HUSSMANN CoreLink Emergency Shutdown Configurations Instruction Manual

June 9, 2024
HUSSmAnn

HUSSMANN - logo CoreLink Emergency Shutdown Configurations
Instruction ManualHUSSMANN CoreLink Emergency Shutdown
Configurations

IMPORTANT
Keep in store for future reference!

CoreLink Emergency Shutdown

Objectives:
To handle some safety and other functional priorities in systems like CO2 systems and other special configurations, rack controller would like to shut down the refrigeration  in the cases/refrigeration units.
When CoreLink is controlling the cases/refrigeration units, Emergency shutdown can be initiated through either a hardwired signal or through communications.
This document describes the configuration, setup and connectivity for both the methods.

Digital Signal – Hardware Setup
Requirements: CoreLink does not have the ability to accept dry contact at the digital input. CoreLink requires a source voltage when triggering the digital input. The source  can be 24vac or 24vdc, though it is recommended to use 24vac for reduced polarity risk and simple installation. CoreLink

Wiring Diagram

HUSSMANN CoreLink Emergency Shutdown Configurations - Figure
1

CoreLink Delivered Configuration

HUSSMANN CoreLink Emergency Shutdown Configurations - Figure
2

Emergency Shutdown Operation:
Following two shutdown methods are enabled in CoreLink.
Enable/Disabled DI – All digital outputs are disabled. Refrigeration, Defrost, Lights, Evap Fan, Cond Fan, etc. Case controller continues to data log and monitor analog  input temperatures & pressure. System Enable is always active on PIN 20 Digital Input.

Refrigeration Shutoff DI (Optional) – Refrigeration, Evap Fan, Cond Fan, EEV 0% disabled ONLY.
This can be configured on one of the available pins in the Digital Inputs menu. All other controller operations continue to operate.

Primary Controller

This is for a direct hardwired configuration through a Primary controller like E2 rack controller.
Install a single 24vac transformer. Use this transformer to provide 24vac signal to all Corelink case controllers. It is recommended that the polarity at the Digital output(DO)  board be configured as the following:

Relay Open = Controller Enabled| (Primary Controller opens relay for normal case operation)
---|---
Relay Closed = Controller Disabled| (Primary Controller closes relay for emergency shutdown)

Note: When configured in this manner, no polarity adjustments at Corelink case controller are required. Landing the wires at the appropriate terminal is only required. If  configured reverse, the polarity opposite at the E2, the polarity would have to be adjusted at each individual case controller in the digital input menu which increases the  amount of work to complete the install.

Network Configuration – Software Setup

Description: Users can use the RS485 communication network and BAS system to send network disable commands to each controller. Depending on the BAS user interface,  a user could point to each individual controller and utilize the same Enable Network or Refrigeration Disable Network commands through software. This can provide  additional system safety through multiply layers of protection if physical digital input setup was to fail.
Application Programs could be used to activate each controller one at a time to reduce the load on the refrigeration rack system after emergency shutdown. Please consult  BAS system operation manuals to benefit from these options or contact your BAS system administrator for application.

Parameter Name| Address| Unit| Scale| Data Type| Data Description and Valid Range
---|---|---|---|---|---
System Enable| 16#6A06| NULL| 0| BOOL| TRUE, system enable; FALSE, system disable
via Network| |
Refrig Disable Network| 16#6B00| NULL| 0| BOOL| Refrig Disable network command if set to 1

CoreLink™
HUSSMANN CORPORATION
BRIDGETON, MO 630442483
U.S.A.
Shutdown

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HUSSmAnn User Manuals

Related Manuals