MEAN WELL DRS-480 All-In-One Intelligent Security Power Instruction Manual

June 8, 2024
MEAN WELL

MEAN WELL DRS-480 All-In-One Intelligent Security Power

MEAN-WELL-DRS-480-All-In-One-Intelligent-Security-Power-product-image-
latest

Features

  • Universal input 90-305VAC (277VAC available)
  • All-in-one function with Power supply, DC-UPS, battery charger and status monitoring in ONE compact unit
  • Signal and alarms design meet UL2524,NFPA 1221,BS EN/EN54-4 and GB17945 requirement, with adjustable parameters configurable by communication interface
  • Form C relay contacts and LED indicators for AC Fail, Battery Low, Charger Fail, and DC-OK
  • Load-dependent high speed battery charging Built-in MODBus protocol, CANBus optional
  • Protections: Short circuit/Overload / Over voltage/ Over temperature(auto derating)
  • Battery reverse polarity (No damage) / Battery cut off Battery Iow protection / Battery reverse polarity protection
  • -30+70’C wide operating temperature
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Charging curve can be set with SBP-001 (Smart programmer sold separately, please refer to: charging current adjustable by VR https://www.meanwell.com/webapp/product/search.aspx?prod=SBP-001)
  • 2 or 3-stage selectable by DIP S.W
  • Suitable for lead acid and lithium-ion batteries .
  • 3 years Warranty

Applications

  • Public safety battery back-up (Red box) Security system Emergency lighting system Alarm system Uninterruptible DC-UPS system, battery detection system Central monitoring system Industrial automation

GTIN CODE

Description

DRS-480 is a 480W AC/DC DIN rail type security power supply series. In addition to the primary output, there is an additional charger circuit that will automatically adjust charge current depending on the primary output current. DRS-480 accepts the universal input between 90VAC and 305VAC, and supports output 24VDC, 36VDC, and 48VDC nominal systems. With high efficiency up to 93.5%, it can operate with free air convection cooling under -30C through 70C ambient temperature. In addition to the key protection features such as overload protection, over voltage protection, battery low voltage disconnect, and battery reverse polarity protection, the DRS-480 also provides Form-C contacts and LED indicator alarm signals for AC-fail, battery low, charger fail, and DC-OK to allow easy integration into security systems that comply with local alarm codes.

Model Encoding

MEAN-WELL-DRS-480-All-In-One-Intelligent-Security-
Power-1

OUTPUT| RIPPLE & NOISE (max.) **Note.5| 240mVp-p| 360mVp-p| 480mVp-p
---|---|---|---|---
VOLTAGE TOLERANCE ****Note.6| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±0.5%| ±0.5%| ±0.5%
SETUP RISETIME Note.7| 2400ms, 1000ms/230VAC            2400ms, 1000ms/115VAC at full load
HOLD UP TIME (Typ.)**| 16ms/230VAC            10ms/115VAC at full load

INPUT

| VOLTAGE RANGE| 90 ~ 305VAC           127 ~ 431VDC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| PF>0.95/230VAC            PF>0.98/115VAC at full load
EFFICIENCY (Typ.)| 92.5%| 93.5%| 93.5%
AC CURRENT (Typ.)| 5.4A/115VAC            2.7A/230VAC
INRUSH CURRENT (Typ.)| COLD START 30A/115VAC           60A/230VAC

PROTECTION

| SHORT CIRCUIT| Protection type: Constant current limiting, power will shutdown after 5 sec, re-power on to recover.
OVERLOAD| 105 ~ 135% rated output power
Protection type: Constant current limiting, shutdown output voltage after 5 sec.
OVER TEMPERATURE| Automatically drop load with temperature only for bat. load.

Protection type : Shut down o/p voltage, recover automatically after temperature goes down.

OVER VOLTAGE| Load main output : 32.4 ~ 37.3V| Load main output : 48.6 ~ 55.9V| Load main output : 64.8 ~ 74.5V
Protection type : Shut down o/p voltage, re-power on to recover
BATTERY CUT OFF| 20.9±0.5V| 31.3±0.7V| 41.8±1V
REVERSE POLARITY| By internal MOSFET, no damage, recovers automatically after fault condition is removed.

FUNCTION

|

FORM-C RELAY

| AC FAIL| Signals AC failure and activates when input voltage drops below : 79~89VAC of 120AC, 132~187VAC of 220VAC. Relay contact output, ON : AC OK ; OFF : AC Fail ; max. rating : 30Vdc/1A
CHARGER FAIL| Relay contact output, ON : Charger OK ; OFF : Charger Fail ; max. rating : 30Vdc/1A
DC OK| Signals normal DC output and activates when output voltage > 90% rated value. Relay contact output, ON : DC OK ; OFF : DC Fail ; max. rating : 30Vdc/1A
BATTERY LOW/ ABNORMAL/ DISCONNECTED| Relay contact output, ON : Battery OK ; OFF : Battery Low ; max. rating : 30Vdc/1A
Battery low voltage : < 22V±0.3V| Battery low voltage : < 33V±0.4V| Battery low voltage : < 44V±0.5V
BATTERY START| Restart system directly from battery and does not require AC power
DC-UPS| UPS switch to battery power within 10ms of AC failure
ADJUSTABLE CHARGING CURRENT| 20% ~ 100% charging current adjustable by VR
BATTERY TEMPERATURE COMPENSATION| The system can change the battery charging voltage by detecting the temperature (Please refer to page 9~10 for more details).

ENVIRONMENT

| WORKING TEMP.| -30 ~ +70℃(Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃) on Load output
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
OPERATING ALTITUDE Note.8| 2000 meters / OVCⅢ
OVER VOLTAGE CATEGORY| Ⅲ; According to Dekra BS EN/EN62368-1; altitude up to 2000 meters

SAFETY & EMC

(Note.10)

| SAFETY STANDARDS| UL62368-1, Dekra BS EN/EN62368-1, RCM AS/NZS 62368.1 approved; EAC TP TC 004 pending
WITHSTAND VOLTAGE| I/P-O/P: 4KVAC  I/P-FG: 2KVAC  O/P-FG: 1.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC/25℃/ 70%RH

EMC EMISSION

| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032 (CISPR32)| Class B
Radiated| BS EN/EN55032 (CISPR32)| Class B
Harmonic Current| BS EN/EN61000-3-2| —–
Voltage Flicker| BS EN/EN61000-3-2| —–

EMC IMMUNITY

| BS EN/EN55035 , BS EN/EN61204-3, BS EN/EN61000-6-2(BS EN/EN50082-2)
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact; criteria A
Radiated| BS EN/EN61000-4-3| Level 3, 10V/m ; criteria A
EFT / Burst| BS EN/EN61000-4-4| Level 3, 2KV ; criteria A
Surge| BS EN/EN61000-4-5| Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line- Chassis ;criteria A
Conducted| BS EN/EN61000-4-6| Level 3, 10V ; criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m ; criteria A
FIRE DETECTION AND FIRE ALARM SYSTEM| Compliance to BS EN/EN54-4

OTHERS

| MTBF| 556.6K hrs min.       Telcordia SR-332 (Bellcore);  74.5K hrs min.        MIL-HDBK-217F (25℃)
DIMENSION| 110125.2150.7mm (WHD)
PACKING| 1.65Kg; 6pcs/ 11Kg / 1.42CUFT
NOTE| https://www.meanwell.com/serviceDisclaimer.aspx
| Arrow| .com.| File Name:DRS-480-SPEC  2022-05-05

Block Diagram

MEAN-WELL-DRS-480-All-In-One-Intelligent-Security-
Power-2

Derating Curve

Static Characteristics

  1. Alarm signals
  2. Alarm Signal is sent out through ” AC fail ” & ” Battery low ” & ” Charger fail “pins via relay contact.
  3. An external voltage source is required for this function. The maximum applied voltage is 30Vdc and the maximum sink current is 1A. Please refer to Fig 1.2.
  4. Table1.1 explains the alarm function built in the power supply

INPUT

| AC fail| DC OK| Battery low/Abnormal

/Disconnected

| Charger fail
---|---|---|---|---
2-3| 1-3| 5-6| 4-6| 8-9| 7-9| 11-12| 10-12
AC only| closed| open| closed| open| open| closed| —–| —–
AC + BAT.| closed| open| closed| open| closed| open| —–| —–
BAT. only| open| closed| closed| open| closed| open| —–| —–
Low BAT.

(<30% capacity)

| —–| —–| —–| —–| open| closed| —–| —–
Charger Fail| —–| —–| —–| —–| —–| —–| open| closed

MEAN-WELL-DRS-480-All-In-One-Intelligent-Security-
Power-5

  1. DC-UPS function
    When AC mains drops below:79~89VAC of 120VAC,132~187VAC of 220VAC, UPS function will activate and power source switch battery backup.
    MEAN-WELL-DRS-480-All-In-One-Intelligent-Security-
Power-7

  2. Charger setting
    1| OFF: 3 stage(Default),  ON: 2 stage
    ---|---
    2| Charging curve adjustable:see below
    3

2 or 3-stage selectable by DIP S.W
※ This series provides 2 or 3 stage charging curve.
Charging curve can be adjustable by DIP S.W

