DIEHL SHARKY 775 Ultrasonic Energy Meter Installation Guide
- June 9, 2024
- DIEHL
Table of Contents
- SHARKY 775 Ultrasonic Energy Meter
- General
- Installation of energy meter (fig. I)
- Temperature sensor
- Power supply
- Start-up operation
- Expansion modules
- Environmental specification
- Display
- Operation
- Display Error codes
- Disposal
- EU DECLARATION OF CONFORMITY
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Ultrasonic energy meter
Installation guide
SHARKY 775 Ultrasonic Energy Meter
General
This guide is intended for trained specialised personnel. Therefore, it does
not include basic working steps.
The seal on the energy meter must not be damaged!
A damaged seal will result in immediate invalidation of the factory warranty
and verification. The cables supplied with the meter must neither be
shortened, extended nor changed in any other way.
Legal regulations and operating instructions for the use of energy meters must
be observed!
The installation must only be carried out by a specialist energy meter
installation and electrical company. The personnel must be trained in the
installation and handling of energy meters and electrical devices as well as
the applicable guidelines.
Medium: water, as per AGFW Instruction Sheet FW510.
If water additives are used (e.g. corrosion protection), the user must make
sure that the corrosion resistance is adequate.
This product is designated (where relevant) as a pressure main-taining
component in the sense of the Pressure Equipment Direc- tive (PED) and may
only be operated as a pressure maintaining component with temperature sensors
suitable for this purpose.
This product is not intended for used as a safety device in the sense of the
Pressure Equipment Directive (PED).
The following information should be taken from the type plate of the device in question:
- The nominal diameter DN for the pipe
- The applied test pressure PT in Bar and the date
- The intended use
- The fluid group
- The mains voltage in volts
- Optional also as a separate variant for the medium Tyfocor LS (see loop 3) available.
- The medium temperature is specified as 5 … 130 °C (150 °C)
- The temperature range depends on variant and nominal size.
- The exact temperature range is shown on the type plate.
- The encapsulated variant is to be used if condensation is expected.
- The operating/ambient conditions are 5 … 55 °C; IP 54/64; 93 % rel. humidity.
- Ambient temperatures below 35 °C have a positive effect on battery lifetime.
If the flow sensor is insulated with the pipeline, the calculator must be accessible.
Detailed user guide available at https://www.diehl.com/metering/en/support-
center/download-center/
The Software IZAR@Mobile2 is used for reading out data and configura- tion and
can be downloaded from the Internet under: https://www.diehl.com/metering/en
/support-center/download-center/
Changing of communication relevant parameters can result in the loss of OMS
certification.
Transport and storage
Unpacking
Energy meters are measuring devices and must be handled with care.
To protect against damage and soiling, they should only be unpacked
immediately prior to installation.
Transport
The transport of the meter is permitted only in the original package.
When sending wireless measuring instruments / components by air, disable the
wireless (place in aircraft mode) before shipping.
Installation of energy meter (fig. I)
- Depending on the design and application (heat or cooling meter), the energy meter is installed in either the hot or cold line of the system.
- The flow sensor must be installed so that the flow direction matches the arrow direction on the sensor.
Depending on the version, the flow sensor must be installed in flow or return.
The installation position is displayed in the info loop 3.5 (see “Information
loop (3)” page 46) and, if necessary, also by means of a pictogram.
| | No pictogram (Installation position can be set on site, see 6.1 page 33)
---|---|---
- Calming sections are not necessary before and after the flow sensor.
For systems without temperature mixing, a straight DN 3 – 10 section upstream of the flow sensor is recommended.
The meter can be installed in both horizontal and vertical pipe sections,
provided air bubbles cannot collect in the meter.
The flow sensor must always be filled with liquid.
Avoid frost at the meter.
- We recommend installing the flow sensor in a tilted position.
- The minimum system pressure must be 1 bar to avoid cavitation.
- Electrical and magnetic fields might disrupt electronic components in the energy metering device. Make sure there is sufficient distance (approx. 10 cm) between the calculator and its measurement signal lines and possible sources of electromagnetic disturbance (e.g. trans- formers, electric motors, supply lines, etc.).
- If possible install the cables of the flow sensor or temperature sensor freely suspended (not bundled – aerial effect) with sufficient distance from electromagnetic interference sources.
- The measurement signal lines (temperature and flow rate) must not be routed in direct proximity to other lines, such as mains supply lines, low-voltage supply lines and data transmission cables. The minimum distance of 5 cm for low-voltage lines must be observed according to EN 1434-6.
- For medium temperatures from 90°C or for T Water < T Ambient (cooling meter application or heat meter with cooling tariff application) the cal- culator must be removed and fitted at a sufficient distance from any heat sources. A wall holder (supplied with meter) or a spacer holder (optional) is available for this purpose.
- It is recommended that shut-off valves are fitted before and after the energy meter to simplify removing the meter.
- The meter should be installed in a conveniently accessible position for service and operating personnel.
- Initial operation is to be carried out and recorded after installation.
Temperature sensor
Disconnectable temperature sensors or temperature sensors not secured with their own calibration sticker must have their own EU approval and CE label.
Handle the temperature sensor carefully!
The sensor cables are provided with coloured type plates:
- Red: Sensor in the hot line
- Blue: Sensor in the cold line
- The maximum cable length of the temperature sensors is 6 m for the PT100 and 10 m for the PT500.
- The connecting cables must not be shortened or extended.
- The free temperature sensors can be fitted so they are directly sub- merged (e.g. ball valve) or in a pocket tested for conformity for this sensor type.
- Sensors must be installed symmetrically.
- After initial operation of the meter, ensure that the temperature sen- sors are always correctly connected at the calculator.
4.1 Installation in the ball valve with adapter
(coupling set in a separate bag)
Use ball valves with installation option for temperature sensor with thread
M10 x 1.
Preparatory measures
- Close the ball valve.
- Unscrew the plug screw from the ball valve.
Installation (see fig. II)
-
Place the O-ring from the attached coupling set (type A or B) on the mounting pin.
-
Insert the O-ring with the mounting pin into the sensor hole of the ball valve (turn the mounting pin).
-
Position the O-ring in its final position using the other end of the mounting pin.
-
Fastening screws
Type A (plastic) – plug the fastening screw onto the temperature sen- sor.
Type B (brass) – insert the temperature sensor in the fastening screw and place the sensor in the mounting pin. Press in the dowel pin com- pletely and remove the mounting pin. -
Insert the temperature sensor with the securing fitting in the ball valve and manually tighten (2-3 Nm).
Power supply
5.1 Battery
A 3.6 VDC lithium battery is fitted in the standard version.
The battery must not be recharged or short-circuited.
Ambient temperatures below 35 °C have a positive effect on battery lifetime.
Used batteries must be disposed of at suitable waste collection points!
Caution: Risk of explosion if battery is replaced by an incorrect type.
5.2 Power supply unit
Power supply units of 24V AC or 230V AC can be changed or supple- mented at
any time.
It is strictly necessary to have the protective safety cover ins- talled at
all times.
Under no circumstances connect between the two phases other- wise the power
supply unit will be destroyed.
- The cable is to be fused at max. 6A and protected against tampering.
- The power supply unit notifies the meter if mains voltage is present.
- If the power supply fails, the backup battery (CR2032) provides the power supply for up to 1 year. The LCD readings (on pressing button) and the date and time are still updated, but none of the measuring functions work, incl. the flow rate measurement. Communication still functions over the optional M-Bus, RS485, RS232 modules or the opti- cal interface, but reduces the life of the backup battery. The wireless function is switched off in the event of power supply failure.
Start-up operation
Once the meter has been installed, the components (calculator, volume
measuring component and both temperature sensors) must be sealed with a
tamper-proof seal and the meter started up by a specialist com- pany approved
according to the legislation.
Check the display for a plausible indication of flow rate and tempe- ratures.
User guide for further Information is available at
https://www.diehl.com/metering/en/support-center/download-center/
6.1 Flow/return setting (optional ex works)
Optionally, the installation position of the meter can be set in-situ in
loop 3 (“3.5” page 46). Consequently installation in the inlet (flow) or
outlet (return) is possible.
This setting must be made prior to initial operation of the meter.
As supplied, the outlet (return) is pre-set and is shown as follows in the
display.
Setting and number of possi- ble changes.
To changeover, switch to the “OutLEt” window in loop 3 (see 9. Operation).
Pressing and holding the button for > 6 s changes the display/setting to
“InLEt”.
This setting can be changed a total of 8 times by pressing the button.
The display changes during the 6 s.
This does not influence functioning.
Sequence during changing
Button pressed <3s Button pressed >3s
If the button is pressed and then held for > 6 s, the meter performs the
command shown in the display.
In each change, the framed number in the display reduced by 1.
After 8 changes, it is no longer possible to change the installation position.
The possibility of changing lapses either immediately upon detection of water,
or after three hours’ operation without error detection (pre-set ex works).
The following indication appears in the display (example):
The changes indication dis- appears.![DIEHL SHARKY 775 Ultrasonic Energy Meter
- fig 8](https://manuals.plus/wp-content/uploads/2023/01/DIEHL-SHARKY-775 -Ultrasonic-Energy-Meter-fig-8.png)
When changing the installation position, the sensors must be matched to the actual installation (see chapter 4).
Expansion modules
The energy meter has two slots for expansion modules.
They can be mixed, but two pulse modules of the same kind must not be
installed.
The analogue module occupies both positions.
These modules have no effect on consumption recording and can be fitted
retrospectively without damaging the verification mark.
The relevant ESD regulations (electrostatic discharge) must be observed.
No responsibility is accepted for damage (especially to the electronics),
resulting from non-observation of the rules.
7.1 Module installation (fig. III)
- Open the calculator by folding down the side catches.
- Lock the module into the appropriate slot and carefully connect the pre-formed ribbon cable at both ends.
- Close the lid and check the meter for correct operation by pressing the push button. Apply the tamper-evident seal of the housing lid if the meter functions correctly.
7.2 Communication
Communication modules must be secured so that opening of meters is only
possible by destroying the securing points.
The calculator supports three communications channels.
Two additional communication modules can be used in wireless operation.
Both communication modules have their own primary address. Both ports have a
common secondary address, which is set to the serial number ex works.
The protocols may be different for all three communication channels and are
pre-set ex works. The telegrams can be defined for each customer using the
IZAR@MOBILE 2 software.
7.2.1 Communication via radio
The integrated radio module is an interface for communication with Diehl
Metering radio receivers.
Unidirectional communication has the following specification:
-
The module transmits every 8 … 256 s (send period 0.1 % of duty cycle (min. 8s); variable, depending on protocol length and programming)
-
The communication always transfers the currently measured data
-
Transmission frequencies:
– 434 MHz, transmission power (EN 300 220-2 V3.2.1): 10mW e.r.p.
– 868 MHz, transmission power (EN 300 220-2 V3.2.1): 25mW e.r.p. -
Various Diehl Metering receivers are available for receiving the proto- col (e.g. Bluetooth, GPRS, LAN, …)
-
The protocol corresponds to OMS Profile A or Profile B and is encrypted.
-
Reading modes: Walk-By, Drive-By, Fixed-Network
-
For problematic radio installations (shield) the external wireless module set can also be used.
7.2.2 M-Bus Communication module
The M-Bus communication module is a serial interface for communication with
external devices (M-Bus control centres), e.g. IZAR CENTER. A num- ber of
meters can be connected to a control centre. The module contains a 2-pole
terminal strip with terminals marked 24, 25.
- The connection is not polarity-sensitive and is electrically isolated
- M-Bus protocol stan- dardised according to EN 1434;
- 300 or 2400 baud (auto baud detect)
- Connection option 2 x 2.5 mm²;
- Power consumption: One M-Bus load
7.2.3 RS232 Communication module
The RS232 communication module is a serial interface for communicating with
external devices, e.g. PC; 300 or 2400 bauds.
The module contains a 3-pole terminal strip with terminals marked 62 (Dat), 63
(Req) and 64 (GND).
A special adapter cable is required for connection (order no. 087H0121).
The coloured wires are to be connected as shown:
62 = brown
63 = white
64 = green
Module RS232 is only to be installed on port 2 (right side).
7.2.4 RS485 Communication module
The RS485 communication module is a serial interface for communication with
external devices, e.g. PC; 2400 bauds.
The module contains a 4-pole terminal strip with terminals marked D+, D-, +12
V and GND. The module requires an external supply voltage of 12 VDC ±5
V.
