EPEVER LS-E-EU Series-5A-30A PWM Charge Controller User Manual

June 9, 2024
EPEVER

EPEVER LS E EU Series 5A 30A PWM Charge Controller LS E EU Series-5A 30A PWM Charge Controller User Manual

LS-E-EU Series-5A-30A PWM Charge Controller

Thank you for selecting the LandStar E/EU series solar charge controller. Please read this manual carefully before using the product and pay attention to the safety information.
Do not install this product in humid, salt spray, corrosion, greasy, flammable, explosive, dust accumulative, or other severe environments.
Solar Charge Controller

Safety Information

  • Read all the instructions in the manual before installation.
  • DO NOT disassemble or attempt to repair the controller.
  • Install an external fast-acting fuse or breaker as required.
  • Disconnect the solar module and fast-acting fuses/breakers near the batterybefore installing or moving the controller.
  • Power connections must remain tight to avoid excessive heating from a loose connection.
  • Only charge batteries that comply with the controller’s parameters.
  • The battery connection may be a single battery or a bank of batteries.
  • Risk of electric shock! The PV and load can produce high voltages when thecontroller is working.

Overview

The LandStar E/EU series controller is a PWM charge controller that adopts the most advanced digital technique. It’s an easy operation and cost-efficient controller featured as:

  • 3-Stage intelligent PWM charging: Bulk, Boost/Equalize, and Float

  • Support 3 charging options: Sealed, Gel, and Flooded

  • Battery status LED indicator indicates battery situation

  • Battery temperature compensation function

  • With humanized settings, the operation is more comfortable and convenient

  • The USB provides a power supply that can charge electronic equipment(LS
    EU series only)

  • Battery type and load output can be set via the button

  • Extensive Electronic protection

Product Features

EPEVER LS E EU Series 5A 30A PWM Charge Controller

1 PV Terminals 6 Load Switch Button
2 Battery Terminals 7 Battery status LED indicator
3 Load Terminals 8 Load status LED indicator
4 USB output interface
(LS EU series only) 9 Charging status LED indicator
5 Mounting Hole Φ4.5

Wiring

Connect the system in the order of ❶battery load PV array following Figure 2-2,” Schematic Wiring Diagram,” and disconnect the system in the reverse order❸❷❶.
NOTE: Do not connect the circuit breaker or fast-acting fuse while wiring the controller. Ensure that the leads of “+” and “-” poles are connected correctly.
NOTE: A fast-acting fuse whose current is 1.25 to 2 times the controller’s rated current must be installed on the battery side with a distance from the battery not greater than 150 mm.
WARNING: The controller has no PV reverse connection protection; please connect it correctly.

EPEVER LS E EU Series 5A 30A PWM Charge Controller

LED Indicators

  1. Charging and load status indicator
    Indicator| Color| Status| Instruction
    ---|---|---|---
    Charging status LED indicator| Green| On Solid| In Charging
    OFF| No Charging
    Fast Flashing| Battery Over
    Voltage
    Load status LED indicator| Green| On Solid| Load ON
    OFF| Load OFF
    Slowly Flashing| Overload
    Fast Flashing| Load short circuit
  2. Battery status indicator
    LED1| LED2| LED3| LED4| Battery Status
    ---|---|---|---|---
    Slowly Flashing| X| X| X| Under voltage
    Fast Flashing| X| X| X| Over-discharge
    | Battery LED indicator status during voltage is up
    0| | 0| X| X| 12.8V< Ubat<13.4V
    0| | 0| 0| X| 13.4V< Ubat<14.1V
    0| | 0| 0| 0| 14.1V < Ubat
    | Battery LED indicator status during voltage is down
    0| | 0| 0| X| 12.8V<Ubat<13.4V
    0| | 0| X| X| 12.4V<Ubat<12.8V
    0| | X| X| X| Ubat<12.4V

NOTE:
① The above voltage values are measured in the 12V system at 25℃; please double the values in the 24V system.
② “○” states LED indicator on; “×” states LED indicator off.

Operating

  1. Load ON/OFF Setting Press the button to control the load output when the controller is powered on.
  2. Battery Type Setting

Operation:
Step 1: Enter the setting mode by pressing the button for 5s until the battery status LEDs are flashing.
Step 2: Select the desired mode by pressing the button.
Step 3: The mode is saved automatically without any operation for 5S, and the LED stops flashing. Battery Type Indicator shows as below:

LED1 LED2 LED3 Battery type
0 X X Sealed(Default)
0 0 X Gel
0 0 0 Flooded

NOTE: “○” states LED indicator on “×” states LED indicator off
Battery Voltage Control Parameters Below parameters are measured in the 12V system at 25 ºC; please double the values in the 24V system

Battery Type Sealed Gel Flooded
Over Voltage Disconnect Voltage 16.0V 16.0V 16.0V
Charging Limit Voltage 15.0V 15.0V 15.0V
Over Voltage Reconnect Voltage 15.0V 15.0V 15.0V
Equalize Charging Voltage 14.6V —— 14.8V
Boost Charging Voltage 14.4V 14.2V 14.6V
Float Charging Voltage 13.8V 13.8V 13.8V
Boost Reconnect Charging Voltage 13.2V 13.2V 13.2V
Low Voltage Reconnect Voltage 12.6V 12.6V 12.6V
Under Voltage Warning Reconnect Voltage 12.2V 12.2V 12.2V
Under Voltage Warning Voltage 12.0V 12.0V 12.0V
Low Voltage Disconnect Voltage 11.1V 11.1V 11.1V
Discharging Limit Voltage 10.6V 10.6V 10.6V
Equalize Duration 120 min. —— 120 min.
Boost Duration 120 min. 120 min. 120 min.

Protection

  • Battery Over Voltage Protection
    When the battery voltage reaches the Over Voltage Disconnect Voltage(OVD), the controller stops charging the battery to protect the battery from being overcharged.

  • Battery Over Discharge Protection
    When the battery voltage reaches the Low Voltage Disconnect Voltage(LVD), the controller stops discharging the battery to protect the battery from being over-discharged.

  • Overload Protection
    The load is switched off after a delay when the load current exceeds 1.25 times the rated current. The user must reduce the load appliance, press the button, or restart the controller.

  • Load Short Circuit Protection
    The load is switched off when the load short circuit (≥3 times the rated current) happens. The user must clear the short circuit faults, press the button, or restart the controller.

  • High Voltage Transients Protection
    The controller is protected against small high voltage transients. In lightning-prone areas, an external lightning arrester is recommended.

Troubleshooting

Faults Possible reasons Troubleshooting

The charging LED turns off during the daytime when sunshine falls on PV modules properly.| PV array disconnection| Confirm that PV and battery wire connections are correct and tight.
No LED indicator| Battery voltage may be less than 8V| Measure battery voltage with the multi-meter. Min.8V can start up the controller.
Charging LED fast flashes.| Battery over voltage| Check if the battery voltage is higher than the OVD, and disconnect the PV.
LED1 fast flashes.| Battery over-discharged| The load will recover when the battery voltage is restored to or above the LVR (low voltage reconnect voltage).
Load LED flashesslowly.| Overload*| 0 Please reduce the number of electric equipment.
C) Press the button or restart the controller.
Load LED fastflashes.| Load short circuit| (i) Check carefully loads connection, clear the fault.
® Press the button or restart the controller.

  • When the load current exceeds 1.25 times, 1.5 times, and 2 times the rated value, the controller can automatically turn off loads after 60s, 5s, and 1s, respectively.

Disclaimer

This warranty does not apply under the following conditions:

  • Damage from improper use or use in an unsuitable environment.
  • PV or load current, voltage, or power exceeds the controller’s rated value.
  • User disassembly or attempted to repair the controller without permission.
  • The controller is damaged due to natural elements such as lighting.
  • The controller is damaged during transportation and shipment.

Technical Specifications

Item| LS0512E| I LS1012E| LS1024E| I LS2024E| LS0512EU| I LS1012EU| LS1024EU| I LS2024EU| I LS3024EU
---|---|---|---|---|---|---|---|---|---
Nominal system voltage| 12VDC| 12/24VDC Auto| 12VDC| 12/24VDC Auto
Rated charge current| 5A| 10A| 20A| 5A| 10A| 20A| 30A
Rateddischarge current| 5A| 10A| 20A| 5A| 10A| 20A| 30A
Battery input voltage range| 8V – -16V| 8V- 32V| 8V – -16V| 8V – -32V
Max. PV open circuit voltage| 30V| 50V| 30V| 50V
Self-consumption| 12V55mA; 24V57mA
Charge Circuit Voltage Drop| 50.21V| 50.13V
Discharge Circuit Voltage Drop| 50.12V| 50.17V
USB input interface| —| 5VDC/1.2A| I 5VDC/2A
Temperature compensation coefficient| -5mV/C/2V
Environment temperature| -35-C — +50`C
Humidity| 595°/0,(N.C.)
Enclosure| IP30| IP20
Grounding| Common Positive
Dimension(L x W x H)| 92.8×65
x20.2mm| 101.2×67 x21.8mm| 101.2×67
x21.8mm| 128×85.6
x34.8mm| 109.7×65.5
x20.8mm| 120.3×67
x21.8mm| 120.3×67 x21.8mm| 148×85.6
x34.8mm| 148×106.8 X43.7mm
Mounting size| 84.4mm| 92.7mm| 92.7mm| 118mm| 100.9mm| 111.5mm| 138mm
Mounting hole size| 04.5
Terminals| 14AWG/2.5mm=| 12AWG/4mm=| 12AWG/4mm=| 1OAWG/6mm=| 14AWG/2.5m m=| 12AWG/4mm=| 12AWG/4mm=| 1OAWG/6mm=| 8AWG/10mm=
Net weight| 0.07kg| 0.08kg| 0.08kg| 0.15kg| 0.09kg| 0.10kg| 0.10kg| 0.18kg| 0.29kg

Any changes without prior notice! Version number: V4.2
HUIZHOU EPEVER TECHNOLOGY CO., LTD.
Tel: +86-752-3889706
Website:www.epever.com