State DRS-480-24 DRS-480-36 DRS-480-48
Constant Current 15.4A 10.2A 7.7A
Vboost 28.8V 43.2V 57.6V
State DRS-480-24 DRS-480-36 DRS-480-48
Constant Current 15.4A 10.2A 7.7A
Vboost 28.8V 43.2V 57.6V
Vfloat 27.6V 41.4V 55.2V

◎ Suitable for lead-acid batteries (flooded, Gel and AGM) and Li-ion batteries (lithium iron and lithium manganese).
※ The default curve is programmable, whereas other pre-defined curves can be activated by the means of the DIP S.W; please refer to the table below and the Mechanical Specification.

Embedded 2 stage charging curve

DIP SW position 24V model
2 3
OFF OFF

15.4A

| 28.8
ON| OFF| Pre-defined, gel batter| 28.0
OFF| ON| Pre-defined, flooded battery| 28.4
ON| ON| Pre-defined, AGM battery,LiFe04| 29.2
DIP SW position| 36V model
2| 3| Description| CC(default)| Vboost
OFF| OFF| Default, programmable|

10.2A

| 43.2
ON| OFF| Pre-defined, gel battery| 42
OFF| ON| Pre-defined, flooded battery| 42.6
ON| ON| Pre-defined, AGM battery,LiFe04| 43.8
DIP SW position| 48V model
2| 3| Description| CC(default)| Vboost
OFF| OFF| Default, programmable|

7.7A

| 57.6
ON| OFF| Pre-defined, gel battery| 56.0
OFF| ON| Pre-defined, flooded battery| 56.8
ON| ON| Pre-defined, AGM battery,LiFe04| 58.4

Embedded 3 stage charging curve

DIP SW position 24V model
2 3
OFF OFF

15.4A

| 28.8| 27.6
ON| OFF| Pre-defined, gel batter| 28.0| 27.2
OFF| ON| Pre-defined, flooded battery| 28.4| 26.8
ON| ON| Pre-defined, AGM battery,LiFe04| 29.2| 28.0
DIP SW position| 36V model
2| 3| Description| CC(default)| Vboost| Vfloat
OFF| OFF| Default, programmable|

10.2A

| 43.2| 41.4
ON| OFF| Pre-defined, gel battery| 42| 40.8
OFF| ON| Pre-defined, flooded battery| 42.6| 40.2
ON| ON| Pre-defined, AGM battery,LiFe04| 43.8| 42.0
DIP SW position| 48V model
2| 3| Description| CC(default)| Vboost| Vfloat
OFF| OFF| Default, programmable|

7.7A

| 57.6| 55.2
ON| OFF| Pre-defined, gel battery| 56.0| 54.4
OFF| ON| Pre-defined, flooded battery| 56.8| 53.6
ON| ON| Pre-defined, AGM battery,LiFe04| 58.4| 56.0

SBP-001 can adjust the charging curves (Only CANBus Model)

2 stage charging curve (programable)

DIP SW position 24V model
2 3
OFF OFF
DIP SW position 36V model
2 3
OFF OFF
DIP SW position 48V model
2 3
OFF OFF

3 stage charging curve (programable)

DIP SW position 24V model
2 3
OFF OFF
DIP SW position 36V model
2 3
OFF OFF
DIP SW position 48V model
2 3
OFF OFF

※ SBP-001 is a programmer, particularly for MEAN WELL’s various programmable battery charger models to program the parameters of charging curves, such as the Constant current (CC), tapper current(TC), Constant voltage (CV), float voltage (FV) and so on, to accommodate the diversified battery specification in industry. With the design accounting for simplicity and convenience, users can easily configure MEAN WELL’s programmable battery chargers with SBP-001 programmer and the computer; all of the setups are able to be finished easily by the means of the specific software.
Note:

  1. Tapper current(TC) default is 10%, can be fine tuned from 2% to 30% by SBP-001 with computer or CANBus Interface.
  2. Please contact MEAN WELL for more details.

