EPEVER SDM120 Series 45A Single Phase Electric Meter User Manual

May 15, 2024
EPEVER

EPEVER SDM120 Series 45A Single Phase Electric Meter

EPEVER SDM120 Series 45A Single Phase Electric Meter

  • Measures kWh, kVarh, kW, kVar, kVA, PF, Hz, dmd, V, A, etc.
  • Bi-directional measurement IMP & EXP
  • Two pulse outputs
  • RS485 Modbus RTU / Mbus
  • Din rail mounting 18mm
  • 45A direct connect / 5A or 100mV CT Connect
  • Better than Class 1 accuracy

Introduction

This document provides operating, maintenance and installation instructions of SD120 series. The unit measures and displays the characteristics of single phase two wires application. It provides voltage, current, power, frequency, power factor and energy information. SDM120 series has both direct connect types and 5A or 100mV CT operated types. The direct connect type can work with direct load 45A. Two Pulse outputs and 1 remote communication port are provided.

This series covers 7 models:

Model   Current Input Communication MID
SDM120M Direct connect 45A RS485 Modbus
SDM120MB Direct connect 45A M-Bus EN13757-3
SDM120P Direct connect 45A —–
SDM120CTM 1A or 5A CT operated RS485 Modbus
SDM120CTMB 1A or 5A CT operated M-Bus EN13757-3
SDM120CTP 1A or 5ACT operated —–
SDM120CT-MV 100mV CT operated RS485 Modbus

Specifications

General Specification

  • Voltage AC (Un)   230V
  • Voltage Range   176-276V AC
  • Current Input   0.25~5(45)A (SDM120 45A) 0.25-5(6)A (SDM120 CT)
  • Power consumption      <2W/10VA
  • Frequency   50/60Hz (50Hz only for MID version)
  • AC voltage withstand 4KV for 1 minute
  • Impulse voltage withstand   6KV-1.2uS wavform
  • Overcurrent withstand     301max for 0.01s (SDM120 45A) 201max for 0.01s (SDM120CT)
  • Pulse output rate   1000imp/kWh (default) 1000/100/10/1 imp/kWh/kVarh (configurable)
  • Display LCD with white backlit
  • Max. Reading  99999.9kWh (SDM120 45A) 999999 kWh (SDM120 CT)

Accuracy

  • Voltage                                               0.5% of range maximum

  • Current                                                0.5% of nominal

  • Frequency                                           0.2% of mid-frequency

  • Power factor                                       1% of Unity

  • Active power                                       1% of range maximum

  • Reactive power                                   1% of range maximum

  • Apparent power                                  1% of range maximum

  • Active energy                                      Class 1 IEC62053-21
    Class B EN50470-3 (MID product only)

  • Reactive energy                                  1% of range maximum

Environment

Operating temperature -25℃ to +55℃
Storage and transportation temperature -40℃ to +70℃
Reference temperature 23℃±2℃
Relative humidity 0 to 95%, non-condensing

Altitudeup to 2000m

Warm up time

| 3s
Mechanical environment| M1
Electromagnetic  environment| E2
Degree of pollution| 2

Mechanics

  • Din rail dimensions                                    18x119x62 (WxHxD) DIN 43880
  • Mounting                                                      DIN rail 35mm
  • Sealing                                                           IP51 (indoor)
  • Material                                                        self-extinguishingUL94V-0

Display

Initialization Display
When it is powered on, the meter will initialize and do self-checking.

EPEVER SDM120 Series 45A Single Phase Electric Meter 1

Full screen

It will last for 3 seconds.


Software version

It will last for 3 seconds.

Ct1 (SDM120CT* only ) Primary current 1A-9999A Default: 5
Total active energy(kWh)

After the self-checking program, the meter screen will display the total active energy (kWh)

Note : For the MID version of SDM120CTM, SDM120CTMB and SDM120CTP, the CT ratio can be set only once. Before you set the CT ratio, please check the ratio of the CT connected to the meter. For example, if the CT is 100/5A, please set CT1 to be 100.

Scroll Display by button
There is a button on the front of the meter. After initialization and self- checking program , the meter display the measured values . The default page is total kWh. If the user wants to check other information, he needs to press the scroll button on the front panel.

| Click the button, the LCD display will scroll the measurements.
---|---
Keep pressing the button for 3 seconds, the meter will enter set-up mode.

Total active energy(kWh)

Display format:0000.00→9999.99 →10000.0→99999.9→0000.00


Import active energy(kWh) Display format:0000.00→9999.99

→10000.0→99999.9→0000.00

Export active energy(kWh) Display format:0000.00→9999.99

→10000.0→99999.9→0000.00

Voltage (V)
Current (A)
Active power (W)
Frequency (F)
Power factor (PF)
Modbus Address or Primary address Default: 001
Baudrate Default : 2400bps
Parity

None/Even/Odd are optional Default: none

CT 1(SDM120CT* only )
Primary current 1A-9999A         Default: 5

Note: For the MID version of SDM120CTM, SDM120CTMB and SDM120CTP, the CT ratio can be set only once.

CT 2(SDM120CT* only )
Secondary current 1A or 5A ,Default: 5
For SDM120CT-MV,CT2 is fixed with 100mV
M-Bus secondary address High
(M-Bus version only )
M-Bus secondary address Low
(M-Bus version only )
Software version In kind prevail

The display of each model:

EPEVER SDM120 Series 45A Single Phase Electric Meter 4

EPEVER SDM120 Series 45A Single Phase Electric Meter 5

Communication

Pulse Output
The meter is equipped with 2 pulse outputs, which are fully isolated from the inside circuit. That generates pulses in proportion to the measured energy. The pulse outputs are polarity dependent , passive transistor output requiring an external voltage source for correct operation. For this external voltage source, the voltage shall be 5-27V DC, and the maximum input current shall be 27mA DC.

ATTENTION :Pule output must be fed as shown in the wiring diagram below.Scrupulousil respect polarities and the connection mode. Opto-coupler with potential-free SPST-NO Contact.
Contact range:5~27VDC Max. current
Input:27mA DC

Pulse Output 1 ( SDM120M/ MB/CTM/CT-MV/CTM only)
Pulse output 1 is configurable. The pulse output 1 can be set to generate pulses to represent total / import/ export kWh or kVarh. The pulse constant can be set to generate 1 pulse per: 0.001 ( default) / 0.01 /0.1 /1kWh /kVarh.
Pulse width: 200 / 100/ 60ms ( default)

Pulse Output 1 ( SDM120P and SDM120CTP only)
Pulse output 1 is non-configurable. It is fixed up with Export kWh.
The constant is 1000imp/kWh.

Pulse Output2
Pulse output 2 is non-configurable. It is fixed up with Import kWh. The constant is 1000imp/kWh.
The Pulse width: 60ms

RS485 output for Modbus RTU (SDM120M and SDM120CTM/CT-MV only)
The meter provides a RS485 port for remote communication. Modbus RTU is the protocol applied. For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247

M-Bus communication EN13757-3 (SDM120MB and SDM120CTMB only)
The meter provides an M-Bus port for remote communication. The protocol fully comply with EN13757-3.The following communication parameters can be configured via M-bus communication. Baud rate: 300,600, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
M-Bus network primary address: nnn – 3 digits number from 001 to 250
M-Bus network secondary address: 00 00 00 00 to 99 99 99 99

Please contact us for the detailed Modbus/M-Bus communication protocol. sales@eastrongroup.com

Dimensions

EPEVER SDM120 Series 45A Single Phase Electric Meter 7

Installation

Safety instruction

Information for your own safety
This manual does not contain all of the safety measures for operation of the equipment(module, device), because special operating conditions, and local code requirements or regulations may necessitate further measures.
However,it does contain information which must be read for your personal safety and to avoid material damages. This information is highlighted by a warning triangle and is represented as follows, depending on the degree of potential danger.

Warning This means that failure to observe the instruction can result in death, serious injury or considerable material damage.
Caution This means hazard of electric shock and failure to take the necessary safety precautions will result in death,serious injury or considerable material damage.

Qualified personnel
Operation of the equipment (module, device) described in this manual may only be performed by qualified personnel. Qualified personnel in this manual means person who are authorized to commission, start up, ground and label
devices, systems and circuits according to safety and Regulatory standards.

Proper handling
The equipment (device, module) may only be used for the application specified in the catalogue and the user manual, and only be connected with devices and components recommended and approved by EASTRON.

  • Use only insulating tools.
  • Do not connect while circuit is live (hot).
  • Place the meter only in dry surroundings.
  • Do not mount the meter in an explosive area or expose the meter to dust, mildew and insects.
  • Make sure the used wires are suitable for the maximum current of this meter.
  • Make sure the AC wires are connected correctly before activating the current/voltage to the meter.
  • Do not connect the meter to a 3 phase – 400VAC – network.
  • Do not touch the meter connecting clamps directly with your bare hands, with metal, blank wire or other material as you may get an electrical shock.
  • Make sure the protection cover is placed after installation.
  • Installation, maintenance and reparation should only be done by qualified personnel.
  • Never break the seals and open the front cover as this might influence the functionality of the meter, and will avoid any warranty.
  • Do not drop, or allow physical impact to the meter as there are high precision components inside that may break.

Installation

EPEVER SDM120 Series 45A Single Phase Electric Meter 8

Wiring diagram

EPEVER SDM120 Series 45A Single Phase Electric Meter 9

Declaration of Conformity (for the MID-approved version meter only)
We Zhejiang Eastern Electronic Co., Ltd. declares under our sole responsibility as the manufacturer that the single phase multifunction electrical energy meter SDM120 series correspond to the production model described in the EU-type examination certificate and the requirements of the Directive 2014/32/EU. Type examination certificate number 0120/SGS0141. Identification number of the
Notified Body: 0120.

Zhejiang Eastron Electronic Co.,Ltd.
N o 1 3 6 9 . C h e n g n a n R d . Jiaxing,
Zhejiang,China
Tel:86 573 83698881/83698882
Tel:86 573 83698883
Email: sales@eastrongroup.com
Web: www.eastrongroup.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals