James James Primed Hardie Architectural Collection HZ10 0.312-in x 48.19-in x 144-in Fiber Cement Instruction Manual

June 8, 2024
James James

James James Primed Hardie LOGO 2James James
Primed Hardie LOGO Hardie® Architectural Panels
Single Family Installation Requirements
Instruction Manual
James James Primed Hardie Architectural Collection HZ10
0 312 in 48 19 in 144 in Fiber Cement Shiplap with V-Groove Aesthetic

Introduction

The material contained herein provides installation guidelines for the Hardie® Architectural Panel System by James Hardie. This document is intended for use by builders, cladding installers, and other contractors who may be involved with the installation of the Hardie® Architectural Panel System.
Before you begin your siding project read the instruction manual completely and thoroughly. This document describes and illustrates the minimum steps required to install the Hardie® Architectural Panel System. No instruction manual can anticipate every condition, circumstance, or situation that might arise during installation over the course of the project. When in doubt about assembly details, contact the architect, specifier, or a building official. Contact your James Hardie Sales and Install Representative for product support 1-800-9HARDIE (1- 800-942-7343).
PREPARATION
Ensure the drainage plane is intact and all penetrations are sealed. Plan your work, use the proper tools, techniques, and follow installation procedures as covered in this installation manual. It is important that builders, specifiers, and installers recognize requirements and information pertaining to:

  • Safety
  • Storage and Handling
  • Cutting
  • Wall Preparation
  • Fastening

For best results, before installation, ensure your panels are clean and free of dirt, dust, chalking, oil, grease, organic contaminants, or mold. Dust from cutting and construction should be removed immediately upon installation.
PRACTICE INSTALLING MATERIAL
Utilize a mock-up to evaluate installation and finishing techniques, with a focus on specific applications designed by a design professional or engineer. The fastening practice and/or fastening tools shall be properly adjusted to avoid overdriving. Do not proceed with remaining work until workmanship, color, and sheen are approved. Repeat mock-up area as required to produce acceptable work.

Safe Working Practices

STORAGE & HANDLING
Store flat and keep dry and covered prior to installation. Installing siding wet or saturated may result in shrinkage. Protect edges and corners from breakage. James Hardie is not responsible for damage caused by improper storage and handling of the product.

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 1

CUTTING INSTRUCTIONS
OUTDOORS

  1. Position cutting station so that airflow blows dust away from the user and others near the cutting area.
  2. Cut using one of the following methods based on jobsite requirements:
    a. Best: Circular saw equipped with a HardieBlade® saw blade and attached vacuum dust collection system.
    b. Shears (manual, pneumatic or electric) or the score and snap method may also be used.
    c. Better: Circular saw equipped with a dust collection feature and a HardieBlade® saw blade.
    d. Good: Circular saw equipped with a HardieBlade® saw blade.

INDOORS

  1. NEVER grind or cut with a power saw indoors.
  2. Cut only using shears (manual, pneumatic or electric) or the score and snap method.

GENERAL

  • During clean-up of dust and debris, wet dust and debris down with a fine water mist, apply a dust reducing sweeping compound in sufficient quantities, or use a vacuum to collect dust and debris. DO NOT use compressed air.
    DO NOT dry sweep without first applying a dust reducing control measure.

  • For best performance when cutting with a circular saw, James Hardie recommends using HardieBlade® saw blades.

  • Go to jameshardiepros.com for additional cutting and dust control recommendations.

IMPORTANT: The Occupational Safety and Health Administration (OSHA) regulates workplace exposure to silica dust. For construction sites, OSHA has deemed that cutting fiber cement with a circular saw having a blade diameter less than 8 inches and connected to a commercially available dust collection system per manufacturer’s instructions results in exposures below the OSHA Permissible Exposure Limit (PEL) for respirable crystalline silica, without the need for additional respiratory protection.
If you are unsure about how to comply with OSHA silica dust regulations, consult a qualified industrial hygienist or safety professional, or contact your James Hardie technical sales representative for assistance. James Hardie makes no representation or warranty that adopting a particular cutting practice will assure your compliance with OSHA rules or other applicable laws and safety requirements.
HANDLING PANELS
When handling Hardie® Architectural Panels care should be given to prevent damage to the machined edges and/or the ColorPlus finish.

  • Utilize 2 persons to carry product.
  • Carry panels along the long edges whenever possible (Fig. 2a).
  • When handling panels on short edges and the need to set down, place with the underlap edge of the shiplap facing down. (tongue/long edge) (Fig. 2b).
    Doing so will:
    – Prevent damage to top edge (visible edge) of panel if dropped or dragged.
    – Help prevent scratches to ColorPlus finish.

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 2

ColorPlus Tip:

  • When possible, carry with plastic covering in place. This will help to protect the ColorPlus finish.
  • Wearing gloves will help prevent fingerprint smudges to the ColorPlus finish

CUT STATION & CUTTING
Setup cutting station (Fig. 2c), and locate close to installation area.
TIP: Utilize the pallet & cardboard toppers to create your cutting table
Use a HardieBlade® to cut James Hardie fiber cement products. A track saw with vacuum system (Fig. 2d) is best for cutting Hardie® Architectural Panels.
a. Cleaner cuts
b. Panels can be cut facing up (minimize panel movements)
c. If using a traditional circular saw with vacuum system, place panel face down to prevent marring of the finished surface caused by friction from the saw.

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 3

ColorPlus Tip:

  • A scratch proof platform is a good idea to prevent from scratching the ColorPlus surface while cutting. The cardboard cover from the top of the pallet makes a great non marking surface.
  • Keep a spray bottle (filled with water) and soft cloths to wipe cut dust off immediately after cutting to keep your ColorPlus finish looking fresh.
  • Touch-up all cut edges

Design & Fastener Aesthetics

PANEL JOINT CONSIDERATIONS
Hardie® Architectural Panels have been designed to feature a “V” groove look at panel joints. When considering the location of panel joint layout, please take into consideration the following:

  1. Installation requirements
    a. Clearances
    b. Floor break (panels cannot be placed across floors) (horizontal flashing / trim is required)
    c. Framing, sheathing, and fastener attachment (see Panel V-Groove joint placement options section within this document)

  2. Align/center to key features (ex. windows, doors, etc.) (fig. 3a)

  3. Align/center to the structure (ex. walls, gables, etc.) (fig. 3b)

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 6| James James Primed
Hardie Architectural Collection HZ10 0 312 in 48 19 in 144 in Fiber Cement -
FIGURE 7
---|---

FASTENER AESTHETICS
Hardie® Architectural Panels have been designed to be installed with stainless steel finish nails, which suggests the impression of a fastener free panel surface.
The following elements should be utilized to aid in achieving a fastener free appearance as well as minimize the need for patching & touch-up.

  • In-Line Regulator.
  • No-Mar Tip.
  • Gun agle to wall.
  • Nails should be left proud, then tapped flush with a smooth face hammer. Do Not over drive fasteners.
  • Straight 16-gauge finish nailer in good working.
  • Refer to the Fastener Requirements section for complete fastener installation & guidance. Additional information can be found in the Tools, installation & Finishing

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 5

Finish Nail *Use a smooth face hammer and lightly tap flush.
Tips: for fastener depth control:

  • Oil nail guns regularly.
  • If excessive air pressure (above 90psi) is needed or having difficulty controlling nail depth. Nail gun may be worn.

* Design Advice: It is okay for panel widths to be equal or unequal at structure ends.

General Requirements

IMPORTANT: Read these instructions in their entirety before attempting installation.

  • These instructions to be used for installation on single family homes only. For Commercial / Multi-Family installation requirements go to www.JamesHardiePros.com**

  • Hardie® Architectural Panels can be installed over braced wood. See General Fastening Requirements. Irregularities in framing and sheathing can mirror through the finished application. Correct irregularities before installing siding.

  • Hardie® Architectural Panels may be installed on flat vertical wall applications only.

  • Information on installing James Hardie® products over non-nailable substrates (ex: gypsum, foam,etc.) can be located in JH Tech Bullet in 19 at www.jameshardie.com

  • A water-resistive barrier (WRB) is required in accordance with local building code requirements. The WRB must be appropriately installed with penetration and junction flashing in accordance with local building code requirements. James Hardie will assume no responsibility for water infiltration.
    James Hardie manufactures HardieWrap® Weather Barrier, a non-woven non- perforated housewrap¹, which complies with building code requirements.

  • When orienting Hardie® Architectural Panels horizontally, a WRB with minimum 90% drainage efficiency per ASTM E2273 is required.

  • Adjacent finished grade must slope away from the building in accordance with local building codes – typically a minimum of 6 in. in the first 10 ft.

  • Do not use Hardie® Architectural Panels in Fascia or Trim applications.

  • Do not install James Hardie® products such that they may remain in contact with standing water.

  • For larger projects, where the span of the wall is significant in length, the designer and/or architect should take into consideration the coefficient of thermal expansion and moisture movement of the product in their design. These values can be found in the Technical Bullet in “Expansion Characteristics of James Hardie Siding Products” at www.jameshardie.com.

  • James Hardie Building Products provides installation/wind load information for buildings with a maximum mean roof height of 85 feet (Refer to the product Technical Data Sheet or ESR report). For information on installations above 60 feet, please contact JH technical support.

  • Minimum standard panel design size is 12” x 16”. Note: Panels may be notched and cut to size to fit between windows, doors, corners, etc.

  • Straight 16 gauge stainless steel finish nails.

¹For additional information on HardieWrap® Weather Barrier, consult James Hardie at 1-866-4Hardie or www.hardiewrap.com
CLEARANCE AND FLASHING REQUIREMENTS

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 8

FASTENING REQUIREMENTS
Refer to TDS (Technical Date Sheet) for Hardie Architectural Panels in the back of this document for wind load ratings (page 18).
FINISH NAIL REQUIREMENTS

  • Minimum 1-1/2 inch.
  • Stainless steel only.
  • 16 gauge straight. DO NOT use 15 gauge angled finish nails.

