EPEVER SDM120 Series 45A Single Phase Electric Meter User Manual
- May 15, 2024
- EPEVER
Table of Contents
EPEVER SDM120 Series 45A Single Phase Electric Meter
- Measures kWh, kVarh, kW, kVar, kVA, PF, Hz, dmd, V, A, etc.
- Bi-directional measurement IMP & EXP
- Two pulse outputs
- RS485 Modbus RTU / Mbus
- Din rail mounting 18mm
- 45A direct connect / 5A or 100mV CT Connect
- Better than Class 1 accuracy
Introduction
This document provides operating, maintenance and installation instructions of SD120 series. The unit measures and displays the characteristics of single phase two wires application. It provides voltage, current, power, frequency, power factor and energy information. SDM120 series has both direct connect types and 5A or 100mV CT operated types. The direct connect type can work with direct load 45A. Two Pulse outputs and 1 remote communication port are provided.
This series covers 7 models:
Model | Current Input | Communication | MID | |
---|---|---|---|---|
SDM120M | Direct connect 45A | RS485 Modbus | • | |
SDM120MB | Direct connect 45A | M-Bus EN13757-3 | • | |
SDM120P | Direct connect 45A | —– | • | |
SDM120CTM | 1A or 5A CT operated | RS485 Modbus | • | |
SDM120CTMB | 1A or 5A CT operated | M-Bus EN13757-3 | • | |
SDM120CTP | 1A or 5ACT operated | —– | • | |
SDM120CT-MV | 100mV CT operated | RS485 Modbus |
Specifications
General Specification
- Voltage AC (Un) 230V
- Voltage Range 176-276V AC
- Current Input 0.25~5(45)A (SDM120 45A) 0.25-5(6)A (SDM120 CT)
- Power consumption <2W/10VA
- Frequency 50/60Hz (50Hz only for MID version)
- AC voltage withstand 4KV for 1 minute
- Impulse voltage withstand 6KV-1.2uS wavform
- Overcurrent withstand 301max for 0.01s (SDM120 45A) 201max for 0.01s (SDM120CT)
- Pulse output rate 1000imp/kWh (default) 1000/100/10/1 imp/kWh/kVarh (configurable)
- Display LCD with white backlit
- Max. Reading 99999.9kWh (SDM120 45A) 999999 kWh (SDM120 CT)
Accuracy
-
Voltage 0.5% of range maximum
-
Current 0.5% of nominal
-
Frequency 0.2% of mid-frequency
-
Power factor 1% of Unity
-
Active power 1% of range maximum
-
Reactive power 1% of range maximum
-
Apparent power 1% of range maximum
-
Active energy Class 1 IEC62053-21
Class B EN50470-3 (MID product only) -
Reactive energy 1% of range maximum
Environment
Operating temperature | -25℃ to +55℃ |
---|---|
Storage and transportation temperature | -40℃ to +70℃ |
Reference temperature | 23℃±2℃ |
Relative humidity | 0 to 95%, non-condensing |
Altitudeup to 2000m
Warm up time
| 3s
Mechanical environment| M1
Electromagnetic environment| E2
Degree of pollution| 2
Mechanics
- Din rail dimensions 18x119x62 (WxHxD) DIN 43880
- Mounting DIN rail 35mm
- Sealing IP51 (indoor)
- Material self-extinguishingUL94V-0
Display
Initialization Display
When it is powered on, the meter will initialize and do self-checking.
Full screen
It will last for 3 seconds.
Software version
It will last for 3 seconds.
Ct1 (SDM120CT* only ) Primary current 1A-9999A Default: 5
Total active energy(kWh)
After the self-checking program, the meter screen will display the total active energy (kWh)
Note : For the MID version of SDM120CTM, SDM120CTMB and SDM120CTP, the CT ratio can be set only once. Before you set the CT ratio, please check the ratio of the CT connected to the meter. For example, if the CT is 100/5A, please set CT1 to be 100.
Scroll Display by button
There is a button on the front of the meter. After initialization and self-
checking program , the meter display the measured values . The default page is
total kWh. If the user wants to check other information, he needs to press the
scroll button on the front panel.
| Click the button, the LCD display will scroll the measurements.
---|---
Keep pressing the button for 3 seconds, the meter will enter set-up mode.
Total active energy(kWh)
Display format:0000.00→9999.99 →10000.0→99999.9→0000.00
Import active energy(kWh) Display format:0000.00→9999.99
→10000.0→99999.9→0000.00
Export active energy(kWh) Display format:0000.00→9999.99
→10000.0→99999.9→0000.00
Voltage (V)
Current (A)
Active power (W)
Frequency (F)
Power factor (PF)
Modbus Address or Primary address Default: 001
Baudrate Default : 2400bps
Parity
None/Even/Odd are optional Default: none
CT 1(SDM120CT* only )
Primary current 1A-9999A Default: 5
Note: For the MID version of SDM120CTM, SDM120CTMB and SDM120CTP, the CT ratio can be set only once.
CT 2(SDM120CT* only )
Secondary current 1A or 5A ,Default: 5
For SDM120CT-MV,CT2 is fixed with 100mV
M-Bus secondary address High
(M-Bus version only )
M-Bus secondary address Low
(M-Bus version only )
Software version In kind prevail
The display of each model:
Communication
Pulse Output
The meter is equipped with 2 pulse outputs, which are fully isolated from the
inside circuit. That generates pulses in proportion to the measured energy.
The pulse outputs are polarity dependent , passive transistor output requiring
an external voltage source for correct operation. For this external voltage
source, the voltage shall be 5-27V DC, and the maximum input current shall be
27mA DC.
ATTENTION :Pule output must be fed as shown in the wiring diagram
below.Scrupulousil respect polarities and the connection mode. Opto-coupler
with potential-free SPST-NO Contact.
Contact range:5~27VDC Max. current
Input:27mA DC
Pulse Output 1 ( SDM120M/ MB/CTM/CT-MV/CTM only)
Pulse output 1 is configurable. The pulse output 1 can be set to generate
pulses to represent total / import/ export kWh or kVarh. The pulse constant
can be set to generate 1 pulse per: 0.001 ( default) / 0.01 /0.1 /1kWh /kVarh.
Pulse width: 200 / 100/ 60ms ( default)
Pulse Output 1 ( SDM120P and SDM120CTP only)
Pulse output 1 is non-configurable. It is fixed up with Export kWh.
The constant is 1000imp/kWh.
Pulse Output2
Pulse output 2 is non-configurable. It is fixed up with Import kWh. The
constant is 1000imp/kWh.
The Pulse width: 60ms
RS485 output for Modbus RTU (SDM120M and SDM120CTM/CT-MV only)
The meter provides a RS485 port for remote communication. Modbus RTU is the
protocol applied. For Modbus RTU, the following RS485 communication parameters
can be configured from the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247
M-Bus communication EN13757-3 (SDM120MB and SDM120CTMB only)
The meter provides an M-Bus port for remote communication. The protocol
fully comply with EN13757-3.The following communication parameters can be
configured via M-bus communication. Baud rate: 300,600, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
M-Bus network primary address: nnn – 3 digits number from 001 to 250
M-Bus network secondary address: 00 00 00 00 to 99 99 99 99
Please contact us for the detailed Modbus/M-Bus communication protocol. sales@eastrongroup.com
Dimensions
Installation
Safety instruction
Information for your own safety
This manual does not contain all of the safety measures for operation of
the equipment(module, device), because special operating conditions, and local
code requirements or regulations may necessitate further measures.
However,it does contain information which must be read for your personal
safety and to avoid material damages. This information is highlighted by a
warning triangle and is represented as follows, depending on the degree of
potential danger.
Warning This means that failure to observe the instruction can result in
death, serious injury or considerable material damage.
Caution This means hazard of electric shock and failure to take the
necessary safety precautions will result in death,serious injury or
considerable material damage.
Qualified personnel
Operation of the equipment (module, device) described in this manual may
only be performed by qualified personnel. Qualified personnel in this manual
means person who are authorized to commission, start up, ground and label
devices, systems and circuits according to safety and Regulatory standards.
Proper handling
The equipment (device, module) may only be used for the application
specified in the catalogue and the user manual, and only be connected with
devices and components recommended and approved by EASTRON.
- Use only insulating tools.
- Do not connect while circuit is live (hot).
- Place the meter only in dry surroundings.
- Do not mount the meter in an explosive area or expose the meter to dust, mildew and insects.
- Make sure the used wires are suitable for the maximum current of this meter.
- Make sure the AC wires are connected correctly before activating the current/voltage to the meter.
- Do not connect the meter to a 3 phase – 400VAC – network.
- Do not touch the meter connecting clamps directly with your bare hands, with metal, blank wire or other material as you may get an electrical shock.
- Make sure the protection cover is placed after installation.
- Installation, maintenance and reparation should only be done by qualified personnel.
- Never break the seals and open the front cover as this might influence the functionality of the meter, and will avoid any warranty.
- Do not drop, or allow physical impact to the meter as there are high precision components inside that may break.
Installation
Wiring diagram
Declaration of Conformity (for the MID-approved version meter only)
We Zhejiang Eastern Electronic Co., Ltd. declares under our sole
responsibility as the manufacturer that the single phase multifunction
electrical energy meter SDM120 series correspond to the production model
described in the EU-type examination certificate and the requirements of the
Directive 2014/32/EU. Type examination certificate number 0120/SGS0141.
Identification number of the
Notified Body: 0120.
Zhejiang Eastron Electronic Co.,Ltd.
N o 1 3 6 9 . C h e n g n a n R d . Jiaxing,
Zhejiang,China
Tel:86 573 83698881/83698882
Tel:86 573 83698883
Email: sales@eastrongroup.com
Web: www.eastrongroup.com