SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
January 2020
No. OCH684
REVISED EDITION-C
SUZ-M25VA.TH
SUZ-M35VA.TH
TECHNICAL & SERVICE MANUAL
[Model Name] | [Service Ref.] |
---|---|
SUZ-M25VA | SUZ-M25VA.TH |
SUZ-M25VAR1.TH
SUZ-M25VAR2.TH
SUZ-M25VA-ET| SUZ-M25VA-ET.TH
SUZ-M25VA-ETR2.TH
SUZ-M35VA| SUZ-M35VA.TH
SUZ-M35VAR1.TH
SUZ-M35VAR2.TH
SUZ-M35VA-ET| SUZ-M35VA-ET.TH
SUZ-M35VA-ETR2.TH
SUZ-M50VA| SUZ-M50VA.TH
SUZ-M50VAR1.TH
SUZ-M50VAR2.TH
SUZ-M50VA-ET| SUZ-M50VA-ET.TH
SUZ-M50VA-ETR2.TH
SUZ-M60VA| SUZ-M60VA.TH
SUZ-M60VAR1.TH
SUZ-M60VAR2.TH
SUZ-M60VA-ET| SUZ-M60VA-ET.TH
SUZ-M60VA-ETR2.TH
SUZ-M71VA| SUZ-M71VA.TH
SUZ-M71VAR1.TH
SUZ-M71VA-ET| SUZ-M71VA-ET.TH
SUZ-M71VA-ETR1.TH
R32
Revision:
- SUZ-M25VAR2.TH,
SUZ-M35VAR2.TH,
SUZ-M50VAR2.TH,
SUZ-M60VAR2.TH
SUZ-M71VAR1.TH
SUZ-M25VA-ETR2.TH
SUZ-M35VA-ETR2.TH
SUZ-M50VA-ETR2.TH
SUZ-M60VA-ETR2.TH, and
SUZ-M71VA-ETR1.TH have been added in
REVISED EDITION-C. OCH684 REVISED EDITION-B is void.
Note:
- This service manual describes service data of the outdoor units only.
TECHNICAL CHANGES
Service ref. have been changed as follows.
SUZ-M25VAR1.TH | SUZ-M25VAR2.TH | |
---|---|---|
SUZ-M35VAR1.TH | SUZ-M35VAR2.TH | |
SUZ-M50VAR1.TH | SUZ-M50VAR2.TH | |
SUZ-M60VAR1.TH | SUZ-M60VAR2.TH | |
SUZ-M71VA.TH | SUZ-M71VAR1.TH | |
SUZ-M25VA-ET.TH | SUZ-M25VA-ETR2.TH | |
SUZ-M35VA-ET.TH | SUZ-M35VA-ETR2.TH | |
SUZ-M50VA-ET.TH | SUZ-M50VA-ETR2.TH | |
SUZ-M60VA-ET.TH | SUZ-M60VA-ETR2.TH | |
SUZ-M71VA-ET.TH | SUZ-M71VA-ETR1.TH |
- Connection with SFZ will be added.
SUZ-M25VA.TH | SUZ-M25VAR1.TH | |
---|---|---|
SUZ-M35VA.TH | SUZ-M35VAR1.TH | |
SUZ-M50VA.TH | SUZ-M50VAR1.TH | |
SUZ-M60VA.TH | SUZ-M60VAR1.TH |
• Connection with MFZ-KT will be added.
COMBINATION OF INDOOR AND OUTDOOR UNITS
INDOOR UNIT SERVICE MANUAL
Only for R1 and R2 models.
*2 Only for R2 models. OCH684C
SAFETY PRECAUTION
MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT
WARNINGRisk of fire
This mark is for R32 refrigerant only. Refrigerant type is written on nameplate of outdoor unit. In case that refrigerant type is R32, this unit uses a flammable refrigerant. If refrigerant leaks and comes in contact with fire or heating part, it will create harmful gas and there is risk of fire.
Read the OPERATION MANUAL carefully before operation.
Service personnel are required to carefully read the OPERATION MANUAL and
INSTALLATION MANUAL before operation.
**** Further information is available in the OPERATION MANUAL, INSTALLATION
MANUAL, and the like.
2-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must be disconnected.
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R32
Preparation before the repair service
- Prepare the proper tools.
- Prepare the proper protectors.
- Provide adequate ventilation.
- After stopping the operation of the air conditioner, turn off the power-supply breaker.
- Discharge the condenser before the work involving the electric parts.
Use new refrigerant pipes.
In the case of using the existing pipes for R22, be careful with the
following.
- Be sure to clean the pipes and make sure that the insides of the pipes are clean.
- Change flare nut to the one provided with this product.
Use a newly flared pipe
- Avoid using thin pipes.
Make sure that the Inside and outside of refrigerant piping is clean and it
has no contaminants such as sulfur, oxides, dirt, shaving particles, etc.,
which are hazard to refrigerant cycle. In addition, use pipes with specified
thickness.
Contamination inside refrigerant piping can cause deterio-ration of
refrigerant oil, etc.
Store the piping indoors, and keep both ends of the piping sealed until just
before brazing. (Leave elbow joints, etc. In their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can cause
deterioration of refrigerant oil or malfunction of compressor.
The refrigerant oil applied to flare and flange connections must be ester oil,
ether oil or alkylbenzene oil in a small amount.
If large amount of mineral oil enters, that can cause deterioration of
refrigerant oil, etc.
Do not use refrigerant other than R32.
If other refrigerant (R22, etc.) is used, chlorine in refrigerant can cause
deterioration of refrigerant oil, etc.
Precautions during the repair service
- Do not perform the work involving the electric parts with wet hands.
- Do not pour water into the electric parts.
- Do not touch the refrigerant.
- Do not touch the hot or cold areas in the refrigerating cycle.
- When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to touch the live parts.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause
deterioration of refrigerant oil, etc.
Use the following tools specifically designed for use with R32
refrigerant.
The following tools are necessary to use R32 refrigerant.
Tools for R32
Gauge manifold| Flare tool
Charge hose| Size adjustment gauge
Gas leak detector| Vacuum pump adaptor
Torque wrench| Electronic refrigerant charging scale
Handle tools wite care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause
deterioration of refrigerant oil or malfunction of compressor.
Use the specified refrigerant only.
Never use any refrigerant other than that specified. Doing so may cause a
burst, an explosion, or fire when the unit is being used, serviced, or
disposed of. Correct refrigerant is specified in the manuals and on the spec
labels provided with our products. We will not be held responsible for
mechanical failure, system malfunction, unit breakdown or accidents caused by
failure to follow the instructions.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes
into contact with a flame, poisonous gases will be released.
[1] Warning for service
- Do not alter the unit.
- For installation and relocation work, follow the instructions in the Installation Manual and use tools and pipe components specifically made for use with refrigerant specified in the outdoor unit installation manual.
- Ask a dealer or an authorized technician to install, relocate and repair the unit. For appliances not accessible to the general public.
- Refrigerant pipes connection shall be accessible for maintenance purposes.
- If the air conditioner is installed in a small room or closed room, measures must be taken to prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. Should the refrigerant leak and cause the concentration limit to be exceeded, hazards due to lack of oxygen in the room may result.
- Keep gas-burning appliances. electric heaters, and other fire sources (ignition sources) away from the location where installation, repair, and other air conditioner work will be performed. If refrigerant comes into contact with a flame, poisonous gases will be released.
- When installing or relocating, or servicing the air conditioner, use only the specified refrigerant (R32) to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines. If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant line, and may result in an explosion and other hazards.
- After installation has been completed, check for refrigerant leaks. If refrigerant leaks into the room and comes into contact with the flame of a heater or portable cooking range, poisonous gases will be released.
- Do not use low temperature solder alloy in the case of brazing the refrigerant pipes.
- When performing brazing work, be sure to ventilate the room sufficiently. Make sure that there are no hazardous or flammable materials nearby. When performing the work in a closed room, small room, or similar location, make sure that there are no refriger-ant leaks before performing the work. If refrigerant leaks and accumulates, it may ignite or poisonous gases may be released.
- Do not install the unit in places where refrigerant may build-up or places with poor ventilation such as a semi-base-ment or a sunken place in outdoor: Refrigerant is heavier than air, and inclined to fall away from the leak source.
- Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manu-facturer.
- The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater).
- Do not pierce or burn.
- Be aware that refrigerants may not contain an odor.
- Pipe-work shall be protected from physical damage.
- The installation of pipe-work shall be kept to a minimum.
- Compliance with national gas regulations shall be observed.
- Keep any required ventilation openings clear of obstruction.
- Servicing shall be performed only as recommended by the manufacturer.
- The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
- Maintenance, service and repair operations shall be performed by authorized technician with required qualification.
- Be sure to have appropriate ventilation in order to prevent ignition. Furthermore, be sure to carry out fire preven-tion measures that there are no dangerous or flammable objects in the surrounding area.
[2] Cautions for unit using R32 refrigerant
Basic work procedures are the same as those for conventional units using
refrigerant R410A. However, pay careful attention to the following points.
attention to the following points.
(1) Information on servicing
(1-1) Checks on the Area
Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimized.
For repair to the refrigerating systems, (1-3) to (1-7) shall be completed
prior to conducting work on the systems.
(1-2) Work Procedure
Work shall be undertaken under a controlled procedure so as to minimize the
risk of a flammable gas or vapor being present while the work is being
performed.
(1-3) General Work Area
All maintenance staff and others working in the local area shall be instructed
on the nature of work being carried out.
Work in confined spaces shall be avoided. The area around the workspace shall
be sectioned off. Ensure that the conditions within the area have been made
safe by control of flammable material.
(1-4) Checking for Presence of Refrigerant
The area shall be checked with an appropriate refrigerant detector prior to
and during work, to ensure the technician is aware of potentially toxic or
flammable atmospheres. Ensure that the leak detection equipment being used is
suitable for use with all applicable refrigerants, i.e. non-sparking,
adequately sealed or intrinsically safe.
(1-5) Presence of Fire Extinguisher
If any hot work is to be conducted on the refrigeration equipment or any
associated parts, appropriate fire extinguishing equipment shall be available
to hand.
Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
(1-6) No Ignition Sources
No person carrying out work in relation to a refrigeration system which
involves exposing any pipe work shall use any sources of ignition in such a
manner that it may lead to the risk of fire or explosion. All possible
ignition sources, including cigarette smoking, should be kept sufficiently far
away from the site of installation, repairing, removing and disposal, during
which refrigerant can possibly be released to the surrounding space. Prior to
work taking place, the area around the equipment is to be surveyed to make
sure that there are no flammable hazards or ignition risks. “No Smoking” signs
shall be displayed.
(1-7) Ventilated Area
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work. A degree of ventilation
shall continue during the period that the work is carried out. The ventilation
should safely disperse any released refrigerant and preferably expel it
externally into the atmosphere.
(1-8) Checks on the Refrigeration Equipment
Where electrical components are being changed, they shall be fit for the
purpose and to the correct specification. At all times the manufacturer’s
maintenance and service guidelines shall be followed. If in doubt, consult the
manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable
refrigerants:
- The charge size is in accordance with the room size within which the refrigerant containing parts are installed.
- The ventilation machinery and outlets are operating adequately and are not obstructed.
- Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected.
- Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being corroded.
(1-9) Checks on Electrical Devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures.
If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.
Initial safety checks shall include that:
- capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
- no live electrical components and wiring are exposed while charging, recovering or purging the system;
- there is continuity of earth bonding
(2) Repairs to Sealed Components
(2-1) During repairs to sealed components, all electrical supplies shall be
disconnected from the equipment being worked upon prior to any removal of
sealed covers, etc. If it is absolutely necessary to have an electrical supply
to equipment during servicing, then a permanently operating form of leak
detection shall be located at the most critical point to warn of a potentially
hazardous situation.
(2-2) Particular attention shall be paid to the following to ensure that by
working on electrical components, the casing is not altered in such a way that
the level of protection is affected. This shall include damage to cables,
excessive number of connections, terminals not made to original specification,
damage to seals, incorrect fitting of glands, etc.
Ensure that the apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded to the point that
they no longer serve the purpose of preventing the ingress of flammable
atmospheres.
Replacement parts shall be in accordance with the manufacturer’s
specifications.
(3) Repair to intrinsically Safe Components
Do not apply any permanent inductive or capacitance loads to the circuit
without ensuring that this will not exceed the permissible voltage and current
permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while
live in the presence of a flammable atmosphere.
The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts
may result in the ignition of refrigerant in the atmosphere from a leak.
(4) Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure,
vibration, sharp edges or any other adverse environmental effects. The check
shall also take into account the effects of aging or continual vibration from
sources such as compressors or fans.
(5) Detection of Flammable Refrigerants
Under no circumstances shall potential sources of ignition be used in the
searching for or detection of refrigerant leaks.
A halide torch (or any other detector using a naked flame) shall not be used.
(6) Leak Detection Methods
Electronic leak detectors may be used to detect refrigerant leaks but, in the
case of flammable refrigerants, the sensitivity may not be adequate, or may
need re-calibration. (Detection equipment shall be calibrated in a
refrigerant-free area.) Ensure that the detector is not a potential source of
ignition and is suitable for the refrigerant used. Leak detection equip- ment
shall be set at a percentage of the LFL of the refrigerant and shall be
calibrated to the refrigerant employed, and the appropriate percentage of gas
(25% maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use
of detergents containing chlorine shall be avoided as the chlorine may react
with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed/extinguished.
If a leakage of refrigerant is found which requires brazing, all of the
refrigerant shall be recovered from the system, or isolated (by means of shut
off valves) in a part of the system remote from the leak. For appliances
containing flammable refrigerants, oxygen free nitrogen (OFN) shall then be
purged through the system both before and during the brazing process.
(7) Removal and Evacuation
When breaking into the refrigerant circuit to make repairs – or for any other
purpose conventional procedures shall be used. However, for flammable
refrigerants it is important that best practice is followed since flammability
is a consideration. The following procedure shall be adhered to:
- remove refrigerant
- purge the circuit with inert gas
- evacuate
- purge again with inert gas
- open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances containing flammable refrigerants, the system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times.
Compressed air or oxygen shall not be used for purging refrigerant systems.
For appliances containing flammable refrigerants, flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and that ventilation is available.
(8) Charging Procedures
In addition to conventional charging procedures, the following requirements
shall be followed:
- Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
- Cylinders shall be kept upright.
- Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
- Label the system when charging is complete (if not already).
- Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak- tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
(9) Decommissioning
Before carrying out this procedure, it is essential that the technician is
completely familiar with the equipment and all its detail. It is recommended
good practice that all refrigerants are recovered safely. Prior to the task
being carried out, an oil and refrigerant sample shall be taken in case
analysis is required prior to re-use of reclaimed refrigerant. It is essential
that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure, ensure that:
- mechanical handling equipment is available, if required, for handling refrigerant cylinders;
- all personal protective equipment is available and being used correctly;
- the recovery process is supervised at all times by a competent person;
- recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer’s instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment
are removed from site promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
(10) Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
(11) Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants including, when applicable, flammable refrigerants.
In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.
2-3. Choosing the outdoor unit installation location
R32 is heavier than air—as well as other refrigerants— so tends to accumulate
at the base (in the vicinity of the floor). If R32 accumulates around base, it
may reach a flammable concentration in case room is small. To avoid ignition,
maintaining a safe work environment is required by ensuring appropriate
ventilation. If a refrigerant leak is
confirmed in a room or an area where there is insufficient ventilation,
refrain from using of flames until the work environment can be improved by
ensuring appropriate
ventilation.
Install outdoor units in a place where at least one of the four sides is open,
and in a sufficiently large space without depressions.
2-4. Minimum installation area
If you unavoidably install a unit in a space where all four sides are blocked
or there are depressions, confirm that one of these situations (A, B or C) is
satisfied.
Note: These countermeasures are for keeping safety not for specification
guarantee.
A) Secure sufficient installation space (minimum installation area Amin).
Install in a space with an installation area of Amin or more, corresponding to
refrigerant amount M (factory-charged refrigerant + locally added
refrigerant).
M [kg] | Amin [m²] |
---|---|
1.0 | 12 |
1.5 | 17 |
2.0 | 23 |
2.5 | 28 |
3.0 | 34 |
3.5 | 39 |
4.0 | 45 |
4.5 | 50 |
5.0 | 56 |
5.5 | 62 |
6.0 | 67 |
6.5 | 73 |
7.0 | 78 |
7.5 | 84 |
B) Install in a space with a depression height of 0.125 [m]
C) Create an appropriate ventilation open area.
Make sure that the width of the open area is 0.9 [m] or more and the height of
the open area is 0.15 [m] or more.
However, the height from the bottom of the installation space to the bottom
edge of the open area should be 0.125 [m] or less.
Open area should be 75% or more opening.
indoor unitys
Install in a room with a floor area of Amin or more, corresponding to
refrigerant amount M (factory-charged refrigerant
+ locally added refrigerant).
- For the factory-charged refrigerant amount, refer to the spec nameplate or installation manual.
For the amount to be added locally, refer to the installation manual.
Install the indoor unit so that the height from the floor to the bottom of the indoor unit is h0; for wall mounted: 1.8 m or more
for ceiling suspended, cassette and ceiling concealed: 2.2 m or more for floor standing (PSA-M): 0 m
for floor standing (MFZ-KT): Refer to indoor unit installation manual.
for floor standing concealed: Refer to indoor unit installation manual. - There are restrictions in installation height for each model, so read the installation manual for the particular unit. Case 1: for wall mounted, ceiling suspended, cassette and concealed
M [kg] | Amin [m²] |
---|---|
1.0 | 4 |
1.5 | 6 |
2.0 | 8 |
2.5 | 10 |
3.0 | 12 |
3.5 | 14 |
4.0 | 16 |
4.5 | 20 |
5.0 | 24 |
5.5 | 29 |
6.0 | 35 |
6.5 | 41 |
7.0 | 47 |
7.5 | 54 |
Case 2: for floor standing (PSA-M)
M [kg] | Amin [m²] |
---|---|
< 1.84 | No requirements |
1.84 | 6 |
2 | 6 |
2.5 | 7 |
3 | 9 |
3.5 | 10 |
4 | 11 |
4.5 | 13 |
5 | 14 |
5.5 | 15 |
6 | 17 |
6.5 | 18 |
7 | 20 |
7.5 | 21 |
Case 3: for floor standing (MFZ-KT)
M [kg] | Amin [m²] |
---|---|
1.00 | No requirements |
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.84| 3.63
1.90| 3.75
2.00| 3.95
2.10| 4.15
2.20| 4.34
2.30| 4.54
2.40| 4.74
Case 4: for floor standing concealed
Case 4-1: When duct is installed
M [kg] | Amin [m²] |
---|---|
h 1.8 | 1.4 h < 1.8 |
1.00 | No requirements |
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.84| 4.5| 5.8| 8.0
1.90| 4.6| 5.9| 8.3
2.00| 4.9| 6.3| 8.7
2.10| 5.1| 6.6| 9.2
2.20| 5.4| 6.9| 9.6
2.30| 5.6| 7.2| 10.0
2.40| 5.8| 7.5| 10.5
- The height h of the air outlet port shall not be less than 1.0 m
M [kg] | Amin [m²] |
---|---|
0=90 | 60=<0<90 |
1.00 | No requirements |
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.84| 4.1| 5.0| 8.3
1.90| 4.3| 5.1| 8.6
2.00| 4.5| 5.4| 9.0
2.10| 4.7| 5.7| 9.5
2.20| 4.9| 5.9| 9.9
2.30| 5.2| 6.2| 10.4
2.40| 5.4| 6.5| 10.8
The grille shall not be less then 30
PARTS NAMES AND FUNCTIONS
SUZ-M25VA.TH
SUZ-M25VAR1.TH
SUZ-M25VAR2.TH
SUZ-M25VA-ET.TH
SUZ-M25VA-ETR2.TH
SUZ-M35VA.TH
SUZ-M35VAR1.TH
SUZ-M35VAR2.TH
SUZ-M35VA-ET.TH
SUZ-M35VA-ETR2.TH
SUZ-M50VA.TH
SUZ-M50VAR1.TH
SUZ-M50VAR2.TH
SUZ-M50VA-ET.TH
SUZ-M50VA-ETR2.TH
SUZ-M60VA.TH
SUZ-M60VAR1.TH
SUZ-M60VAR2.TH
SUZ-M60VA-ET.TH
SUZ-M60VA-ETR2.TH
SUZ-M71VA.TH
SUZ-M71VAR1.TH
SUZ-M71VA-ET.TH
SUZ-M71VA-ETR1.TH
Model | SUZ-M·VA |
---|---|
Drain socket | 1 |
SPECIFICATION
Service ref.
| SUZ-M25VA.TH SUZ-M25VAR1.TH SUZ-M25VAR2.TH SUZ-M25VA-ET.TH SUZ-M25VA-
ETR2.TH| SUZ-M35VA.TH SUZ-M35VAR1.TH SUZ-M35VAR2.TH SUZ-M35VA-ET.TH
SUZ-M35VA-ETR2.TH| SUZ-M50VA.TH SUZ-M50VAR1.TH SUZ-M50VAR2.TH SUZ-
M50VA-ET.TH SUZ-M50VA-ETR2.TH| SUZ-M60VA.TH SUZ-M60VAR1.TH SUZ-
M60VAR2.TH SUZ-M60VA-ET.TH SUZ-M60VA-ETR2.TH| SUZ-M71VA.TH SUZ-
M71VAR1.TH SUZ-M71VA-ET.TH SUZ-M71VA-ETR1.TH
---|---|---|---|---|---
Power supply| Single phase 230 V, 50 Hz
Compressor
| Model| KVB073FYXMC| SVB092FBAMT| SVB130FBBMT| SVB172FCKMT
Output| W| 470| 660| 900| 1,200
Current*
| Cooling| ****
A
| 3.0| 4.1| 7.1| 8.4| 9.1
Heating| 3.7| 5.0| 8.0| 9.3| 9.5
Refrigeration oil (Model)| L| 0.27 (FW68S)| 0.35 (FW68S)| 0.40 (FW68S)
Fan motor
| Model| RC0J50-NC| RC0J50-RA| RC0J60-BC
Current*
| Cooling| ****
A
| 0.22| 0.20| 0.29| 0.84
Heating| 0.20| 0.23| 0.29| 0.84
Dimensions W × H × D| mm| 800 × 550 × 285| 800 × 714 × 285| 840 × 880 × 330
Weight| kg| 30| 35| 41| 54| 55
Special remarks| ****
Air
| ****
Cooling
| High| ****
m³/h
| 2,178| 2,058| 2,748| 3,006
Low| 1,038| 906| 1,320| 1,716
Heating
| High| 2,076| 1,962| 2,622| 3,006
Med.| 1,788| 1,686| 2,238| 2,892
Low| 1,452| 1,260| 1,704| 2,280
Sound pressure level*
| Cooling| ****
dB(A)
| 45| 48| 49
Heating| 46| 48| 49| 51
Sound power level| 59| 64| 65| 66
Fan speed
| ****
Cooling
| High| ****
rpm
| 940| 840
Low| 470| 460| 490| 450
Heating
| High| 900| 840| 860
Med.| 780| 810
Low| 640| 600| 610| 650
Fan speed regulator| 3
(R32)
| kg| 0.65| 0.90| 1.20| 1.25| 1.45
Note: Test conditions are based on ISO 5151
Cooling: Indoor D.B. 27°C W.B. 19°C
Outdoor D.B. 35°C
Heating: Indoor D.B. 20°C
Outdoor D.B. 7°C W.B. 6°C
Refrigerant piping length (one way): 5 m
*Measured under rated operating frequency.
Specifications and rating conditions of main electric parts
Service ref.
Item
| SUZ-M25VA.TH SUZ-M25VAR1.TH SUZ-M25VAR2.TH SUZ-M25VA-ET.TH SUZ-M25VA-
ETR2.TH| SUZ-M35VA.TH SUZ-M35VAR1.TH SUZ-M35VAR2.TH SUZ-M35VA-ET.TH
SUZ-M35VA-ETR2.TH| SUZ-M50VA.TH SUZ-M50VAR1.TH SUZ-M50VAR2.TH SUZ-
M50VA-ET.TH SUZ-M50VA-ETR2.TH| SUZ-M60VA.TH SUZ-M60VAR1.TH SUZ-
M60VAR2.TH SUZ-M60VA-ET.TH SUZ-M60VA-ETR2.TH| SUZ-M71VA.TH SUZ-
M71VAR1.TH SUZ-M71VA-ET.TH SUZ-M71VA-ETR1.TH
---|---|---|---|---|---
Smoothing capacitor
| (C61)| —| | | —| —
(C62, C63)| | | | —| —
(CB1, 2, 3)| —| —| —|
Diode module
| (DB61)| 15 A 600 V| 15 A 600 V| 25 A 600 V| —| —
(DB65)| 25 A 600 V| —| —
Fuse
| (F61)| 25 A 250 V| —| —
(F62)| 15 A 250 V| —| —
(F701, F801, F901)| T3.15 A L250 V| —| —
(F601, F880, F901)| —| —| —| T3.15 A L250 V
Power module
| (IC700)| 15 A 600 V| 20 A 600 V
(IC932)| 5 A 600 V
Switch power transistor| (Q821)| 30 A 600 V| —| —
Expansion valve coil| (LEV)| 12 V DC
Reactor
| (L61)| 18 mH| 23 mH| —| —
(L)| —| —| —|
Diode| (D3A, D3B)| —| —| —| 20 A 600 V
Diode module| (DB41A, DB41B)| —| —| —| 20 A 600 V
Current-Limiting PTC thermistor| (PTC64, PTC65)|
Terminal block| (TB1)| 5P| 3P
Relay
| (X63)| 3 A 250 V| —| —
(X64)| 20 A 250 V
(X601)| —| —| —| 3 A 250 V
(X602)| —| —| —| 3 A 250 V
R.V. coil| (21S4)| 220–240 V AC
NOISE CRITERIA CURVES
OUTLINES AND DIMENSIONS
OCH684C
Documents / Resources
|
MITSUBISHI ELECTRIC OCH684 Split Type Heat Pump Air