MEAN WELL DRS-480 All-In-One Intelligent Security Power Instruction Manual
- June 8, 2024
- MEAN WELL
Table of Contents
MEAN WELL DRS-480 All-In-One Intelligent Security Power
Features
- Universal input 90-305VAC (277VAC available)
- All-in-one function with Power supply, DC-UPS, battery charger and status monitoring in ONE compact unit
- Signal and alarms design meet UL2524,NFPA 1221,BS EN/EN54-4 and GB17945 requirement, with adjustable parameters configurable by communication interface
- Form C relay contacts and LED indicators for AC Fail, Battery Low, Charger Fail, and DC-OK
- Load-dependent high speed battery charging Built-in MODBus protocol, CANBus optional
- Protections: Short circuit/Overload / Over voltage/ Over temperature(auto derating)
- Battery reverse polarity (No damage) / Battery cut off Battery Iow protection / Battery reverse polarity protection
- -30+70’C wide operating temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- Charging curve can be set with SBP-001 (Smart programmer sold separately, please refer to: charging current adjustable by VR https://www.meanwell.com/webapp/product/search.aspx?prod=SBP-001)
- 2 or 3-stage selectable by DIP S.W
- Suitable for lead acid and lithium-ion batteries .
- 3 years Warranty
Applications
- Public safety battery back-up (Red box) Security system Emergency lighting system Alarm system Uninterruptible DC-UPS system, battery detection system Central monitoring system Industrial automation
GTIN CODE
- MW Search: https://www.meanwel.com/serviceGTIN.aspx
Description
DRS-480 is a 480W AC/DC DIN rail type security power supply series. In addition to the primary output, there is an additional charger circuit that will automatically adjust charge current depending on the primary output current. DRS-480 accepts the universal input between 90VAC and 305VAC, and supports output 24VDC, 36VDC, and 48VDC nominal systems. With high efficiency up to 93.5%, it can operate with free air convection cooling under -30C through 70C ambient temperature. In addition to the key protection features such as overload protection, over voltage protection, battery low voltage disconnect, and battery reverse polarity protection, the DRS-480 also provides Form-C contacts and LED indicator alarm signals for AC-fail, battery low, charger fail, and DC-OK to allow easy integration into security systems that comply with local alarm codes.
Model Encoding
OUTPUT| RIPPLE & NOISE (max.) **Note.5| 240mVp-p| 360mVp-p|
480mVp-p
---|---|---|---|---
VOLTAGE TOLERANCE ****Note.6| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±0.5%| ±0.5%| ±0.5%
SETUP RISETIME Note.7| 2400ms, 1000ms/230VAC 2400ms,
1000ms/115VAC at full load
HOLD UP TIME (Typ.)**| 16ms/230VAC 10ms/115VAC at full load
INPUT
| VOLTAGE RANGE| 90 ~ 305VAC 127 ~ 431VDC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| PF>0.95/230VAC PF>0.98/115VAC at full
load
EFFICIENCY (Typ.)| 92.5%| 93.5%| 93.5%
AC CURRENT (Typ.)| 5.4A/115VAC 2.7A/230VAC
INRUSH CURRENT (Typ.)| COLD START 30A/115VAC 60A/230VAC
PROTECTION
| SHORT CIRCUIT| Protection type: Constant current limiting, power will
shutdown after 5 sec, re-power on to recover.
OVERLOAD| 105 ~ 135% rated output power
Protection type: Constant current limiting, shutdown output voltage after 5
sec.
OVER TEMPERATURE| Automatically drop load with temperature only for bat.
load.
Protection type : Shut down o/p voltage, recover automatically after temperature goes down.
OVER VOLTAGE| Load main output : 32.4 ~ 37.3V| Load main output : 48.6 ~
55.9V| Load main output : 64.8 ~ 74.5V
Protection type : Shut down o/p voltage, re-power on to recover
BATTERY CUT OFF| 20.9±0.5V| 31.3±0.7V| 41.8±1V
REVERSE POLARITY| By internal MOSFET, no damage, recovers automatically
after fault condition is removed.
