BLAUBERG KOMFORT Roto EC S6K 200 Heat Recovery Air Handling Unit User Manual
- June 9, 2024
- BLAUBERG
Table of Contents
- KOMFORT Roto EC S6K 200 Heat Recovery Air Handling Unit
- SAFETY REQUIREMENTS
- DELIVERY SET
- DESIGNATION KEY
- TECHNICAL DATA
- DESIGN AND OPERATING PRINCIPLE
- MOUNTING AND SET-UP
- HUMIDITY SENSOR MOUNTING
- DECORATIVE PANEL MOUNTING
- SERVICE SIDE CHANGE
- UNIT INSTALLATION
- TECHNICAL MAINTENANCE
- TROUBLESHOOTING
- STORAGE AND TRANSPORTATION REGULATIONS
- MANUFACTURER’S WARRANTY
- CERTIFICATE OF ACCEPTANCE
- SELLER INFORMATION
- INSTALLATION CERTIFICATE
- WARRANTY CARD
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
KOMFORT Roto EC S6K 200 Heat Recovery Air Handling Unit
User Manual Heat recovery air Handling unit
KoMFort roto ec S6K 200
KoMFort roto ec S6eK 200
KOMFORT Roto EC S6K 200 Heat Recovery Air Handling Unit
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about purpose, technical details, operating
principle, design, and installation of the KOMFORT Roto EC S6(E)K 200 unit and
all its modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
SAFETY REQUIREMENTS
All user’s manual requirements as well as the provisions of all the applicable
local and national construction, electrical, and technical norms and standards
must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing,
maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to
1000 V are allowed for installation. The present user’s manual should be
carefully read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the
grille before starting installation. The casing internals must be free of any
foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing! Deformation of the
casing may result in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky
substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing
spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the
efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the
document’s preparation.
The Company reserves the right to modify the technical characteristics,
design, or configuration of its products at any time in order to incorporate
the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the
appliance.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent, or similarly qualified persons in order to avoid a safety
hazard.
Ensure that the unit is switched off from the supply mains before removing the
guard.
Precautions must be taken to avoid the back-flow of gases into the room from
the open flue of gas or other fuel-burning appliances.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT
DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
The unit is designed to ensure continuous mechanical air exchange in houses,
offices, hotels, cafes, conference halls, and other utility and public spaces
as well as to recover the heat energy contained in the air extracted from the
premises to warm up the filtered stream of intake air.
The unit is not intended for organizing ventilation in swimming pools, saunas,
greenhouses, summer gardens, and other spaces with high humidity.
Due to the ability to save heating energy by means of energy recovery, the
unit is an important element of energy-efficient premises.
The unit is a component part and is not designed for stand-alone operation. It
is rated for continuous operation.
Transported air must not contain any flammable or explosive mixtures,
evaporation of chemicals, sticky substances, fibrous materials, coarse dust,
soot and oil particles or environments favourable for the formation of
hazardous substances (toxic substances, dust, pathogenic germs).
THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL,
MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE TRAINING.
THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL
AFTER THE APPROPRIATE BRIEFING.
THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORISED ACCESS BY
UNATTENDED CHILDREN.
DELIVERY SET
Name | Number |
---|---|
Air handling unit | 1 |
User’s manual | 1 |
Control panel* | 1 |
Decorative panel | 1 |
Decorative panel mounting bracket | 4 |
Fastening kit | 1 |
Packing box | 1 |
*The control panel is not included in the delivery set of the units with the S21 controller.
DESIGNATION KEY
TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature
ranging from +1 °C up to +40 °C and relative humidity up to 60 % without
condensation. In cold, damp rooms, there is a possibility of freezing or
condensation inside and outside the casing.
In order to prevent condensation on the internal walls of the unit, it is
necessary that the surface temperature of the casing is 2-3 °C above the dew
point temperature of the transported air.
The unit should be operated continuously, and in cases where ventilation is
not necessary, reduce the air flow of the fans to a minimum (20%). This will
ensure a favorable indoor climate and reduce the amount of condensation inside
the unit, which can damage electronic components. Never use the unit for
dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP22 for the unit connected to the air ducts
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly
different from those described in this manual.
Parameter | KOMFORT Roto EC S6K 200 | KOMFORT Roto EC S6EK 200 |
---|---|---|
Unit voltage [V/SO (60) Hz] | 1— 230 | |
Maximum unit power (without a heater) [W] | 118 | |
Maximum heater power [W] | – | 700 |
Maximum unit power [W] | 118 | 818 |
Maximum unit current (without a heater) [A] | 10 | |
Maximum heater current [A] | – | 3 |
Maximum unit current [A] | 1 | 4 |
Maximum air flow [rrO/h] | 270 | |
RPM [min”] | 1800 | |
Sound pressure level at 3 m distance [dBA] | 28 | |
Transported air temperature [°C] | -25…+40 | |
Casing material | painted steel | |
Insulation | 20 mm mineral wool | |
Filter | extract | G4 |
supply | G4, F7 | |
Connected air ducts diameter [mm] | 125 | |
Weight [kg] | 47 | I 48 |
Heat recovery efficiency [96] | 75..92 | |
Heat exchanger type | rotary | |
Heat exchanger material | Aluminium | |
SEC class | A |
DESIGN AND OPERATING PRINCIPLE
The unit has the following operating principle:
stale extract air from the room flows to the unit, where it is filtered. Then
the air is moved through the rotary heat exchanger and is exhausted outside
with the exhaust fan. Clean air from outside is moved to the supply filter.
Then filtered air flows through the rotary heat exchanger and is moved to the
room with the supply fan. Heat exchange between extract air and intake air
takes place in the rotary heat exchanger. Heat recovery minimizes heat losses
and space heating expenses in cold seasons and cooling expanses in warm
seasons.
The KOMFORT Roto EC S6EK 200 unit is equipped with an electric heater for
preheating the supply air.
The unit is equipped with an additional extract spigot for connecting a
kitchen hood.
The air handling unit is equipped with quick-detachable service panels for
scheduled repair and maintenance operations. 1 – supply fan 2 – supply filter
3 – supply filter with higher level of filtering 4 – extract filter 5 –
humidity sensor (option) 6 – rotary heat exchanger 7 – control unit 8 – rotary
heat exchanger drive 9 – electric PTC heater (for models equipped with a
heater) 10 – kitchen hood 11 – Setup Mode button 12 – cable glands
A – spigot for intake air B – spigot for exhaust air C – spigot for supply air
D – spigot for extract air E – additional spigot for optional remote
connection of a kitchen hood
MOUNTING AND SET-UP
READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.
THE UNIT MUST BE MOUNTED BY A QUALIFIED EXPERT ONLY, PROPERLY TRAINED
AND HAVING THE REQUIRED TOOLS AND MATERIALS.
While mounting the unit provide enough access for maintenance or repair work.
The minimum recommended clearances between the unit and the adjoining walls
are given in the figure below.
To attain the best performance of the unit and to minimise turbulence-induced
air pressure losses, connect the straight air duct section to the spigots on
both sides of the unit while mounting.
Minimum straight air duct length:
- equal to 1 air duct diameter on the intake side
- equal to 3 air duct diameters on outlet side
If the air ducts are too short or not connected, protect the unit parts from
ingress of foreign objects. To prevent uncontrollable access to the fan, the
spigots may be covered with a protecting grille or other protecting device
with mesh width not more than 12.5 mm. The unit must be mounted on a plane
wall. Installing the unit to an uneven surface could lead to the unit’s casing
distortion and operation disturbance.
The unit is designed for wall mounting with a fixing bracket that is fastened
with four screws and dowels (not included in the delivery set). While choosing
fasteners consider the material of the mounting surface as well as the weigh
of the unit, refer to the “Technical data” section. Fasteners for unit
mounting should be selected by a qualified specialist.
HUMIDITY SENSOR MOUNTING
The humidity sensor is not included in the delivery set and can be ordered separately. The humidity sensor must be installed prior to unit mounting. Remove the service panel and fix the humidity sensor to the wall of the exhaust air duct. Connect the connector to the sensor.
DECORATIVE PANEL MOUNTING
The decorative panel must be installed using the suspension brackets (included in the delivery set). Fix the suspension brackets on the decorative panel according to the drawing.
Install the decorative panel by inserting the brackets in special holes.
SERVICE SIDE CHANGE
The design of the unit allows changing the service side.
A – supply air B – intake air C – extract air D – exhaust air E – extract air
from kitchen hood Remove the decorative panel.
Remove the service panel (fixed with 6 screws). Disconnect the ground cable
from the service panel.
Remove the rear panel of the unit (fixed with 6 screws). Disconnect the ground
cable from the rear panel.
Turn the unit around.
Install the back panel instead of the service panel and the decorative and
service panels instead of the back panel.
UNIT INSTALLATION
Attach the mounting bracket to the wall considering the wall material and the unit weight.
Install the unit on the mounting bracket. Suspend it carefully. Make sure the unit is fastened securely prior to operation.
CONNECTION TO POWER MAINS
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT. THE
UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN. THE RATED
ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID
THE WARRANTY.
- The unit is rated for connection to 1~230 V/50 (60) Hz power mains according to the wiring diagram. The connection must be made using durable, insulated and heat-resistant conductors (cables, wires). The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and installation method.
- The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the circuit in the event of overload or short-circuit. The position of the external circuit breaker must ensure free access for quick unit power-off. The trip current of the automatic circuit breaker must exceed the maximum current consumption of the unit (refer to the “Technical data” section or to the unit label). It is recommended to select the nominal current of the circuit breaker from the standard series, following the maximum current of the connected unit.
- The circuit breaker is not included in the delivery set and can be ordered separately.
ACCESS TO THE CONTROL UNIT
EXTERNAL WIRING DIAGRAM
Electric shock hazard!
Designation | Name | Contact type | Cable type | Note |
---|---|---|---|---|
SM1* | Supply air damper actuator | NO | 2 x 0. 75 mm2 | 3A, 30DC/-250 AC |
SM2 * | Extract air damper actuator | NO | 3A, 30DC/-250 AC | |
PK1 * | Contact from fire alarm panel | NC | Remove the jumper | |
CCU* | CCU control | NO | 3A, 30DC/-250 AC | |
P1* | External control panel | 4 x 0.25 mm2 | ||
Boost* | On/Off contacts of the Boost mode | NO | 2 x 0.75 mm2 | |
CO2* | Outdoor CO2 sensor | 3 x 0.25 mm2 | ||
KH1* | Kitchen hood | 5 x 0.75 mm2 |
Is not included in the delivery set.
The supply voltage U of the SM1, SM2 external dampers is selected depending on the type of dampers.
Output parameters: terminals 12-17 – 3 A, 30VDC / ~ 250VAC (“dry contact”).
The maximum cable length from external devices to the terminal block should
not exceed 100 meters. The recommended cable cross-section is shown in the
table.
TECHNICAL MAINTENANCE
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
MAKE SURE THE UNIT IS DISCONNECTED FROM POWER MAINS BEFORE REMOVING THE
PROTECTION
Maintenance operations of the unit are required 3-4 times per year. They
include general cleaning of the unit and the following operations:
1. Filter maintenance.
Dirty filters increase air resistance in the system and reduce supply air
volume. The filters require cleaning not less than 3-4 times per year. Clean
the filter with a vacuum cleaner or replace it with a new one. For new filters
contact the Seller.
To extract filters, do the following:
- Disconnect the unit from power mains.
- Remove the decorative panel.
- Remove the service hatch.
- Pull the filters to remove.
2. Heat exchanger maintenance (once per year).
Some dust may accumulate on the heat exchanger even in case of regular
maintenance of the filters. To maintain the high heat recovery efficiency,
regular cleaning is required. To clean the heat exchanger, remove it from the
unit and clean the heat exchanger by using compressed air or a vacuum cleaner.
After cleaning, reinstall the heat exchanger
into the unit.
To remove the heat exchanger, do the following:
- Disconnect the unit from power mains.
- Remove the decorative and the service panel.
- Disconnect the ground cable from the service panel.
- Disconnect the heat exchanger and then pull it to remove.
3. Fan maintenance (once per year).
Even in case of regular maintenance of the filters, some dust may accumulate
inside the fans and reduce the fan performance and supply air flow. Fans
should be cleaned selected by the service technician.
4. Supply air flow control (twice per year).
The supply duct grille may get clogged with leaves and other objects reducing
the unit performance and supply air delivery. Check the supply grille twice
per year and clean it as required.
6. Ductwork system maintenance (once in 5 years).
Even regular fulfilling of all the maintenance operations prescribed above may
not completely prevent dirt accumulation in the air ducts, which leads to air
pollution and reduces the unit capacity. Duct maintenance means regular
cleaning or replacement.
TROUBLESHOOTING
IF UNIDENTIFIED NOISES OR ODOURS SHOULD ARISE AND IN CASE OF DEFORMATION OF
ELEMENTS, VIBRATION, TERMINATION OF AIR SUPPLY/EXTRACTION OR REDUCED SYSTEM
PERFORMANCE, IMMEDIATELY DISCONNECT THE UNIT FROM POWER SUPPLY AND CONTACT THE
SELLER FOR THE VENTILATION SYSTEM DIAGNOSTICS.
DIAGNOSTICS MUST BE CARRIED OUT BY QUALIFIED SPECIALISTS.
Problem | Possible reasons | Troubleshooting |
---|
The fan(s) does (do)
not start when the unit
is on.| No power supply.| Make sure the power supply line is connected
correctly,
otherwise troubleshoot a connection error.
The motor is jammed, the impeller blades are soiled.| Turn the unit off.
Troubleshoot the motor jam and the
impeller clogging. Clean the blades.
Automatic circuit
breaker trips following
the unit turning on.| High current consumption due to short circuit in
power line.| Turn the unit off. Contact the Seller.
Low air flow.| Low set fan speed.| Set higher speed.
The filters and the fans are clogged, the heat
exchanger is clogged.| Clean or replace the filters, clean the fans, and the
heat
exchanger.
Ventilation system elements (air ducts, diffusers,
louver shutters, grilles) are clogged, damaged or
closed.| Clean or replace the ventilation system elements, such as air ducts,
diffusers, louvre shutters, grilles.
Cold supply air.| The extract filter is soiled.| Clean or replace the extract
filter.
Noise, vibration.| The impeller(s) is soiled.| Clean the impeller(s).
The fan or casing screw connection is loose.| Tighten the screw connection of
the fans or the casing
against stop.
No anti-vibration connectors on air duct pipe
flanges.| Install anti-vibration connectors.
If troubleshooting steps have failed, contact the Seller of the product.
In case of faults not described in the table, contact the Seller for further
information.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range +5…+40 ˚C and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility. We hereby declare that the
product complies with the provisions of Electromagnetic Compatibility (EMC)
Directive 2014/30/EU of the European Parliament and of the Council, Low
Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the
Council and CE-marking Council Directive 93/68/EEC. This certificate is issued
following test carried out on samples of the product referred to above. The
manufacturer hereby warrants normal operation of the unit for 24 months after
the retail sale date provided the user’s observance of the transportation,
storage, installation, and operation regulations. Should any malfunctions
occur in the course of the unit operation through the Manufacturer’s fault
during the guaranteed period of operation, the user is entitled to get all the
faults eliminated by the manufacturer by means of warranty repair at the
factory free of charge. The warranty repair includes work specific to
elimination of faults in the unit operation to ensure its intended use by the
user within the guaranteed period of operation. The faults are eliminated by
means of replacement or repair of the unit components or a specific part of
such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s
manual with the purchase date stamp, and the payment paperwork certifying the
purchase. The unit model must comply with the one stated in the user’s manual.
Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND
TROUBLE-FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION
OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE
DATE STAMP.
CERTIFICATE OF ACCEPTANCE
Unit Type | Heat recovery air handling unit |
---|---|
Model | |
Serial Number | |
Manufacture Date | |
Quality Inspector’s Stamp |
SELLER INFORMATION
Seller|
---|---
Address|
Phone Number|
E-mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s
manual. The warranty terms are
Customer’s Signature|
INSTALLATION CERTIFICATE
The | unit is installed pursuant to the requirements stated |
---|
in the present user’s manual.
Company name|
Address|
Phone Number|
Installation
Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the
applicable local and national construction, electrical and technical codes and
standards.The unit operates normally as intended by the manufacturer.
Signature:|
WARRANTY CARD
Unit Type | Heat recovery air handling unit |
---|---|
Model | |
Serial Number | |
Manufacture Date | |
Purchase Date | |
Warranty Period | |
Seller |
www.blaubergventilatoren.de
B140-1-1EN-02