EPEVER LS-EPD Solar Charge Controller LandStar User Guide

June 3, 2024
EPEVER

Solar Charge Controller

General Information

LS EPD series solar charge controller adopts the most advanced digital technique and operates fully automatically. It is ideal for extreme environments with corrosion, dust, water etc and has various unique functions:

  • Electronic protection: Over charging, over discharging, overload, short circuit and reverse protection of solar module
  • High efficient Series PWM charging, increase the battery lifetime and improve the solar system performance
  • Widely used, automatically recognize day/night
  • Battery LED indicate battery status
  • Industrial design, wide application range
  • Digital tube menu, only one key solve all setting simply
  • Intelligent timer function with 1~13 hours option
  • IP67 protection

Features and Mounting

EPEVER LS-EPD Solar Charge Controller LandStar - fig 1

1 Charging Status LED indicator
2 Battery Status LED indicator
3 Temperature Sensor
4 Solar Module Terminals
5 Battery Terminals
6 Load Terminals
7 Digital tube
8 Key
9 Aluminum housing
10 Mounting hole Φ5

Mounting

  1. Connect components to the charge controller in the sequence as shown above picture and pay much attention to the “+” and “-”. Always power the battery firstly.
  2. After power the battery, check the battery indicator on the controller, it will be green. If it’s not green, please refer to chapter 4.
  3. The battery fuse should be installed as close to battery as possible. The suggested distance is within 150mm.

Indicators Description and Operation

  1. Indicator Status Description
    Charging Status LED indicator| Green| On Solid| Normal
    ---|---|---|---
    Green| Fast Flashing| Over voltage
    Battery Status LED
    indicator| Green| On Solid| Normal
    Green| Slowly Flashing| Full
    Orange| On Solid| Under voltage
    Red| On Solid| Over discharged
    Radix Point of Digital
    tube
    (Load indicator)| Red| On Solid| Load ON
    Red| Slowly Flashing| Over Load
    Red| Fast Flashing| Short Circuit
  2. Operation

  1. After Powering on, disconnect the PV or connect the PV(Voltage <5V) , the light of the digital tube point go on; Connect the PV(Voltage>6V) ,the light of the digital tube point go off.
  2. The key can be used to operate switching on/off the load (Manual control) or clearing the faults
  3. Keeping pressing the button over 5S, It will go to the parameter in browsing mode which can cycle through the parameter item by clicking the button ,after the light of the digital tube point going on.
  4. After the digital tube displaying the value what you want to configure, releasing the key and waiting 15S, Digital Tube stop flashing, then the configuration is successful.

Load mode

  • Manual Control:Control the load via the button.

EPEVER LS-EPD Solar Charge Controller LandStar - fig 3

Note: In the mode of Light ON/OFF and Light ON/Timer, the Load is turned on after 10Min. delay.

  • Test Mode (Default):Test Mode is as same as Light Control Mode but no delay.
    The correspondence table of Load Work Mode & LED digital tube value
Value Working mode Value Working mode
0 Light ON/OFF O. Light ON + 8 hours
1 Light ON + 1 hours 1. Light ON + 9 hours
2 Light ON + 2hours 2. Light ON + 10 hours
3 Light ON + 3hours 3. Light ON + 11 hours
4 Light ON + 4 hours 4. Light ON + 12 hours
5 Light ON + 5 hours 5. Light ON + 13 hours
6 Light ON + 6 hours 6. Manual Control
7 Light ON + 7 hours 7. Test Mode

Troubleshooting

Faults Possible reasons Troubleshooting

Charging LED indicator off during daytime when sunshine falls on PV modules properly| PV array disconnection| Check that PV and battery wire connections are correct and tight
Battery indicator green
fast flashing| Battery voltage higher than over voltage disconnect voltage| 1. Disconnect the solar array and measure the battery voltage whether is too high; 2. Change the controller; 3. Change the battery
Battery LED indicators red color and loads not working| Battery over discharged| The controller cut off the output automatically. LED indicator will return to green automatically when fully
The radix point of digital tube fast flashing and load not working| Short circuit| Clear short circuit. It is reactivated after delayed 10 seconds for the first time, If over 1 time,press the key to clear error and the controller will resume to work after 3s or restart the controller
The radix point of digital tube slowly
flashing and load not working| Over load| Please reduce the number of electric equipments.
When load power reaches 1.25-1.5 times, 1.5-2 times and 2 times more than nominal value, controller will automatically close loads in 60 seconds, 5 seconds and 1 second, respectively.
Please press the key to clear error and the controller will resume to work after 3s or restart the controller

Technical Specifications

Item LS1024EPD LS2024EPD
Nominal system voltage 12/24VDC Auto 12/24VDC Auto
Max. PV input voltage 50V 50V
Rated current 10A 20A
Equalize Voltage 14.8V(12V);29.6V(24V)
Boost Voltage 14.4V(12V);28.8V(24V)
Float Voltage 13.7V(12V);27.4V(24V)

Low Voltage Reconnect
Voltage| | 12.6V(12V);25.2V(24V)
Low Voltage Disconnect
Voltage| | 11.2V(12V);22.4V(24V)
Self-consumption| | 12V: s-4.58mA: 24V: .6.01mA
Temperature compensation
coefficient| | -5mV/t/2V ( 25°C )
Working temperature| | -35°C —+50 C
Enclosure| | IP67
Dimension| | 108.5mmx75mmx25.6mm
Mounting size| | 100.5mm
Mounting hole size| | 5
Power cable| | PV/BAT/LOAD:4.0mm2| PV/BAT/LOAD:6.0mm2
Net weight| | 410g| 435g

Any changes without prior notice!