FUNCTION
|
FORM-C RELAY
| AC FAIL| Signals AC failure and activates when input voltage drops
below : 79~89VAC of 120AC, 132~187VAC of 220VAC. Relay contact output, ON : AC
OK ; OFF : AC Fail ; max. rating : 30Vdc/1A
CHARGER FAIL| Relay contact output, ON : Charger OK ; OFF : Charger Fail
; max. rating : 30Vdc/1A
DC OK| Signals normal DC output and activates when output voltage > 90%
rated value. Relay contact output, ON : DC OK ; OFF : DC Fail ; max. rating :
30Vdc/1A
BATTERY LOW/ ABNORMAL/ DISCONNECTED| Relay contact output, ON : Battery
OK ; OFF : Battery Low ; max. rating : 30Vdc/1A
Battery low voltage : < 22V±0.3V| Battery low voltage : < 33V±0.4V| Battery
low voltage : < 44V±0.5V
BATTERY START| Restart system directly from battery and does not require
AC power
DC-UPS| UPS switch to battery power within 10ms of AC failure
ADJUSTABLE CHARGING CURRENT| 20% ~ 100% charging current
adjustable by VR
BATTERY TEMPERATURE COMPENSATION| The system can change the battery
charging voltage by detecting the temperature (Please refer to page 9~10 for
more details).
ENVIRONMENT
| WORKING TEMP.| -30 ~ +70℃(Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃) on Load output
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
OPERATING ALTITUDE Note.8| 2000 meters / OVCⅢ
OVER VOLTAGE CATEGORY| Ⅲ; According to Dekra BS EN/EN62368-1; altitude
up to 2000 meters
SAFETY & EMC
(Note.10)
| SAFETY STANDARDS| UL62368-1, Dekra BS EN/EN62368-1, RCM AS/NZS 62368.1
approved; EAC TP TC 004 pending
WITHSTAND VOLTAGE| I/P-O/P: 4KVAC I/P-FG: 2KVAC O/P-FG: 1.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC/25℃/
70%RH
EMC EMISSION
| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032 (CISPR32)| Class B
Radiated| BS EN/EN55032 (CISPR32)| Class B
Harmonic Current| BS EN/EN61000-3-2| —–
Voltage Flicker| BS EN/EN61000-3-2| —–
EMC IMMUNITY
| BS EN/EN55035 , BS EN/EN61204-3, BS EN/EN61000-6-2(BS EN/EN50082-2)
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact; criteria A
Radiated| BS EN/EN61000-4-3| Level 3, 10V/m ; criteria A
EFT / Burst| BS EN/EN61000-4-4| Level 3, 2KV ; criteria A
Surge| BS EN/EN61000-4-5| Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-
Chassis ;criteria A
Conducted| BS EN/EN61000-4-6| Level 3, 10V ; criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m ; criteria A
FIRE DETECTION AND FIRE ALARM SYSTEM| Compliance to BS EN/EN54-4
OTHERS
| MTBF| 556.6K hrs min. Telcordia SR-332 (Bellcore); 74.5K hrs
min. MIL-HDBK-217F (25℃)
DIMENSION| 110125.2150.7mm (WHD)
PACKING| 1.65Kg; 6pcs/ 11Kg / 1.42CUFT
NOTE| https://www.meanwell.com/serviceDisclaimer.aspx
| Arrow| .com.| File Name:DRS-480-SPEC 2022-05-05
Block Diagram
Derating Curve
Static Characteristics
- Alarm signals
- Alarm Signal is sent out through ” AC fail ” & ” Battery low ” & ” Charger fail “pins via relay contact.
- An external voltage source is required for this function. The maximum applied voltage is 30Vdc and the maximum sink current is 1A. Please refer to Fig 1.2.
- Table1.1 explains the alarm function built in the power supply
INPUT
| AC fail| DC OK| Battery low/Abnormal
/Disconnected
| Charger fail
---|---|---|---|---
2-3| 1-3| 5-6| 4-6| 8-9| 7-9| 11-12| 10-12
AC only| closed| open| closed| open| open| closed| —–| —–
AC + BAT.| closed| open| closed| open| closed| open| —–| —–
BAT. only| open| closed| closed| open| closed| open| —–| —–
Low BAT.
(<30% capacity)
| —–| —–| —–| —–| open| closed| —–| —–
Charger Fail| —–| —–| —–| —–| —–| —–| open| closed
-
DC-UPS function
When AC mains drops below:79~89VAC of 120VAC,132~187VAC of 220VAC, UPS function will activate and power source switch battery backup.
-
Charger setting
1| OFF: 3 stage(Default), ON: 2 stage
---|---
2| Charging curve adjustable:see below
3
2 or 3-stage selectable by DIP S.W
※ This series provides 2 or 3 stage charging curve.
Charging curve can be adjustable by DIP S.W
State | DRS-480-24 | DRS-480-36 | DRS-480-48 |
---|---|---|---|
Constant Current | 15.4A | 10.2A | 7.7A |
Vboost | 28.8V | 43.2V | 57.6V |
State | DRS-480-24 | DRS-480-36 | DRS-480-48 |
---|---|---|---|
Constant Current | 15.4A | 10.2A | 7.7A |
Vboost | 28.8V | 43.2V | 57.6V |
Vfloat | 27.6V | 41.4V | 55.2V |
◎ Suitable for lead-acid batteries (flooded, Gel and AGM) and Li-ion batteries
(lithium iron and lithium manganese).
※ The default curve is programmable, whereas other pre-defined curves can be
activated by the means of the DIP S.W; please refer to the table below and the
Mechanical Specification.
Embedded 2 stage charging curve
DIP SW position | 24V model |
---|---|
2 | 3 |
OFF | OFF |
15.4A
| 28.8
ON| OFF| Pre-defined, gel batter| 28.0
OFF| ON| Pre-defined, flooded battery| 28.4
ON| ON| Pre-defined, AGM battery,LiFe04| 29.2
DIP SW position| 36V model
2| 3| Description| CC(default)| Vboost
OFF| OFF| Default, programmable|
10.2A
| 43.2
ON| OFF| Pre-defined, gel battery| 42
OFF| ON| Pre-defined, flooded battery| 42.6
ON| ON| Pre-defined, AGM battery,LiFe04| 43.8
DIP SW position| 48V model
2| 3| Description| CC(default)| Vboost
OFF| OFF| Default, programmable|
7.7A
| 57.6
ON| OFF| Pre-defined, gel battery| 56.0
OFF| ON| Pre-defined, flooded battery| 56.8
ON| ON| Pre-defined, AGM battery,LiFe04| 58.4
Embedded 3 stage charging curve
DIP SW position | 24V model |
---|---|
2 | 3 |
OFF | OFF |
15.4A
| 28.8| 27.6
ON| OFF| Pre-defined, gel batter| 28.0| 27.2
OFF| ON| Pre-defined, flooded battery| 28.4| 26.8
ON| ON| Pre-defined, AGM battery,LiFe04| 29.2| 28.0
DIP SW position| 36V model
2| 3| Description| CC(default)| Vboost| Vfloat
OFF| OFF| Default, programmable|
10.2A
| 43.2| 41.4
ON| OFF| Pre-defined, gel battery| 42| 40.8
OFF| ON| Pre-defined, flooded battery| 42.6| 40.2
ON| ON| Pre-defined, AGM battery,LiFe04| 43.8| 42.0
DIP SW position| 48V model
2| 3| Description| CC(default)| Vboost| Vfloat
OFF| OFF| Default, programmable|
7.7A
| 57.6| 55.2
ON| OFF| Pre-defined, gel battery| 56.0| 54.4
OFF| ON| Pre-defined, flooded battery| 56.8| 53.6
ON| ON| Pre-defined, AGM battery,LiFe04| 58.4| 56.0
SBP-001 can adjust the charging curves (Only CANBus Model)
2 stage charging curve (programable)
DIP SW position | 24V model |
---|---|
2 | 3 |
OFF | OFF |
DIP SW position | 36V model |
2 | 3 |
OFF | OFF |
DIP SW position | 48V model |
2 | 3 |
OFF | OFF |
3 stage charging curve (programable)
DIP SW position | 24V model |
---|---|
2 | 3 |
OFF | OFF |
DIP SW position | 36V model |
2 | 3 |
OFF | OFF |
DIP SW position | 48V model |
2 | 3 |
OFF | OFF |
※ SBP-001 is a programmer, particularly for MEAN WELL’s various programmable
battery charger models to program the parameters of charging curves, such as
the Constant current (CC), tapper current(TC), Constant voltage (CV), float
voltage (FV) and so on, to accommodate the diversified battery specification
in industry. With the design accounting for simplicity and convenience, users
can easily configure MEAN WELL’s programmable battery chargers with SBP-001
programmer and the computer; all of the setups are able to be finished easily
by the means of the specific software.
Note:
- Tapper current(TC) default is 10%, can be fine tuned from 2% to 30% by SBP-001 with computer or CANBus Interface.
- Please contact MEAN WELL for more details.
User Interface:
Communication cable for DRS series
DRS series pin assigment :
Connector | Pin Assigment |
---|---|
SBP-001 10pin connector | |
(Connector part No.:HRS DF11-10DS) | 1 |
10 (GND)
| | | | | | | | | |
DRS-480 RJ45 Communication port|
—–
|
—–
|
—–
|
—–
|
6
|
7
|
—–
|
—–
|
—–
|
8
Wire color| —–| —–| —–| —–| Green| White/Brown| —–| —–| —–| Brown
Communication interface
Charging parameters can be modified by MODBus (Built-in) or CANBus(optional) communication commands. For details, please refer to: http://www.meanwell.com/manual.html
Power Boost Mode
The maximum current on the load output is the 2 times the rated current for 4
minutes max. and 3 times the rated current for 4 seconds max. For example (48V
model):
Output load
Battery temperature compensation
- To exploit the temperature compensation function, please attach the temperature sensor(NTC) which is enclosed with DRS-480, to the battery or the battery’s vicinity.
- DRS-480 is able to work normally without the temperature sensor(NTC).
The compensation parameters included Disable, -3, -4 and -5mV/ ℃ /Cell .It can be modified by communication command of CANBus, MODBus. The factory default value is -3mV/ ℃ /Cell.
It will be regarded as normal temperature and will not be compensated when temperature compensation resistance is not connected; And temperature compensation will only compensate lead-acid battery, not lithium iron battery.
The range of temperature compensation is 0-40℃ , normal temperature 25℃ is the
central value, no compensation; When the temperature is < 0 ℃ or > 40 ℃, the
current temperature compensation value will be limited to 0 ℃ or 40℃.
24V model as an example
Assuming that V =28.8V, temperature compensation set to -5mV/℃/Cellby
communication, TEMP_bat is NTCtemperature detection.
boost
The compensating voltage can be calculated by the following equation:
V =28.8V-5mV(TEMP_bat -25℃)12Cell
boost_comp
Max. compensation voltage:
V =28.8V-5mV(0℃-25℃)12Cell=30.3V
Min. compensation voltage:
V =28.8V-5mV(40℃-25℃)12Cell=27.9V
Accessory List
NTC Sensor and mating wire along with DRS-480 (Standard accessory)
Item | Quantity |
---|---|
1 |
NTC sensor wire
| 1
2| Mating wire
or equivalent
| 1
Connection Diagram
LED alarm
Function | Description | Output of alarm |
---|
DC OK
| DC fail| OFF
DC OK| Green
AC fail
| AC fail| Red
AC OK| OFF
Status
| ****
Charging status
| Float| Green
Charging: CC/CV| Orange
System diagnosis
| Discharging| Orange: 1 Blink/Pause
Charger fail| Red : 1 Blink/Pause
Battery overvoltage / Battery reverse polarity| Red : 2 Blink/Pause
Battery low / No Battery| Red : 3 Blink/Pause
Battery discharge peak power timeout.| Red : 4 Blink/Pause
Over load / short| Red : 5 Blink/Pause
Over temperature| Red : 6 Blink/Pause
Timeout| Red : 7 Blink/Pause
Suggested Application
-
Backup connection for AC interruption
- Please refer to Fig2.1 for suggested connection.
The power supply charges the battery and provides energy to the load at the same time when AC mains is OK. The battery starts to supply power to the load when AC mains fails.
- Please refer to Fig2.1 for suggested connection.
-
Backup time
Backup time depends on:
※ from the load current
※ from the size of the batteries.
The following table is an example (battery capacity at C10 discharge rate)Battery
Load
| 10AH| 20AH| 50AH| 100AH| 200AH
---|---|---|---|---|---
1.5A| 350min| 13h| 33h| 67h| 133h
3A| 125min| 350min| 17h| 33h| 67h
5A| 60min| 180min| 600min| 20h| 40h
7.5A| 35min| 90min| 350min| 13h| 27h
10A| 23min| 60min| 240min| 10h| 20h
15A| 13min| 35min| 125min| 350min| 13h
Mechanical Specification
Force button Connector (CN12): JS-2008R-4*2-T or equivalent
Pin No. | Assignment |
---|---|
1 | 3.3V |
2 | GND |
3 | RTH+ |
4 | RTH- |
5 | A0 |
6 | A1 |
7,8 | Open: Normal Short: Force start |
Terminal Pin No. Assignment (RJ45)
Pin No. | Function | Description |
---|---|---|
1,2,3,4,5 | NC | Retain for future use. |
6 | Data+ | For MODBus model:Serial Date used in the MODBus interface. |
CANH | For CANBus model:Date line used in the CANBus interface. | |
7 | Data- | For MODBus model:Serial Clock used in the MODBus interface. |
CANL | For CANBus model:Date line used in the CANBus interface. | |
8 | GND-AUX | Auxillary voltage output GND. The signal return is isolated from |
the output terminals(+V & -V).
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the Instruction manual.
ADMISSIBLE DIN rail:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)
Installation Manual
Please refer to : http://www.meanwell.com/manual.html