FASTENING GUIDELINES
The following guidelines should be followed to achieve the desired aesthetics from the fastening of stainless steel finish nails to attach Hardie® Architectural Panels:

  1. In-Line Regulator (Fig. 13)
    a. Control variable air supply from compressor
    b. 75-90 psi (average setting) if difficulty maintaining psi and/or depth control, check nailer for wear and replace or repair accordingly

  2. No-Mar Tips (fig.14)
    a. Avoid surface damage
    b. Depth control

  3. Gun angle to wall (fig. 15)

  4. Nails should be left proud, then tapped flush immediately with a smooth face hammer

  5. Do Not over drive fasteners
    a. Will appear after painting
    b. Will increase need for patching & touch-up

  6. Test nail depth on scrap prior to panel installation

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 9

GENERAL
Finish nails must be stainless steel. Fasteners must be corrosion resistant, galvanized, or stainless steel. Electro-galvanized are acceptable but may exhibit premature corrosion. Unless otherwise directed, James Hardie recommends the use of quality, hot-dipped galvanized nails. James Hardie is not responsible for the corrosion resistance of fasteners.
Stainless steel fasteners are recommended when installing James Hardie® products near the ocean, large bodies of water, or in very humid climates. Note: Ring shank (not smooth) shall be used when specifying stainless steel nails.
Manufacturers of ACQ and CA preservative-treated wood recommend spacer materials or other physical barriers to prevent direct contact of ACQ or CA preservative-treated wood and aluminium products. Fasteners used to attach HardieTrim Tabs, aluminium trim, or flashing to preservative treated wood shall be of hot dipped zinc-coated galvanized steel or stainless steel and in accordance to the latest versions of the IRC/IBC.

  • Consult applicable product evaluation or listing for correct fasteners type and placement to achieve specified design wind loads.
  • NOTE: Published wind loads may not be applicable to all areas where Local Building Codes have specific jurisdiction. Consult James Hardie Technical Services if you are unsure of applicable compliance documentation.
  • Drive fasteners perpendicular to siding and framing.
  • Fastener heads should fit snug against siding (no air space).

PNEUMATIC FASTENING
James Hardie® products can be hand nailed or fastened with a pneumatic tool. Pneumatic fastening is highly recommended. Set air pressure so that the fastener is driven snug with the surface of the siding. A flush mount attachment on the pneumatic tool is recommended. This will help control the depth the nail is driven. If setting the nail depth proves difficult, choose a setting that under drives the nail. (Drive under driven nails snug with a smooth faced hammer – Does not apply for installation to steel framing).
COLORPLUS FASTENERS
Color matched stainless steel finish nails are available for Hardie® Architectural Panels with ColorPlus technology Nails installed the same as described above. Touch- up fasteners as needed using the touch applicator brush Fig.16

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 5

Finish Nail *Use a smooth face hammer and lightly tap flush.
Tips: for fastener depth control:

  • Oil nail guns regularly.
  • If excessive air pressure (above 90psi) is needed or having difficulty controlling nail depth. Nail gun may be worn.

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 11

Tools

TOOLS FOR FASTENING

1. Straight 16 Gauge Stainless Finish Nails| 2. Straight Finish Nailer| 3. Inline Air Regulator
---|---|---
James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 12
Fasten using minimum 1-1/2 inch straight 16 gauge stainless steel nails. DO NOT use 15 gauge angled finish nails.| 16 gauge straight finish nailer for attaching trims and panels.| An inline pressure regulator will assist in better fastener depth control. Nails shall be underdriven as opposed to
overdriven if depth control is an issue

TOOLS FOR CUTTING METAL TRIMS

1. Miter Saw 2. Non-Ferrous Metals Blade 3. Tin Snips

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 13
To cut metal trims| 80-tooth| Cutting flashings

TOOLS FOR CUTTING HARDIE® ARCHITECTURAL PANELS

  1. Track Saw With Vacuum dust collection systemJames James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in 144 in Fiber Cement - FIGURE 14 OR
  2. 7-1/4 in Circular Saw with Vacuum dust collection systemJames James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in 144 in Fiber Cement - FIGURE 15 Cutting against straight edge is recommended.
  3. HardieBlade® Saw BladeJames James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in 144 in Fiber Cement - FIGURE 16Poly-dimaond blade for James Hardie® fiber cement.

FASTENING METAL TRIMS

Attach trims to: Wood – using a staple, or finish nail or flat head nail.
DO NOT use a button or bugle headed fastener when attaching trims.

Products and Accessories

INSTALLATION EXAMPLE

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 18

*Max 16 in. O.C. stud spacing applies to finish nail direct to stud application only. See Technical Data Sheet for nail spacing and additional framing options.
ACCESSORIES

1. Joint Sealant 2. HardieWrap® Weather Barrier 3. Seam Tape

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 19
General purpose polyutherane exterior grade joint sealant. Not supplied by James Hardie.| Water barrier and vapor permeable membrane.†| HardieWrap® seam tape or equivalent.
4. Flex Flashing| 5. Pro-Flashing| 6. Foam Back Sealing Tape (EPDM)
James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 20
HardieWrap® flex flashing or equivalent.| HardieWrap® pro-flashing or equivalent.| Minimum 2 in. x 1/16 in. thick.
Installed under vertical joints to improve water tightness.

TRIM

6. J Trim 7. Low-Profile Inside Corner Trim 8. Inside Corner Trim

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 21
Aluminium extrusion used as a trim at windows and soffits.
Aluminium extrusion to be used as a trim at abutments.
(e.g. soffits, masonry, windows, etc.)| Aluminium extrusion to be used for inside corners.| Aluminium extrusion to be used for inside corners.
9 Low-Profile Outside Corner Trim| 10 Low Profile 45˚ Inside Corner Trim| 11 Low Profile 45˚ Outside Corner Trim
James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 22
Aluminium extrusion to be used for outside corners.| Aluminum extrusion to be used for bay windows.| Aluminum extrusion to be used for bay windows.

VERTICAL TRIM OPTIONS

12. Vertical T Trim 13. Vertical H Trim

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 23
Aluminium extrusion to be used along vertical butt joints.
For horizontal panel orientations only.| Aluminium extrusion to be used along vertical butt joints.
For horizontal panel orientations only.

HORIZONTAL TRIM OPTIONS

14. Horizontal Angled T Flashing Trim 15. Horizontal Z Flashing Trim

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 24
Aluminium extrusion to be used along horizontal control joints.| Aluminium extrusion to be used along horizontal control joints.

OPTIONAL ACCESSORIES

16. Base Trim 17. Base Outside Corner Trim 18. Base Inside Corner Trim

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 25
Aluminum extrusion to be used as a base edge solution.| To be used as an outside corner connection for Base trim.| To be used as an inside corner connection for Base trim.
19. Base Jointer| 20. HardieTrim® Boards
---|---
James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 26
To be used to connect Base trims.| Fiber cement trim for corners and windows. Can be mounted horizontally or vertically.

FASTENER DETAILS
21. Straight 16 Gauge Stainless Finish Nails

Min. 1½ in. straight 16 gauge stainless steel finish nails. DO NOT use 15 gauge angled finish nails.

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 5

Finish Nail *Use a smooth face hammer and lightly tap flush.
Tips: for fastener depth control:

  • Oil nail guns regularly.
  • If excessive air pressure (above 90psi) is needed or having difficulty controlling nail depth. Nail gun may be worn.

Refer to the Hardie® Architectural Panel Technical Data Sheet for fastening options.
†When orienting panels horizontally a weather resistive barrier (WRB) with minimum 90% drainage efficiency per ASTM E 2273 is required.
Note: When installing preservative-treated wood/furring, a non permeable membrane shall be installed between the furring and aluminium trims.

Panel Installation

PANEL INSTALLATION PROCESS – VERTICAL ORIENTATION
When installing Hardie® Architectural Panels in the vertical orientation, one of the following conditions shall be used to meet moisture management requirements:

  1. Use drainage wrap† – install joint in moderate contact (no caulk or EPDM tape required by James Hardie).
  2. Standard WRB – caulk the vertical joint.
  3. Standard WRB – EPDM tape at the vertical joint.

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 28

*Refer to the Hardie® Architectural Panel Technical Data Sheet for fastening options.
†Requires code approved drainage wrap – a weather resistive barrier (WRB) with minimum 90% drainage efficiency per ASTM E 2273
PANEL INSTALLATION PROCESS – HORIZONTAL ORIENTATION
Requires code approved drainage wrap – a weather resistive barrier (WRB) with minimum 90% drainage efficiency per ASTM E 2273.

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 29

Construction Details

CONSTRUCTION DETAILS – JUNCTIONS

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 30

CONSTRUCTION DETAILS – CORNER DETAILS

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 31

NON-NAILABLE SUBSTRATES 1in. OR LESS (eg. foam & gypsum)

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 32

V-GROOVE JOINT PLACEMENT OPTIONS

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 33

CONSTRUCTION DETAILS – WINDOW DETAIL OPTIONS

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 34

CONSTRUCTION DETAILS – WINDOW DETAIL OPTIONS CONTINUED

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 35

CONSTRUCTION DETAILS – SOFFIT DETAILS

  • Finish nails are not allowed when installing Hardie® Architectural Panels as a soffit. Full headed nails only.
  • Multi-Groove panels can not be used in soffit applications.
  • For proper fastener selection, spacing and wind load rating refer to ESR 1844.

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 36

Finishing & Maintenance

CUT EDGE TREATMENT
IMPORTANT: Caulk, paint or prime all field cut edges. James Hardie touchup kits are required to touch-up James Hardie® products with ColorPlus® Technology finishes.
CARE & MAINTENANCE
Routinely perform the following to help maintain the appearance and performance of James Hardie® siding and trim products:

  • Washing down the exterior surfaces every 6 to 12 months with a garden hose or low pressure water spray to remove dirt and debris.
  • Re-applying of exterior finishes.
  • Maintaining the exterior envelope and connections including joints, penetrations, flashings, and sealants (caulking) to prevent moisture entry behind the siding.
  • Cleaning out gutters, blocked pipes, and overflows as required.
  • Prune vegetation to prevent contact with the siding.
  • Ensuring required external ground clearances and drainage slopes are maintained.

CAULKING
For best results use an Elastomeric Joint Sealant complying with ASTM C920 Grade NS, Class 25 or higher or a Latex Joint Sealant complying with ASTM C834. Caulking/Sealant must be applied in accordance with the caulking/sealant manufacturer’s written instructions.
NOTE: some caulk manufacturers do not allow “tooling”.
PAINTING
DO NOT use stain, oil/alkyd base paint, or powder coating on James Hardie® products. James Hardie factory primed products must be painted within 180 days of installation. 100% acrylic topcoats are recommended. Do not paint when James Hardie® products are wet. Follow paint manufacturer’s instructions and application rates. Back rolling is recommended if spray application is used.
Tips: for a beautiful finish

  • Surface preparation – Ensure the surface is dry, clean and any blemishes are patched using a suitable exterior grade cementitious patching compound and blend with surrounding texture using a sponge or scouring pad.
  • Prevent paint bridging by applying thin even coats of paint. If bridging occurs, take a paint brush and brush bridging out. When rolling or brushing paint with the joint lines. Do not paint across the joint lines, this may result in bridging.
  • Avoid excess painting of the “V” joint.

COLORPLUS® TECHNOLOGY FINISH CAULKING, TOUCH-UP & LAMINATE

  • Care should be taken when handling and cutting James Hardie® products ColorPlus® Technology finishes. During installation, use a wet soft cloth or soft brush to gently wipe off any residue or construction dust left on the product, then rinse with a garden hose.

  • Touch up nicks, scrapes and nail heads using the ColorPlus® Technology touch-up applicator. Touch-up should be used sparingly.
    If large areas require touch-up, replace the damaged area with a new piece of siding with ColorPlus Technology.

  • Laminate sheet must be removed immediately after installation of each course.

  • Terminate non-factory cut edges into trim where possible, and caulk.
    Color matched caulks are available from your James Hardie® products ColorPlus® Technology finishes dealer.

  • Treat all other non-factory cut edges using the ColorPlus® Technology edge coaters, available from your James Hardie® products ColorPlus® Technology finishes dealer.

NOTE: James Hardie does not warrant the usage of third party touch-up or paints used as touch-up on James Hardie® products with ColorPlus® Technology finishes.
PAINTING JAMES HARDIE® SIDING AND TRIM PRODUCTS WITH COLORPLUS® TECHNOLOGY FINISHES
When repainting James Hardie® products with ColorPlus® Technology finishes, James Hardie recommends the following regarding surface preparation and topcoat application:

  • Ensure the surface is clean, dry, and free of any dust, dirt, or mildew.
  • Repriming is normally not necessary.
  • 100% acrylic topcoats are recommended.
  • DO NOT use stain or oil/alkyd based paints on James Hardie products.
  • Apply finish coat in accordance with paint manufacturers’ written instructions regarding coverage, application methods, and application temperature.
  • DO NOT caulk nail heads when using James Hardie® products with ColorPlus® Technology finishes, refer to the ColorPlus® Technology touch-up section.

WARNING
High pressure water blast and sand blasting may damage the surface of the fiber cement product. Low pressure water spray, a soft medium bristle (nonmetal) brush is most suitable for cleaning fiber cement products. Acid washing can damage fiber cement surface and is not recommended.
NOTE: if using a pressure washer, care must be taken to ensure that the water stream does not damage the surface of the siding. Use wide fan tips that are kept a minimum of 6 feet from the wall and at a pressure under 1500 psi to minimize the chance of damaging the siding. Damage arising from improper cleaning or maintenance is not covered under applicable James Hardie warranties.

TECHNICAL DATA SHEET

Hardie® Architectural Panels
All national, state, and local building code requirements must be followed and where they are more stringent than the Hardie® Textured Panels installation requirements, state and local requirements will take precedence.
Document Scope
This document applies to the following Hardie® Architectural Panel- Fine Sand, Hardie® Architectural Panel- Fine Sand-Grooved, Architectural Panel- Mounded Sand, Architectural Panel- Sea Grass, and Architectural Panel- Sculpted Clay. The use of this product is limited to buildings not exceeding 85 feet in height.
General Description
Hardie® Architectural Panels are non-combustible fiber-cement panel, manufactured by James Hardie Building Products Inc.
Product Dimensions
Thickness –0.3125 inches
Length – 96, 120, & 144 inches
Width – 48 inches
Vertical Joint – Shiplap
Product Composition
Hardie® Architectural Panels are Grade II, Type A, fiber-cement sheets as defined by ASTM C 1186. The panels are manufactured by the Hatschek process and cured by high pressure steam autoclaving.
Code Compliance
Hardie® Architectural Panels complies with:

  • The 2009, 2012, and 2015 International Building Code® (IBC) Section 1404.10, 2018 and 2021 International Building Code® (IBC) Section 1403.10 and 2009, 2012, 2015, 2018, and 2021 International Residential Code® (IRC) Table R703.3(1) and Section R703.10.1 as ASTM C 1186 Grade II, Type A Fiber Cement.
  • The 2017 and 2020 Florida Building Code® (FBC) Section 1404.10 and 1405.16 as ASTM C 1186 Grade II, Type A Fiber Cement.

Wind Design:

  • Design Tables 2 & 3 provide allowable capacity in mph for transverse load conditions for the Hardie® Architectural Panels attached to either wood framing, furring or WSP, tested in accordance to ASTM E 330.
  • Wood framing shall have a specific gravity of 0.42 or greater unless otherwise stated.
  • Wood Structural Sheathing (WSP) panel must have a specific gravity of 0.50 or higher unless otherwise stated.

Fire Characteristics:

  • Hardie® Architectural Panels are classified as non-combustible when tested in accordance with ASTM E136.
  • Hardie® Architectural Panels may be used in ASTM E119 fire resistance rated assemblies as listed by Warnock Hersey.
  • Hardie® Architectural Panels are a Class A material according to 2017 and 2020 FBC, 2018 and 2021 IBC Section 803.1.2; Surface Burning Characteristics when tested in accordance with ASTM E 84: Flame Spread Index = 0 and Smoke Developed Index = 0.
  • The building official reserves the right to approve alternate materials, design and methods of construction based on research reports and/or tests based on 2018 IBC, 2017 & 2020 FBC Section 104.11.

Installation Requirements

  • Test reports can be furnished to the building official upon request, contact your local James Hardie sales representative.
  • Hardie® Architectural Panels shall be installed on exterior walls braced in accordance with the applicable building code.
  • A water-resistive barrier complying with Section R703.2 of the IRC or Section 1403.2 of the FBC is required to be installed.
  • Install the Hardie® Architectural Panels in accordance with this report and the James Hardie published installation requirements. For a copy contact your local James Hardie sales representative or visit www.JamesHardiePros.com.

Table 1, Hardie® Architectural Panels ASTM C 1186 Physical Properties and Supplementary Requirements

Physical Attributes| ASTM Test Method| General Property| Unit or Characteristic| Requirement| Result
---|---|---|---|---|---
ASTM C1185| Dimensional Tolerances| Length
Width
Thickness
Squareness
Edge Straightness| ± 0.5% or ±1/4in
± 0.5% or ±1/4in
± 0.04 in
<1/32 in/ft of length
<1/32 in/ft of length| Pass
ASTM C1185| Density, Ibift,| | As reported| <83
ASTM C1185| Water Tightness| Physical Observations| No drop formation| Pass
ASTM C1185| Flexural Strength| Wet conditioned, psi Equilibrium conditioned, psi| >1015 psi

1450 psi| Pass
ASTM C1185| Warm Water Resistance, Observations| Physical Observations| No visible cracks or structural alteration| Pass
Ammeina| ASTM C1185| Heat/Rain Resistance| Physical Observations| No visible cracks or structural alteration| Pass
ASTM C1185| Freeze/Thaw Resistance| Physical Observations Mass
Loss, %
Freeze/Thaw, % strength retention| No visible cracks or structural alteration
≤ 3.0%
≥ 80%| Pass
Fire Characteristics| ASTM E84| Surface Burning Characteristics| Flame Spread Index (FSI) Smoke
Developed Index (SDI)
Fuel Contributed
International Building Code®| As reported| 0
0
0
A
ASTM E136| Non-combustibility| | As reported| Pass

Table 2, Wind Design Table, Exposed Fastening
Allowable Wind Speed (mph) for Hardie® Architectural Panels (Analytical Method in ASCE 7-10, 7-16 Chapter 30)

| 2017 & 2020 FBC,
2012 & 2015 IBC,
2015 & 2018 IRC
(Ultimate Design
Wind Speed, Vult),5,9 2018 IBC (Basic Design Wind Speed, V)11| 2006, 2009 &
2012 IRC
2006 & 2009 IBC
(Nominal Design
Wind Speed,
vasd)4.10.12.13
---|---|---
Wind| BCD exposure category| | Wind| BCD exposure category|
Product¹| Minimum
Thicknes
s (in.)| Fastener
T yp e| Fastener
S p acin g| Frame Type| Stud
Spacing
(in.)| Allowable
Design
load (psf)| Building
Height
(ft.)23
Hardie®
Architect
ural Panel¹| | 16 Gauge, 11/2″ long, ,
stainless
Finish Nail| 4 inches
along studs| 2X4 wood 6| 16| 34.| 0-15| 153| 139| 126| 119| 108| 98
20| 153| 135| 123| 119| 105| 95
40| 147| 126| 116| 114| 97| 90
60| 139| 120| 112| 108| 93| 87
Hardie®
Architect
ural Panel¹| | 16 Gauge, 11/2″ long, ,
stainless
Finish Nail| 4 inches
along studs| 2X4 wood ‘| 16| 37.0| 0-15| 160| 145| 132| 124| 113| 102
20| 160| 141| 129| 124| 109| 100
40| 154| 131| 121| 119| 102| 94
60| 145| 126| 117| 113| 98| 91
Hardie@
Architect
ural¹| Panel l 5/16| 16 Gauge, 1.25″ long, stainless Finish Nail| 4 inches o.c.
vertically
along furring
strips spaced
at 16 inches
o.c., min. 3/8″
from edge of
siding| 2×4 wood or
20 ga. (33
mils) steel
framing with
%” thick by
3.5″ wide WSP
furring
(SG=0.50)14| 16| 28.| 0-15| 139| 126| 114| 107| 97| 89
20| 139| 122| 112| 107| 95| 86
40| 133| 114| 105| 103| 88| 81
60| 126| 109| 101| 97| 85| 78
Hardie@
Architect
ural Panel¹| 5/16| 16 Gauge, 1.25″ long, stainless Finish Nail| 4 inches o.c.
vertically
along furring
strips spaced
at 16 inches
o.c., min. 3/8″
from edge of
siding| 2×4 wood or
20 ga.(33 mils)
steel framing
with 3/4 ” by3.5″
wide SPF
furring
(SG=0.42)14| 16| 21.| 0-15| 122| 110| 100| 94| 85| 78
20| 122| 107| –| 94| 83| –
40| 117| –| –| 90| –| –
60| 110| –| –| 85| –| –

Table 3, Wind Design Table, Off-Stud Nailing Application
Allowable Wind Speed (mph) for Hardie® Textured Panels (Analytical Method in ASCE 7-10, 7-16 Chapter 30)

| 2017 & 2020 FBC, 2012 & 2015 IBC, 2015 & 2018 IRC (Ultimate Design Wind Speed, Vult),5,9 2018 IBC (Basic Design Wind Speed, V)11| 2006, 2009 & 2012
IRC 2006 & 2009 IBC
(Nominal Design
Wind Speed, Vasd)
4,10,12,13
---|---|---
Wind B| exposure category
C| D| Wind B| exposure category
C| D
Product¹| Minimum
Thickness
(in.)| Fastener
Type| Fastener
Spacing| Frame Type| Stud
Spacing
(in.)| Allowable
Design
load (psf)| Building
Height
(ft.)23
Hardie®
Architect
ural Panel¹| 5/16| 16
Gauge,
11/2″
long,
stainless
Finish
Nail| 4 inches
along studs
& panel
edges.
See figure 1| 2X4 wood’
with min
7/16″ Wood
Structural
Panel9 Sheathing
attached per
code| 16| 43.| 0-15
110| 172| 156| 142| 133| 121|
20| 172| 152| 138| 133| 117| 107
40| 165| 141| 130| 128| 109| 101
60| 156| 135| 126| 121| 105| 97
Hardie®
Architect
ural Panel¹| 5/16| 16
Gauge,
11/2″
long,
stainless
Finish
Nail| 4 inches
along studs
& panel
edges.
See figure 2| 2X4 woods
with min
7/16″ Wood
Structural
Panel9
Sheathing
attached per
code| 24| 31.| 0-15| 147| 133| 121| 114| 103| 94
20| 147| 130| 118| 114| 100| 92
40| 141| 121| 111| 109| 93| 86
60
-2X4| 133| 116| –| 103| 90|
Hardie®
Architect
ural Panel¹| 5/16| 16 Gauge,
11/2″
long, stainless
Finish Nail| 4 inches
along studs
& panel
edges. See figure 2| wood’
with min
7/16 Wood”
Structural
Panel9
Sheathing
attached per
code| 24| 28.0| 0-15| 139| 126| 115| 108| 98| 89
20| 139| 123| 112| 108| 95| 87
40| 134| 114| –| 104| 89| –
60| 126| –| –| 98| –| –

  1. Installation must be in accordance with manufacturer’s installation instructions
  2. Building heights are the mean roof height (ft) of a building except the eave height shall be used for the roof angles of less than or equal to 10° (2-12 roof slope)
  3. Linear interpolation of building height (≤ 60ft) and wind speed is permitted.
  4. Wind speed design coefficient assumptions per Analytical Method in ASCE 7-05: I=1, Kzt=1, Kd=0.85, GCp= -1.4, GCpi= -0.18
  5. Wind speed design assumptions per Analytical Method in ASCE 7-10 &ACE 7-16 Section 30.4: Kzt=1, Kd=0.85, GCp= -1.4, GCpi= 0.18
  6. Wood framing species must have a specific gravity of 0.42 gravity or higher.
  7. Wood framing species must have a specific gravity of 0.46 gravity or higher.
  8. Wood Structural Sheathing panel must have a specific gravity of 0.50 or higher.
  9. Vult = ultimate design wind speed.
  10. Vasd = nominal design wind speed.
  11. V = basic design wind speed
  12. Basic Design Wind Speed per ASCE 7-16 or 2017 FBC/2018 IBC Figures 1609.3(1) through 1609.3(8). Where design is based on the fastest mile wind speeds, the basic wind speed shall be converted to the fastest mile wind speed Vfm per Section R301.2.1.3 of the 2012 IRC.
  13. 2017 & 2020 FBC, 2018 IBC Section 1609.3.1 Eq. 16-33, Vasd = Vult (0.6)⁰.⁵
  14. The NDS published specific gravities of SPF lumber & Wood Structural Panel (WSP) furring are 0.42 and 0.50 respectively. Attachment of the furring to the structural framing must be determine by the project design engineer to resist the allowable design wind loads for the maximum wind speeds as tabulated.

© 2022 James Hardie Building Products, Inc. All rights reserved. TM, SM, and ® denote trademarks or registered trademarks of James Hardie Technology Limited. Other marks or registered trademarks or service marks are the property of their respective owners
Figure 1, Fastening Configuration for 16″ O.C. Wood Frame: Off-Stud Application

  • 4 in o.c. along studs
  • 4 in o.c. along panel edges
    • Edges may be attached to WSP sheathing only

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 37

Figure 2, Fastening Configuration for 24” O.C. Wood Frame: Off-Stud Application

  • 4 in o.c. along studs
  • 4 in o.c. along panel edges
    • Edges may be attached to WSP sheathing only

James James Primed Hardie Architectural Collection HZ10 0 312 in 48 19 in
144 in Fiber Cement - FIGURE 38

SILICA WARNING
022 James Hardie Building Products, Inc. All rights reserved. TM, SM, and ® denote trademarks or registered trademarks of James Hardie Technology Limited. Other marks or registered emarks or service marks are the property of their respective owners. DANGER: May cause cancer if dust from product is inhaled. Causes damage to lungs and respiratory system through prolonged or repeated inhalation of dust from product. Refer to the current product Safety Data Sheet before use. The hazard associated with fiber cement arises from crystalline silica present in the dust generated by activities such as cutting, machining, drilling, routing, sawing, crushing, or otherwise abrading fiber cement, and when cleaning up, disposing of or moving the dust. When doing any of these activities in a manner that generates dust you must (1) comply with the OSHA standard for silica dust and/or other applicable law, (2) follow James Hardie cutting instructions to reduce or limit the release of dust; (3) warn others in the area to avoid breathing the dust; (4) when using mechanical saw or high speed cutting tools, work outdoors and use dust collection equipment; and (5) if no other dust controls are available, wear a dust mask or respirator that meets NIOSH requirements (e.g. N-95 dust mask). During clean-up, use a well maintained vacuum and filter appropriate for capturing fine (respirable) dust or use wet clean-up methods – never dry sweep.
WARNING: This product can expose you to chemicals including respirable crystalline silica, which is known to the State of California to cause cancer. For more information go to P65Warnings.ca.gov.
RECOGNITION: James Hardie® Hardie® Architectural Panels complies with ASTM C1186 and meets the following Fiber-Cement siding code requirements; Sections 1404.10, 1405.16, and 1405.16.1 (2006, 2009, 2012, 2015 IBC), Sections 1403.10, 1404.16 & 1404.16.1 (2018, 2022 IBC), Table R703.4 (2006, 2009, 2012 IRC), Table R703.3 (2015, 2018, 2022 IRC) and Section R703.10. Hardie® Architectural Panel is also recognized for application with the following product approval agencies: State of Florida Product Approval FL#13223.
© 2022 James Hardie Building Products Inc. All rights reserved TM, SM and ® denote trademarks or registered trademarks of James Hardie Technology Limited.
Product warranties, safety information and additional installationinformation are available at jameshardiepros.com

James James Primed Hardie LOGO 2 HS20110 P 21/21 01/22

Documents / Resources

| James James Primed Hardie Architectural Collection HZ10 0.312-in x 48.19-in x 144-in Fiber Cement [pdf] Instruction Manual
Primed Hardie Architectural Collection HZ10 0.312-in x 48.19-in x 144-in Fiber Cement Primed Hardie Architectural Collection, HZ10 0.312-in x 48.19-in x 144-in Fiber Cement
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

James James User Manuals

Related Manuals