MEAN-WELL-DRS-480-All-In-One-Intelligent-Security-
Power-11

User Interface:

MEAN-WELL-DRS-480-All-In-One-Intelligent-Security-
Power-12

Communication cable for DRS series

MEAN-WELL-DRS-480-All-In-One-Intelligent-Security-
Power-13

DRS series pin assigment :

Connector Pin Assigment
SBP-001 10pin connector
(Connector part No.:HRS DF11-10DS) 1

10 (GND)
| | | | | | | | | |
DRS-480 RJ45 Communication port|

—–

|

—–

|

—–

|

—–

|

6

|

7

|

—–

|

—–

|

—–

|

8

Wire color| —–| —–| —–| —–| Green| White/Brown| —–| —–| —–| Brown

Communication interface

Charging parameters can be modified by MODBus (Built-in) or CANBus(optional) communication commands. For details, please refer to: http://www.meanwell.com/manual.html

Power Boost Mode

The maximum current on the load output is the 2 times the rated current for 4 minutes max. and 3 times the rated current for 4 seconds max. For example (48V model):
Output load

Battery temperature compensation

  • To exploit the temperature compensation function, please attach the temperature sensor(NTC) which is enclosed with DRS-480, to the battery or the battery’s vicinity.
  • DRS-480 is able to work normally without the temperature sensor(NTC).

The compensation parameters included Disable, -3, -4 and -5mV/ ℃ /Cell .It can be modified by communication command of CANBus, MODBus. The factory default value is -3mV/ ℃ /Cell.

It will be regarded as normal temperature and will not be compensated when temperature compensation resistance is not connected; And temperature compensation will only compensate lead-acid battery, not lithium iron battery.

The range of temperature compensation is 0-40℃ , normal temperature 25℃ is the central value, no compensation; When the temperature is < 0 ℃ or > 40 ℃, the current temperature compensation value will be limited to 0 ℃ or 40℃.
24V model as an example
Assuming that V =28.8V, temperature compensation set to -5mV/℃/Cellby communication, TEMP_bat is NTCtemperature detection.
boost
The compensating voltage can be calculated by the following equation:
V =28.8V-5mV(TEMP_bat -25℃)12Cell
boost_comp
Max. compensation voltage:
V =28.8V-5mV(0℃-25℃)12Cell=30.3V
Min. compensation voltage:
V =28.8V-5mV(40℃-25℃)12Cell=27.9V

Accessory List

NTC Sensor and mating wire along with DRS-480 (Standard accessory)

Item Quantity
1

NTC sensor wire

| 1
2| Mating wire

or equivalent

| 1

Connection Diagram

MEAN-WELL-DRS-480-All-In-One-Intelligent-Security-
Power-20

LED alarm

Function Description Output of alarm

DC OK

| DC fail| OFF
DC OK| Green


AC fail

| AC fail| Red
AC OK| OFF










Status

| ****

Charging status

| Float| Green
Charging: CC/CV| Orange








System diagnosis

| Discharging| Orange: 1 Blink/Pause
Charger fail| Red : 1 Blink/Pause
Battery overvoltage / Battery reverse polarity| Red : 2 Blink/Pause
Battery low / No Battery| Red : 3 Blink/Pause
Battery discharge peak power timeout.| Red : 4 Blink/Pause
Over load / short| Red : 5 Blink/Pause
Over temperature| Red : 6 Blink/Pause
Timeout| Red : 7 Blink/Pause

Suggested Application

  1. Backup connection for AC interruption

    • Please refer to Fig2.1 for suggested connection.
      The power supply charges the battery and provides energy to the load at the same time when AC mains is OK. The battery starts to supply power to the load when AC mains fails.
      MEAN-WELL-DRS-480-All-In-One-Intelligent-Security-
Power-21
  2. Backup time
    Backup time depends on:
    ※ from the load current
    ※ from the size of the batteries.
    The following table is an example (battery capacity at C10 discharge rate)Battery

Load

| 10AH| 20AH| 50AH| 100AH| 200AH
---|---|---|---|---|---
1.5A| 350min| 13h| 33h| 67h| 133h
3A| 125min| 350min| 17h| 33h| 67h
5A| 60min| 180min| 600min| 20h| 40h
7.5A| 35min| 90min| 350min| 13h| 27h
10A| 23min| 60min| 240min| 10h| 20h
15A| 13min| 35min| 125min| 350min| 13h

Mechanical Specification

Force button Connector (CN12): JS-2008R-4*2-T or equivalent

Pin No. Assignment
1 3.3V
2 GND
3 RTH+
4 RTH-
5 A0
6 A1
7,8 Open: Normal Short: Force start

Terminal Pin No. Assignment (RJ45)

Pin No. Function Description
1,2,3,4,5 NC Retain for future use.
6 Data+ For MODBus model:Serial Date used in the MODBus interface.
CANH For CANBus model:Date line used in the CANBus interface.
7 Data- For MODBus model:Serial Clock used in the MODBus interface.
CANL For CANBus model:Date line used in the CANBus interface.
8 GND-AUX Auxillary voltage output GND. The signal return is isolated from

the output terminals(+V & -V).

Installation Instruction

This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the Instruction manual.

ADMISSIBLE DIN rail:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)