7.2.5 Communication module Modbus RTU
- Polarity independent: Con- nections 60 and 61
- External power supply: 12-24 V AC/DC
- Energy consumption: max. 150 mW
- Connection 90 (not inver- ted, +)
- Connection 91 (inverted,-)
- Communications protocol: Modbus RTU
- Channel EIA-485 (electri- cally isolated)
- Flexible data format: Standard 9600 bits/s, 8N1, Modbus Slave ID-1
7.2.6 Communication module LonWorks
- Polarity independent: Con- nections 60 and 61
- External power supply: 12-24 V AC/DC
- Energy consumption: max. 150 mW
- Polarity independent: Con- nections 96 (A) and 97 (B)
- Channel TP/FT-10
- Baud rate: 78 kbit/s
- Data format: Differential Manchester encoding
7.3 Pulse input function module
Module for two additional meters Pulse input 1 is marked as “I1- “, input 2
with “I2 – “.
Pulse inputs can be programmed (IZAR@MOBILE 2) with a value: 1, 2.5, 10, 25,
100, 250, 1000, 2500 l per pulse.
- Pulse transmitter must be electrically isolated, e.g. Reed contact
- Possible units are all the energy units available in the meter, the volume unit m³ or no unit.
input frequency | ≤ 8 Hz |
---|---|
Min. pulse duration | 10 ms |
input resistance | 2.2 MΩ |
Terminal voltage | 3 VDC |
cable length | up to 10m |
Data is accumulated separa- tely in registers; can be read in the display as IN1 and IN2 and can be transferred via the communication facility.
7.4 Pulse output function module
The module is equipped with 2 pulse outputs, which can be freely pro-grammed
using the IZAR@MOBILE 2 software. The outputs are indicated as “O1 – ” and “O2
– ” on the terminal strip and as Out1 and Out2 in the display.
- External supply: Vcc = 3-30 VDC
- Output current ≤ 20mA with a residual voltage of ≤ 0.5V
- Open collector (drain)
- Electrically insulated
- Output 1: f ≤ 4Hz Pulse duration: 125 ms ± 10 % Pulse pause: ≥ 125 ms – 10 %
- Output 2: f ≤ 200 Hz Pulse duration/pulse pause ~1:1
- Pulse width: ≥ 5 ms
- The volume pulse weighting can be freely programmed
- Standard: last digit in the display
7.5 Combined function module (IN/OUT)
The combined module has 2 inputs and 1 output.
See chapter 7.3 for the specific characteristics on the pulse input.
The pulse output is speci- fied as pulse output 1 under point 7.4, not however
galva- nically isolated.
7.6 Analogue output function module
The module is equipped with 2 passive analogue outputs, which can be freely
programmed using the IZAR@MOBILE 2 software. On the terminal strip, the
electrically isolated outputs “1” and “2” are marked and the polarity is
indicated (“+” and “-“).
- Passive, external power supply: 10…30 VDC
- Current loop 4 … 20 mA whereby 4 mA = 0 value; 20 mA = programmed max. value
- Overload up to 20.5 mA, then fault current
- Errors are output with 3.5 mA or 22.6 mA (pro- grammable)
- Output values: power, flow, temperatures
The module is connected to the meter electronics by a pre-fabri-cated ribbon cable. The separate plug on the module slot 2 is necessary for the proper function of the analogue outputs.
7.7 Function NB-IoT module
- Green LED
- Red LED
- Battery Power Connector
- SIM Card Holder
- Push Button
- Antenna Connector (MCX)
- NFC Antenna (around whole board)
Mechanics
Dimensions (w x h x d) | 43 x 37 x 9 mm |
---|---|
External antenna connector | MCX (female) |
SIM card | Size Nano |
Electrical connections
Mains supply | – |
---|---|
24 V supply | – |
Battery supply | externally mounted (DIEHL Mete- ring D-cell: 311713451) |
Battery life time | externally mounted (DIEHL Mete- ring D-cell: 311713451) |
Nominal voltage PSU | – |
Nominal voltage Battery | 3,0 VDC |
Power consumption (max.) | 400 mA |
Power consumption (StandBy) | 6 μA |
not available separately, only in combination with the NB-IoT module
Environmental specification
Operating temperature | +5 °C to +55 °C |
---|---|
Operating humidity | 0 – 93 % RH, no condensation |
Operating altitude (max.) | 2000 m |
Pollution degree | Degree 1 |
Usage environment | Indoors |
Storage temperature | -20 °C to +60 °C (Module) |
Cellular network
Band | 20, 8, 3 |
---|---|
3GPP | Release 14 (NB2) |
Transmit power (max.) | 23,0 dBm |
Receiver sensitivity | -135 dBm |
Meter and battery module
7.7.1 Activation
Upon delivery, NB-IoT module has a standard configuration. To change the
configuration, please download the OTC Application (One-Touch com-missioning)
for Android, available in Google Play store. The OTC connects to the module
via NFC.
Make sure to locate the NFC antenna on your phone. When you scan or write new configurations to the module, you should place the phone’s NFC antenna as close as possible to the NFC antenna of the module. The NFC is reachable from back side of the meter or from top when lid is removed.
By default, the product is set to passive mode, which means no messages will be transmitted from the device. There are two ways to activate the product:
- Press and hold down the push button (5) for at least 5 seconds until the green LED (1) lights up.
- Via the OTC mobile application. Go to the Apply tab, set the Power mode to “Active”, push “Apply” and place the phone on the back side of the meter, next to the module. Make sure to hold the phone still until the phone vibrates.
Upon start-up, the module will attempt to connect to the mobile network.
The phase is indicated by short flashes on the green LED. After success- fully
connecting to the mobile network, the green LED will light up for 8 seconds,
as indicated by the figure below.
7.8 Test output
The internally located test output is intended for testing laboratories.
The manufacturer supplies two special cables:
- Volume testing pulses
- Energy testing pulses
Please refer to the inspection and testing manual for further specifications (pulse weighting, pulse duration/pause, pulse frequency).
Ensure that the temperature sensors (measurement resistances) remain in contact without interruption during energy verification.
Display
The data generated by the calculator can be viewed in several displays.
These displays contain the assigned system information (e.g. energy
quantities, water volumes, operating days, water quantities, actual tem-
peratures, maximum values) and can be accessed by calling the displays in the
pre-defined sequence / loop. The energy meter has up to 6 diffe- rent display
sequences / loops.
Main loop, due date loop, information loop, pulse input loop, tariff loop.
The month loop comprises up to seven readings alternatingly displayed for 2 s
– 4 s each. For quick visual identification, the loops are labelled 1 to 6 in
the display. As standard, the main loop contains the actual data, e.g.
energy, volume, flow and temperatures. The verified register is marked with a
padlock icon.
Main loop (1)
Attention: Overview applies to heat meters and cooling meters only
S equence | Window 1 |
---|---|
1.1 | Accumulated energy |
1.2 | Volume |
1.4 | Flow |
1.5 | Power |
1.6 | Flow/return flow temperature |
1.7 | Differential temperature |
1.8 | Operating days |
1.9 | Error status |
1.10 | Display test |
Due date loop (2)
Sequence | Window 1 | Window 2 | Window 3 |
---|---|---|---|
2.1 | Due date 1 date | Due date 1 energy | “Accd 1” |
2.2 | “Accd 1” | Date of future due date 1 | |
2.3 | Due date 1 previous year date | Due date 1 previous year energy | “Accd 1L” |
2.4 | Due date 2 date | Due date 2 energy | “Accd 2A” |
2.5 | “Accd 2” | Date of future due date 2 | |
2.6 | Due date 2 previous year date | Due date 2 previous year energy | “Accd 2L” |
2.7 | Due date 1 | Pulse input 1 | Volume pulse input 1 |
2.8 | Due date 1 previous year | Pulse input 1 | Volume pulse input 1 |
2.9 | Due date 2 | Pulse input 1 | Volume pulse input 1 |
2.10 | Due date 2 previous year | Pulse input 1 | Volume pulse input 1 |
2.11 | Due date 1 | Pulse input 2 | Volume pulse input 2 |
2.12 | Due date 1 previous year | Pulse input 2 | Volume pulse input 2 |
2.13 | Due date 2 | Pulse input 2 | Volume pulse input 2 |
2.14 | Due date 2 previous year | Pulse input 2 | Volume pulse input 2 |
Information loop (3)
Sequence | Window 1 | Window 2 |
---|---|---|
3.1 | Actual date | Time |
3.2 | “Sec_Adr” | Secondary address |
3.3 | “Pri_Adr 1” | Primary address 1 |
3.4 | “Pri_Adr 2” | Primary address 2 |
3.5 | “Inlet” / “Outlet” * (installation position) | depending on the setting |
(see 6.1 page 33)
3.6 [A]| “Port 1”| 0 (no. of the plugged in module at port 1)
3.7 [A]| “Port 2”| 1 (no. of the plugged in module at port 2)
3.8| “UHF ON” (status of integrated radio)
3.9| Software version| Check sum
[A]| Index| [A]| Index
---|---|---|---
No module| 0| Analog out| 6
MBus| 1| Pulse in out| 7
RS232| 2| Test cable energy| 9
RS485| 3| Test cable volume| 10
Pulse in| 4| External radio| 18
Pulse out| 5| |
Pulse loop (4)
Sequence | Window 1 | Window 2 | Window 3 |
---|---|---|---|
4.1 | Pulse input 1 | Cumulative value pulse |
input 1
| Pulse weight
4.2| Pulse input 2| Cumulative value pulse input 2| Pulse weight
4.3| Pulse output 1| Pulse weighting pulse output 1
4.4| Pulse output 2| Pulse weighting pulse output 2
Tariff loop (5) 1
Month loop (6)
Sequence | Window 1 | Window 2 | Window 3 | Window 4 |
---|---|---|---|---|
6.1 | “LOG” | Date-1 | Energy | Max. flow |
6.2 | “LOG” | Date-2 | Energy | Max. flow |
: | : | : | : | : |
6.24 | “LOG” | Date-24 | Energy | Max. flow |
* Example | 1Only for heat meters with activated cooling tariff |
Operation
Use the push button to page through the individual displays. When doing so a differentiation is made between short and long button presses. With a short button press (<3 seconds) you get to the next display within a loop; with a long button press (>3 seconds) you get to the next display loop. The “Energy” window (sequence 1.1) of the main loop is the basic display. If the button is not pressed for approx.4 minutes, the meter automatically switches off the display to save power (exception: an error exists). If you press the button again, the meter returns to the basic display.
Display Error codes
If an error occurs, the error code is displayed in the main loop. All win-
dows, however, can still be accessed by pressing the button. If the button is
not pressed for approx. 4 min, the error code is automatically displayed
again.
The error message disappears automatically as soon as the source of the error
is corrected. All errors that exist for longer than 6 min, are saved in the
error memory.
Error code | Description |
---|---|
C – 1 | Basic parameter error in flash or RAM – Meter must be replaced |
E 1 | Temperature range outside [-19.9 °C. 199.9 °C] e.g. sensor short-circuit, |
sensor break
E 3| Forward and return sensor reversed
E 4| Hardware error US measurement, e.g. transducer or control defective or
short circuit
E 5| Communication not possible (too frequent read-out)
E – 6| Flow direction of flow meter incorrect
E 7| No plausible ultrasound receiver signal, e.g. air in the measuring path
E 8| No primary power supply (only with power supply unit); supply via backup
battery
E 9| Battery nearly discharged, design lifetime reached
E A| Leak: Pipe break detection
E b| Leak: Energy meter leak detection
E C| Leak: Leak pulse input 1
E d| Leak: Leak pulse input 2
optional ** application dependent
Disposal
The transposed European Directives on waste batteries and waste electri-cal
and electronic equipment supervise the actions necessary to limit the negative
impact of the product end of life.
This product is subject to special collection and disposal. It should be
deposited at an appropriate facility to enable recovery and recycling.
For further details about recycling this product, please contact your Diehl
Metering agency.
Declaration of Conformity for devices according to MID
See from page 97 onwards.
Further information as well as the actual declaration of conformity are
available at: https://www.diehl.com/metering/en/support-center/download-
center/
EU DECLARATION OF CONFORMITY
Device Type
Type | Technology | No of the EU type examination certificate |
---|---|---|
775 | Ultrasonic Thermal Energy Meter | DE-10-MI004-PTB013, PTB,Berlin NB 0102 |
SE-EMCD-2200519 Ed.1, Intertek Semko AB, Kista, NB 0413
This declaration of conformity is issued under the sole responsibility of the manufacturer. The object of the declaration described above is in conformity with the relevant Union harmonisation legislation, insofar as it is applied:
2011/65/EU (OJ L 174, 1.7.2011) | RoHS Directive |
---|---|
2014/30/EU (OJ L 96, 29.3.2014) | Electromagnetic Compatibility Directive |
2014/32/EU (OJ L 96, 29.3.2014) | Measuring Instruments Directive |
2014/35/EU (OJ L 96, 29.3.2014) | Low Voltage Directive |
2014/53/EU (OJ L 153, 22.5.2014) | Radio Equipment Directive |
2014/68/EU (OJ L 189, 27.6.2014) category I | Pressure Equipment Directive |
In conformity with the following relevant harmonised standards or normative documents or other technical specifications:
EN IEC 63000:2018
EN 55032:2015/A11:2020
EN 1434-1:2007
EN 1434-2:2007/AC:2007
EN 1434-3:2007
EN 1434-4:2007/AC:2007
EN 1434-5:2007
OIML R75-1:2002| OIML R75-2:2002
EN 62479:2010
EN 62368-1:2014/AC:2015
EN 301 489-1 v2.2.3
EN 301 489-3 v2.2.0
EN 301489-52 V1.1.2
EN 300 220-1 v3.1.1
EN 300 220-2 v3.1.1| EN 301 908-1 v13.1.1
EN 301 908-13 v13.1.1
EN 1092-3:2003
EN 1982:2017
EN 12266-1:2012
EN 12516-2:2014
AD2000:2018 A4 , B0, B5, B8,
AD W3/2, W6/2
---|---|---
Name and address of the manufacturer| The notified body LNE n° 0071 has
carried out the module D certification of quality assurance under number:
---|---
DIEHL METERING| LNE-36769
The contact address marked on the product can be one of the site listed in the
module D certificate.
Nürnberg, 2022-08-08
Dr. Christof Bosbach
President of the Division Board
Diehl Metering Reiner Edel
Member of the Division Board
Finance & Administration EU DoC_775_REV5 – 08/2022
EU DECLARATION OF CONFORMITY
Device Type
Type | Technology | No of the EU type examination certificate |
---|---|---|
775 | Ultrasonic Thermal Energy Meter | SE-EMCD-2200519 Ed.1, |
Intertek Semko AB, Kista, NB 0413
This declaration of conformity is issued under the sole responsibility of the
manufacturer. The object of the declaration described
above is in conformity with the relevant Union harmonisation legislation,
insofar as it is applied:
2011/65/EU (OJ L 174, 1.7.2011) | RoHS Directive |
---|---|
2014/30/EU (OJ L 96, 29.3.2014) | Electromagnetic Compatibility Directive |
2014/35/EU (OJ L 96, 29.3.2014) | Low Voltage Directive |
2014/53/EU (OJ L 153, 22.5.2014) | Radio Equipment Directive |
2014/68/EU (OJ L 189, 27.6.2014) category I | Pressure Equipment Directive |
In conformity with the following relevant harmonised standards or normative documents or other technical specifications:
EN 1434-1:2015+A1:2018
EN 1434-2:2015+A1:2018
EN 1434-3:2015+A1:2018
EN 1434-4:2015+A1:2018
EN 1434-5:2015+A1:2019
EN 55032:2015/A11:2020
EN 62479:2010| EN 301 489-1 v2.2.3
EN 301 489-3 v2.2.0
EN 301 489-52 V1.1.2
EN 300 220-1 v3.1.1
EN 300 220-2 v3.1.1
EN 301 908-1 v13.1.1
EN 301 908-13 v13.1.1| EN 62368-1:2014/AC:2015
EN 1092-3:2003
EN 1982:2017
EN 12266-1:2012
EN 12516-2:2014
AD 2000:2018 A4 , B0, B5, B8,
AD W3/2, W6/2
EN IEC 63000:2018
---|---|---
Name and address of the manufacturer| DIEHL METERING
---|---
Nürnberg, 2022-08-16
Dr. Christof Bosbach
President of the Division Board
Diehl Metering Reiner Edel
Member of the Division Board
Finance & Administration EU DoC_775_noMID_REV4 – 08/2022
Technical changes reserved
Mat.-Nr. 3093716 • 29/9/2022
Diehl Metering GmbH
Industriestrasse 13
91522 Ansbach
Phone: +49 981 1806-0
Fax: +49 981 1806-615
metering-germany-info@diehl.comhttps://www.diehl.com/metering
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>