HYTRONIK HIM30 IP65 High Bay HF Sensor Instructions

June 8, 2024
HYTRONIK

HYTRONIK HIM30 IP65 High Bay HF Sensor

Technical Data

Input Characteristics

  • Model No. HIM30
  • Mains voltage 220-240VAC 50/60Hz
  • Stand-by power <1W Load ratings:
  • Capacitive 800W
  • Resistive 1000W
  • Warming-up 30s

Sensor Data

Model No.  HIM30

  • Sensor principle High Frequency (microwave), PIR
  • Operation frequency 5.8GHz +/- 75MHz (HF)
  • Transmission power <0.2mW (HF)
  • Sensor mode 4 modes: PIR, HF, PIR+HF, PIR/HF
  • Detection range Max. ( O x H) 10m x 12m
  • Detection angle 360O

Safety and EMC

  • EMC standard (EMC) EN55015, EN61000
  • Safety standard (LVD) EN60669, AS/NZS60669
  • Radio Equipment (RED) EN300440, EN301489-1, EN62479
  • Certifcation Semko, CB, CE , EMC, RED

Environment

  • Operation temperature  Ta: -20OC ~ +50OC
  • IP rating IP65

Mechanical Structures and Installations

For more details, please refer to user manual.

A. Ceiling mount

HYTRONIK-HIM30-IP65-High-Bay-HF-Sensor-FIG-1

B. Screw to the Luminaire by conduit

HYTRONIK-HIM30-IP65-High-Bay-HF-Sensor-FIG-2

C. Attach to the shade by clamp

HYTRONIK-HIM30-IP65-High-Bay-HF-Sensor-FIG-3

Dual Sense Introduction

It’s commonly known Microwave and Infrared are main detecting technologies in lighting controls. Both have the advantage and disadvantage for industrial applications.

Advantage

  • sensitive to minor motion.
  • sensitive to radial movement.
  • can be retected by objects hence covering big detection area
  • resilient to heat source, smoke and and air conditioner.

Advantage

  • no penetration, confined detection area.
  • sensitive to tangential movement.
  • resilient to motion object which has no heat radiation.

Disadvantage

  • can be false triggered by air conditioner, smoke and other heat sources.

The remedy is to create Dual Sense by combining both technologies to make use of the advantage and bypass the disadvantage.

4 optional detection modes via remote control

  • HF: Microwave only
  • PIR: PIR mode only
  • HF+PIR: both PIR and microwave mode, to decrease the detection capability and detection area. Only when both detections are activated, the motion is considered valid. This is to prevent the sensor from false trigger by heat source, air conditioner, ventilation fans, water pipe and elevators etc…
  • HF/PIR: either PIR or microwave mode, to increase the detection capability and detection area;

Functions and Features

Intelligent Photocell (daylight detection prior to motion detection) The built-in photocell will also automatically turn off the light when the ambient natural light exceeds the programmed lux level for more than 5min, regardless of whether motion is detected or not.

  • With suffcient natural light, the light does not switch on when presence is detected.
  • With insuficient natural light, the sensor switches on the light automatically when presence is detected.
  • The sensor switches off the light when natural light is suficient, even with presence.HYTRONIK-HIM30-IP65-High-Bay-HF-Sensor-FIG-7

On/off Control This sensor is a motion switch, which turns on the light upon detection of motion, and turns off after a pre-selected hold-time when there is no movement. A daylight sensor is also built in to prevent the light from switching on when there is suficient natural light.

Zero-cross Relay Operation
Designed in the software, sensor switches on/off the load right at the zero- cross point, to ensure that the in-rush current is minimised, enabling the maximum lifetime of the relay.

Rotary Switch Preset

A rotary switch is built inside the sensor for scene selection / fast programming. Total 16 channels are available:

Note: settings can also be changed by remote control HRC-11. The last action controls.

Settings (Remote Control HRC-11)

Permanent ON/OFF function

Press button “ON/OFF” to select permanent ON or permanent OFF mode.  Press button “AUTO”, “RESET” to quit this mode.

Reset Settings

Press button “RESET”, all settings go back to rotary switch settings.

Shift Button

Press button “Shift”, the LED on the top left corner is on to indicate mode selection. All values / settings in RED are valid for 20 seconds.

AUTO mode

Press button “AUTO” to initiate automatic mode. The sensor starts working and all settings remain as before the light is switched ON/OFF.
Note: “ Semi-auto” function is disabled.

Power output

These two buttons are disabled.

Brightness +/-

These two buttons are disabled.HYTRONIK-HIM30-IP65-High-Bay-HF-Sensor-
FIG-17

HRC-11

Load Indication: The light will flash ONCE rapidly after receiving the commamd from the remote control successfully.

Scene program – 1-key commissioning

  1. Press button “Start” to program.
  2. Select the buttons in “Detection range”, “Daylight threshold”, “Hold-time” to set all parameters.
  3. Press button “Memory” to save all the settings programmed in the remote control.
  4. Press button “Apply” to set the settings to each sensor unit(s).

For example, to set detection range 100%, daylight threshold Disable, hold- time 5min, the steps should be: Press button “Start”, button ”100%”, “Disable”, “Shift”, “5min”, “Memory”. By pointing to the sensor unit(s) and pressing “Apply”, all settings are passed on the sensor(s).

Detection range
Press buttons in zone “Detection range” to set detection range at 100% / 75% / 50% / 10%.

Daylight threshold

Press buttons in zone “ Daylight threshold” to set daylight sensor at 2Lux/ 10Lux / 50Lux / 100Lux / 300Lux / 500Lux / Disable.
Note: To set daylight sensor at 100Lux / 300Lux / 500Lux, press “Shift” button first.

Ambient daylight threshold

  1. Press button “Shift”, the red LED starts to fash.
  2. Press button “Ambient”, the surrounding lux level is sampled and set as the new daylight threshold.

Hold-time

Press buttons in zone “hold-time” to set the hold-time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.
Note: 1. To set hold-time at 30s / 5min / 15min / 30min, press “Shift” button first. 2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode. *To exit from Test mode, press button “RESET” or any button in “Hold-time”.

All buttons in zone “Stand-by time”, “Standy-by dimming level & Auto-config”, “Dual tech & RF mode” are disabled.HYTRONIK-HIM30-IP65-High-Bay-HF-Sensor-
FIG-19

Detection Pattern

End user can choose the suitable PIR lens in real application to fulill various requirements. Three options are offered for selection:

HYTRONIK-HIM30-IP65-High-Bay-HF-Sensor-FIG-20

Detection pattern for forklift

HYTRONIK-HIM30-IP65-High-Bay-HF-Sensor-FIG-21

Detection pattern for human

HYTRONIK-HIM30-IP65-High-Bay-HF-Sensor-FIG-22

Additional Information / Documents

  1. Regarding precautions for microwave sensor installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->Microwave Sensors – Precautions for Product Installation and Operation
  2. Regarding precautions for PIR sensor installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->PIR Sensors – Precautions for Product Installation and Operation
  3. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download->knowledge ->Hytronik Standard Guarantee Policy

www.hytronik.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals