Operating Instructions
Warning: Always test on a known live circuit before use to ensure proper
operation.
Identification and Description of Operating Controls and Functions for the
61-502 Receptacle and GFCI Tester:
- Hot Neutral and Ground Prongs
- Ergonomic Grip
- GFCI Test Button
- GFCI Test LED
- Wiring Indicator Legend
- Wiring Indicator Lights
- Tactile Barrier
Wiring Configuration Testing
Tests for correct wiring, open ground, reverse polarity, open hot, open
neutral and hot/ground reversed and hot on neutral with open hot.
- Plug tester into receptacle under test.
- Verify proper wiring configuration by noting the bulbs lit on the tester.
- Compare the bulbs lit to the legend on the product label to determine the wire condition.
- If a mis-wired condition is found, stop any further testing and consult a qualified electrician to rectify the problem.
GFCI Testing
- Verify receptacle for correct wiring.
- Consult the GFCI device manufacturer’s instructions to determine that the GFCI is installed in accordance with the manufacturer’s specifications.
- Check for correct wiring of the receptacle and all remotely connected receptacles on the branch circuit.
- Operate the test button on the GFCI installed in the circuit. The test light will turn on, indicating the activation of the GFCI test. The GFCI must trip. If the GFCI does not trip, consult a qualified electrician. If it does trip, reset the GFCI.
- Activate the test button on the GFCI tester for a minimum of 6 seconds when testing the GFCI condition. Visible indication (ALL LED’s will turn off and you will hear a click as the GFCI breaker functions) on the GFCI tester must cease when tripped.
- If the tester fails to trip the GFCI, it suggests: (a) a wiring problem with a totally operable GFCI, or (b) proper wiring with a faulty GFCI. Consult with an electrician to check the condition of the wiring and the GFCI.
CAUTION: When testing GFCIs installed in 2-wire systems (no ground wire available), the tester may give a false indication that the GFCI is not functioning properly. If this occurs, recheck the operation of the GFCI using the test and reset buttons ON THE GFI, not the 61-502 transmitter. The GFCI button ON THE GFI test function will demonstrate proper operation.
NOTE:
- All appliances or equipment on the circuit being tested should be unplugged to help avoid erroneous readings.
- Not a comprehensive diagnostic instrument but a simple instrument to detect nearly all probable common improper wiring conditions.
- Refer all indicated problems to a qualified electrician.
- Will not indicate quality of ground.
- Will not detect 2 hot wires in circuit.
- Will not detect a combination of defects.
- Will not indicate reversal of grounded and grounding conductors
Safety
Complies with cULus UL1436 and CSAC22.2 No. 160
CATII 150V AC
Overvoltage CAT II 150V. Any voltages exceeding the defined maximum voltage
measurement category described above are outside the normal use of the
equipment and protection cannot be guaranteed.
Pollution Degree Class 2
Two-year warranty limited solely to repair or replacement; no warranty of
merchantability, fitness for a particular purpose or consequential damages.