave Version | 6.51.06 |
Certification ID | ZC10-16045048 |
Z-Wave Product Id | 0x0098.0xC801.0x000C |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>