Technical Specifications
Sensor principle | PIR detection |
---|---|
Operation voltage | 9.5~22.5VDC |
Consumption current | Max.10mA(no LED) |
Max.11mA(with LED)
Detection range *| HIR61
Max installation height:3m
Max detection range (Ø):12m
HIR61/R
Max installation height:8m (for person)
Max installation height:12m (for forklift)
Max detection range (Ø):14m
Lux reading range| < 1000 lux
Detection angle| 360°
Operation temperature| -40°C ~ +70°C
Storage temperature| Ta: -20°C ~ 50°C
Relative humidity| 10 ~ 90%
IP rating| IP20
CE| EN55015, EN61547 ,
EN61000-3-2/-3-3,
EN62386-101/103,
EN62386-303/304,
Zhaga Book 20
Warming-up| 5s
- The detection range is heavily influenced by sensor placement (angle) and different walking paces.
It may be reduced under certain conditions.
Optional Accessories
- Default: white housing, transparent version can be requested.
Demenstration of installation for transparent version
Wire Preparation
To make or release the wire from the terminal, use a screwdriver to push down the button.
Wiring Diagram
- 100 metres (total) max. for 0.5mm² CSA (Ta = 50 ℃)
- 150 metres (total) max. for 0.75mm² CSA (Ta = 50 ℃)
Installation
Mechanical Structure & Dimensions
Detection Pattern – – Diagram 1
The data below is tested under following conditions:
- Single person walking;
- Sensor not connected to any driver that may have soft-on period;
- Testing temperature Ta = 20°C;
- The testing is conducted in an open and spacious indoor field, without noticeable obstacles or influences that may affect PIR performances.
Mount height | Tangential Movement |
---|---|
3m | max 113m2 (Ø = 12m) |
Detection Pattern – – Diagram 2
The data below is tested under following conditions:
- Forklift driving;
- Sensor not connected to any driver that may have soft-on period;
- Testing temperature Ta = 20°C;
- The testing is conducted in an open and spacious indoor field, without noticeable obstacles or influences that may affect PIR performances.
Mount height | Tangential Movement |
---|---|
8m | max 201m2 (Ø = 16m) |
9m | max 227m2 (Ø = 17m) |
10m | max 254m2 (Ø = 18m) |
11m | max 314m2 (Ø = 20m) |
12m | max 314m2 (Ø = 20m) |
Detection Pattern – – Diagram 3
The data below is tested under following conditions:
- Single person walking;
- Sensor not connected to any driver that may have soft-on period;
- Testing temperature Ta = 20°C;
- The testing is conducted in an open and spacious indoor field, without noticeable obstacles or influences that may affect PIR performances.
Mount height | Tangential Movement |
---|---|
3m | max 38m2 (Ø = 7m) |
4m | max 50m2 (Ø = 8m) |
5m | max 50m2 (Ø =8m) |
6m | max 64m2 (Ø = 9m) |
7m | max 95m2 (Ø = 11m) |
8m | max 113m2 (Ø = 12m) |
Additional Information / Documents
- Regarding precautions for PIR Sensors installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->PIR Sensors – Precautions for Product Installation and Operation
- Data sheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/Motion Sensors ->Stand-alone Sensors
- Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>