REC Pre-Charge Unit User Manual

June 8, 2024
REC

REC PRE-CHARGE UNIT V3.0

REC Pre-Charge Unit

Features:

– robust and small design
– low power consumption @ 11-80 V DC
– 1/2/4/8 s DIP switch delay settings
– up to 120 V, 4.0 A pre-charge
– integrated 15 and 30 Ω power resistor + 10 Ω NTC
– 6.0 A top side coil drive with over-current protection
– single pole or bi-stable latching contactor drive
– reverse polarity protection
– over-voltage protection
– one-year warranty

General Description:

High input capacitance systems such as inverters, dc-dc converters, etc. can be exposed to large inrush currents during the initial power up procedure. If appropriate measures
are not employed, these currents can overly stress or even damage the system components. The pre-charge unit eliminates high in-rush currents by charging the input capacitor before the main contactor switches on, prolonging lifespan of the contactor and other components dramatically.

Parameters:

Table 1: Pre-charge parameter table.

Parameter Value Unit
Supply voltage range Vcc — V55 10 – 80 v
Supply current Ism 1 @ VCC = 10 V mA
2 @VCC=30V mA
3@VCC=60V mA
4@VCC=80V mA
Battery pack voltage range VEAT – Vm 10 – 120 V V
BMS input voltage range Vss — (Vss + 5.0) V
BMS input voltage enable threshold <=(Vss + 0.2) Ω
BMS input voltage disable threshold >(Vss + 1.7) Ω
BMS input current 0.03 mA
Pre-charge resistance output pin 5 15 + NTC 10 Ω
Pre-charge resistance output pin 10 30 + NTC 10 Ω
Pre-charge output voltage VPRECHARGE 30 + NTC 10 Ω
Contactors + output coil voltage max Vcc -0.7 v
Contactors + output coil voltage min Vcc -1.0 v
Contactor coil fuse 6.3 slow blow A
Pre-charge fuse 4.0 slow blow A
Time delay 1/2/4/8 s
Bi-stable latching relay set/reset time 100/150 ms
Contactors — to VSS resistance 100
Dimensions 127x 70.6 x 35.5 mm
Crimps TE connectivity 795299-1 n a
Crimping tool 18-22 AWG
Weight 129 g
IP rating 20 n a

Pre-charge description:

REC Pre-Charge Unit - Fig 1

Pre-charge connections:

REC Pre-Charge Unit - Fig 2

Table 2: Pre-charge pinout.

Pin| Tab| Single pole contactor connection| 3i-stable latching contactor connection
---|---|---|---
1| N/SET COIL +| Contactor coil +| Bi-stable latching contactor SET coil +
2| N/SET COIL –| Contactor coil –| Bi-stable latching contactor SET coil –
3| SUPPLY +| Supply positive 10 — 80 V| Supply positive 10 — 80 V
4| PACK +| Battery pack + (10 — 120 V)| Battery pack + (10 — 120 V)
5| SYSTEM + 15 Ω| System side + pre-charge 15Ω| System side + pre-charge 15 Ω
6| RESET COIL +| –| Bi-stable latching contactor RESET coil +
7| RESET COIL –| –| Bi-stable latching contactor RESET coil –
8| SUPPLY GND| Supply GND| Supply GND
9| BMS Input GND| BMS input — pull down to Supply GND| BMS input — pull down to Supply GND
10| SYSTEM + 30 0| System side + pre-charge 30 0| System side + pre-charge 30 0

System Overview:

Figure 3 shows the integration of the pre-charge unit in a typical 24 V battery power system, using REC 1Q BMS with an internal relay control. Only the connections relevant to the pre-charge unit operation are shown. 15 Ω pre- charge output is used in conjunction with 24 V single coil power contactor. After the battery pack is connected to SUPPLY + and SUPPLY GND internal pre- charge slowly charges the input capacitor and powers the POWER red LED. Unit enters standby mode lowering its consumption
until the BMS input GND is pulled down to SUPPLY GND. Then the internal DIP switches are read (see Table 4 for detail settings description). When the pre- charge  timeouts, SET coil is powered either constantly ON for normal single coil relay/contactor or turned ON for a period of 100 ms for engaging bi- stable latching relay. Then the pre-charge transistor inside the unit is turned OFF. When the BMS input GND is released, SET coil is either turned OFF or RESET output is powered for 150 ms to turn the bi-stable relay/contactor OFF.
Figures 3 – 6 show typical system integrations.

REC Pre-Charge Unit - Fig 3

REC Pre-Charge Unit - Fig 4

REC Pre-Charge Unit - Fig 5

REC Pre-Charge Unit - Fig 6

Measuring/Setting Pre-charge Delay:

To set the pre-charge delay properly, system voltage should be measured at the end of pre-charge timer phase. Connect all required connections except the N/SET COIL + connection to disable contactor engaging. Enable the pre-charge by pulling BMS Input GND to SUPPLY GND by the BMS or manually. Measure the system voltage @ the system side of the contactor. Before the pre-charge timer ends the system, voltage should rise to at least to 80 % of the battery voltage. If the voltage stays below this value increase the pre-charge delay or use the SYSTEM + 15 Ω output. Pre-charge current should be limited to a maximum value of 4 A (Max battery voltage / pre-charge resistance).

Table 3: Pre-charge resistance selection.

Battery voltage [V]| Battery voltage range[V]| Pre-charge output
---|---|---
12| 10 -16| SYSTEM + 15 Ω output
24| 21- 30| SYSTEM + 15 Ω output
48| 43 – 67| SYSTEM + 15Ω output
80| 64 -88| SYSTEM + 30 Ω output
80+| 90 to 120| SYSTEM + 30 Ω output +
external 22-33 Ω 50 W

Please note: Some of the inverters/controllers on the system side may start to work with lower voltage and their power consumption prevent system voltage to rise.

REC Pre-Charge Unit - Fig 7

You can prolong the pre-charge time by changing DIP switches inside the Pre- charge unit without Precharge unit power disconnection. Per-charge only requires to be  disabled by the BMS input GND. Bellow you can find DIP switch settings description.

REC Pre-Charge Unit - Fig 8

Table 3: DIP switch function description.

Settings DIP 3 DIP 2 DIP 1 Function

REC Pre-Charge Unit - Fig 9| OFF| OFF| OFF| Single pole contactor/relay 1 s pre-charge time
OFF| OFF| ON| Single pole contactor/relay 2 s pre-charge time
OFF| ON| OFF| Single pole contactor/relay 4 s pre-charge time
| OFF| ON| ON| Single pole contactor/relay 8 s pre-charge time
---|---|---|---|---
ON| OFF| OFF| Bi-stable latching contactor/relay 1 s pre-charge time*
ON| OFF| ON| Bi-stable latching contactor/relay 2 s pre-charge time
ON| ON| OFF| Bi-stable latching contactor/relay 4 s pre-charge time
ON| ON| ON| Bi-stable latching contactor/relay 8 s pre-charge time

Dimensions:

REC Pre-Charge Unit - Fig 11

Rozna ulica 20, 6230 Postojna, Slovenia
mail: info@rec-bms.com; www.rec- bms.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals