TOSHIBA APG001Z TOSVERT VF-PS1 Series APOGEE FLN Option Unit Instruction Manual

June 3, 2024
Toshiba

TOSHIBA APG001Z TOSVERT VF-PS1 Series APOGEE FLN Option Unit

NOTICE

  1. Make sure that this instruction manual is delivered to the end user of APOGEE® FLN option unit.
  2. Read this manual before installing or operating the APOGEE® FLN option unit. Keep it in a safe place for reference.
  3.  All information contained in this manual are subject to change without notice. Please confirm the latest information on our web site “www.inverter.co.jp”.

Safety precautions

On the inverter and in its instruction manual, important information is contained for preventing injuries to users, damages to assets, and for proper use of the device.
Read the instruction manual attached to the inverter along with this instruction manual to completely understand the safety precautions, the symbols and indications shown below. Please adhere to the contents of these manuals at all times.

Explanation of markings
Marking Meaning of marking
Warning Indicates that errors in operation may lead to death or serious

injury.
Caution| Indicates that errors in operation may lead to injury (1) to people or that these errors may cause damage to physical property. (2)

(*1) Such things as injury, burns or shock that will not require hospitalization or long periods of outpatient treatment.

(*2) Physical property damage refers to wide-ranging damage to assets and materials.

Meanings of symbols

Marking Meaning of marking
Indicates prohibition (Do not do it).

What is prohibited will be described in or near the symbol in either text or picture form.

| Indicates something mandatory (must be done).

What is mandatory will be described in or near the symbol in either text or picture form.

| Indicates danger or warning.

What is dangerous, or what the warning should be applied to will be described in or near the symbol in either text or picture form.

Limitation of use

Safety precaution
Never use this unit with any device other than TOSVERT VF-PS1 series inverters. Doing so may cause an accident.

**Handling in general**

  Warning


Never Disassemble

| Never disassemble, modify or repair the product.

Disassembling the product may cause electric shocks, fire or injuries. For repairs, call your sales/repair agency.




Prohibited

| Do not open the front cover on the inverter while the inverter power is on. It may lead to electric shocks.

Do not remove this option from VF-PS1 while the power is on. It may lead to electric shocks.

Do not put or insert foreign objects such as waste cable, bars or wires into the product. It may lead to electric shocks or fire.

Do not splash water over the product, and do not wipe the body with a wet cloth.

It may lead to electric shocks or fire.



Mandatory

| Turn off the power immediately in case of any abnormalities such as smoke, smell or abnormal noise.

Neglect of these conditions may lead to fire. For repairs, call your sales/repair agency.

Do not touch the sharp portions (such as leads of parts on the board, the corner of board, or etc.) on this option.

It may lead to injuries.

  Caution


Mandatory

| This option is an electrostatic discharge sensitive device. Handle it, where the environment is protected against electrostatic electricity.

Otherwise, permanent damage to device will result.

Transportation and installation

  Warning



Prohibited

| Do not apply a dropping shock or other physical shocks. Otherwise, damage or malfunction will result.

Do not install or operate the inverter if it is damaged or any part of it is missing. Operating a defective inverter may lead to electric shocks or fire.

For repairs, call your sales/repair agency.

Do not put any flammable material near the product.

It may catch fire due to the product sparking in the case of a malfunction.

Mandatory| Use this product under the environmental conditions prescribed in the instruction manual.

Usage it under any other conditions may result in malfunction.

An emergency stop device must be installed that fits with system specifications (e.g. shut off input power then engage mechanical brake).

Operation cannot be stopped immediately by the inverter or this unit alone, thus risking

an accident or injuries.

Wiring

  Caution

Mandatory| Electrical construction work must be done by a qualified expert.

Connection of input power by someone who does not have expert knowledge may result in electric shocks or fire.

Turn off input power before wiring.

Wait at least 15 minutes and make sure that the charge lamp (on the inverter unit) is no longer lit. Otherwise, it may lead to electric shocks.

Tighten the screws on the terminal blocks to the specified torque when connecting cables to terminal blocks.

Otherwise, it may lead to fire.

Operations

  Warning


Prohibited

| Do not pull on the cable and connector. It may cause damage or malfunctions.
Mandatory| Use this option under the environment specified in the instruction manual.

Usage under the environment other than them may cause damages or malfunctions or an accident.

Use an additional safety device with your inverter or system to prevent a serious accident due to the unit malfunctions.

Usage without an additional safety device may cause an accident.

  Caution
Mandatory| Set up “Communication error trip function (see below)” to stop the inverter when the option unit is deactivated by an unusual event such as an operating error, power outage, failure, etc.

– Network time-out ( f832 )

(See the VF-PS1 APOGEE® FLN Communication Function Manual for details.) Deactivated option unit may cause an accident, if the “Communication error trip function” is not properly set up.

Make sure that the operation signals are STOP before resetting inverter’s fault. The

motor may suddenly start and that may result in injuries.

Disposal

  Caution

Mandatory| If you dispose off this unit, have it done by a specialist in industrial waste disposal*. Improper disposal may result in explosion of capacitors or produce noxious gases, resulting in injuries.

(*) Persons who specialize in the processing of waste and known as “Industrial Waste Product Collectors and Transporters” or “Industrial Waste Disposal Persons.” If the collection, transport and disposal of industrial waste is done by someone who is not licensed for that job, it is a punishable violation of the law (Laws in regard to cleaning

and processing of waste materials).

Notes on operation

Notes

| Avoid installing in a place where ambient temperature or/and humidity change sharply. Keep the transmission cable separate from the power cable of the inverter to prevent the inverter from malfunctioning due to electromagnetic noise.

Ground of SCR terminal on this option at the grounding terminal separated from those of inverters and motors. It may cause malfunction due to noise.

Preface

Thank you for purchasing the “APOGEE® FLN option (APG001Z)” for TOSVERT VF-PS1 inverter. By Installing this board into the VF-PS1, data communication can be made with a host computer or other device via APOGEE® FLN network.
Before using this unit, carefully read this instruction manual in order to completely and correctly utilize excellent performance of this unit. Besides this instruction manual, the “APOGEE® FLN option Function Manual” which includes the contents to install into APOGEE® FLN network is prepared. If it is required, please contact with our branch offices, sales offices or web site
www.inverter.co.jp”.
(“APOGEE® FLN option Function Manual”: E6581542)
After reading this instruction manual, please keep it handy for future reference.

  • APOGEE® FLN is a registered trademark of Siemens Building Technologies, Inc.

TOSHIBA-APG001Z-TOSVERT-VF-PS1-Series-AP-08

  • Accessory check list
    APOGEE® FLN communication option is shipped together with the following accessories. On
    opening the packing case, check to see if the following accessories are contained or not.

APOGEE® FLN option (APG001Z)……. 1 board
Connector: MSTB2.5/4-STF-5.08

Manufactured by PHOENIX CONTACT
Instruction manual for the VF-PS1 APOGEE® FLN option …..1 copy

English: E6581541
(This manual)  (4) LED name label 1 sheet

Overview

The APOGEE® FLN interface (APG001Z) allows the VF-PS1 inverter to be connected into a APOGEE® FLN network.
APG001Z is applicable for VF-PS1 software version V620 or later.

Names and functions

The drawing below shows names and functions of main parts.

Outline

TOSHIBA-APG001Z-TOSVERT-VF-PS1-Series-AP-12

APOGEE® FLN Connector
Terminal symbol Function Electrical specifications Internal circuits
B APOGEE® FLN communication signal EIA-485 Communication signal (+)

TOSHIBA-APG001Z-TOSVERT-VF-PS1-Series-AP-13
A| Communication signal (-)
GND| Signal common
SCR| Shield terminal.

LED indicator

The LED shows the present status of the network and error.

TOSHIBA-APG001Z-TOSVERT-VF-PS1-Series-AP-14The option has two LEDs. Those function are below table. TOSHIBA-APG001Z-
TOSVERT-VF-PS1-Series-AP-15

State LEDs Comment
A COM LED: OFF

ERR LED: Flashing 5 times in 1 second

| APG001Z failure.

B

| COM LED: OFF

ERR LED: 3 times in 2 seconds, OFF for 1 second

| Communication loss was detected. Confirm the network condition and connection of the cable.

C

| COM LED: ON

ERR LED: OFF 0.5s, ON 0.5s

| Invalid configuration was detected. (Note)When inverter occurred in e-23 or e-24 , the LED becomes this state.
D| COM LED: Flashing ERR LED: –| Valid message was received for this node
E| COM LED: –

ERR LED: Flashing

| Invalid message was node)| received| (any

| COM LED: OFF ERR LED: OFF| No communication Confirm the network connection of the cable.|

condition

|

and

Installing the APG001Z

Install the APOGEE® FLN option to VF-PS1 as follows.

Mandatory| Turn off the input power of VF-PS1 and wait for at least 15 minutes and then check that the CHARGE lamp on VF-PS1 is no longer lit.
---|---

  1. Turn off input power of VF-PS1 and wait for at least 15 minutes and then check that the CHARGE lamp on VF-PS1 is no longer lit.
  2. Securing the option to the inverter
    • Insert a flat-blade screwdriver in each of the two holes at the upper part of the front panel, release the panel mounting tab by pushing the screwdriver down and remove the front panel cover.
    • Install the option in the inverter by fitting the tabs on the lower side the option into the slots at the lower part of the inverter front panel.
    • Make sure the option is securely attached to the inverter. Then check whether the plastic bosses on the inverter case have fitted in the holes at the upper and lower parts of the option.
    • Insert the tabs at the lower part of the front cover into the slots at the lower part of the inverter to attach the front cover to the inverter.
    • Stuck the enclosed “LED name label” in the option LED display part of a front cover.

TOSHIBA-APG001Z-TOSVERT-VF-PS1-Series-AP-16

Case of installing two options

Please install this option (APG001Z) on the top of options when you install two options. Do not install under the another option.

Network cable connection

Connect the APOGEE® FLN network cable to communication option as follows.

Title Description
Wire type Shielded twisted cable
Characteristic impedance Between 100 and 130 ohm
Distributed impedance between conductors Less than 100pF per meter
Distributed impedance between conductors and shield Less than 200pF per meter

Foil or braided shield are acceptable.

Length of a segment| 1200 meters with AWG18 (0.8mm2)

TOSHIBA-APG001Z-TOSVERT-VF-PS1-Series-AP-17Cable sheath should be peeled off by about 7mm.
For wiring work, use a flat blade screwdriver with a 0.6mm thick and 3.5mm width blade.
Tightening torque for the terminal block is 0.5Nm.

  • Fix a cable so that a communication connector may be not taken the weight of wire.
Network configuration

Make up the network as follows.

  • Transmission/reception signals (A, B)
    Make up the communication path by connecting all transmission/reception data cables.

  • Signal common (GND)
    GND is the signal common.

  • Grounding the shield of cable (SCR)
    Connect the all shield lines of network cable. The shield shall be grounded at one end only prevent currents from being created.

  • Termination resistor
    A termination resistance of 120 ohms plus or minus 5% shall be connected at each of the two ends of the segment medium. This option has a termination resistor, so if use, set up the termination resistor SW. (Refer to 2.1 Outline)

  • It is recommended that the Siemens Building Automation FLN Trunk Terminator (PN: 538-664) be used and that the network termination switch on the APG001Z, SW102, be set to OFF.
    At least one set, and no more than two sets, of network bias resistors shall exist for each segment. This option has local bias resistors.

TOSHIBA-APG001Z-TOSVERT-VF-PS1-Series-AP-18 N.B.: Do not connect the SCR terminal to the power ground of inverters or other units.

Keep the network cables 20cm or more separate from the power cables to prevent from malfunctioning due to electromagnetic noise.

Parameters

Communication parameters

Set up the inverter parameters as follows. To update, reset of inverter. If these parameters are not set to correct value, this unit can not work normally.

Title Communication No. Function Description Factory setting
f831 0831 Network Baudrate    (*1) 0: 9600bps,1: 4800bps,2: 9600bps 3:

19200bps,4: 38400bps,
5: 57600bps,6: 76800bps
Over 7 is 9600bps.| 0000
f832| 0832| Network Time-Out (1)| 0: No action
Unit 0.1 sec, Setting range: 1 – 1000 Over 1000 is 100.0s.| 0000
f833| 0833| Factory setting    (
1)| Except ACh:Reset to factory setting ACh:Finished with reset to factory setting| 0000 (ACh)
f834| 0834| Station address| 1-99 _
_The range outside is converted into 99| 0000
f851| 0851| Operation at communication error by disconnection| 0 : Inverter stop, communication command, frequency mode open (by cmod, fmod)

  1. None (continued operation)
  2. Deceleration stop
  3. Coast stop
  4. Network error (err8 trip)
  5. Preset speed operation (by f852 setting)

| 0
f852| 0852| Preset speed operation selection| 0:None

1~15:Preset speed operation (by parameter setting)

| 0
f853| 0853| Communication option station address monitor (Read Only)| Real station address monitor

If a value of f834 is out of a range, the value of f853 becomes 99.

|

f899| 0899| Network option reset setting| 0:None
1:Reset option circuit board and inverter| 0
-| FE66| Add-on option 1 CPU version(Under side option)| High byte is version Low byte is revision. For example, When version number 1, and revision number 2 is, panel indication becomes with 1.02.

The version of the option with it has equipped can be checked by using the function of f710 to f718 (standard monitor display selection).

*For details, refer to the inverter instruction manual.

| -
-| FE67| Add-on option 2 CPU version(Panel side)| -

  • When fn0d or cn0d is set to “Communication option input”, VF-PS1 drives without FLN LOC REF (LDO point #69) or FLN LOC CTL (LDO point #68) at each Objects.
    (*1): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.

Command & Setpoint selection (Local/Remote)

Indication to display Local/Remote mode is on the inverter unit (Refer to the inverter instruction manual for details). APOGEE® FLN option command and setpoint are activated on Remote mode.

Inverters have some switches to select the command and setpoint location. Following figure shows the diagram. Refer to the inverter instruction manual for the parameter in detail. TOSHIBA-APG001Z-TOSVERT-VF-PS1-Series-
AP-19Be careful that cn0d command and fn0d setpoint are activated for a short time just after the inverter power turned on. Set cmod and fmod to “network” to prevent this problem.

< Example>

The example below shows how to configure the VF-PS1 for local/remote operation.
F terminal………………… Operating command
R terminal ………………..The APOGEE® FLN local/remote (Terminal in this example) switching
RR/S4 terminal………. Operation frequency command

< Wiring>

TOSHIBA-APG001Z-TOSVERT-VF-PS1-Series-AP-20

< Parameter setting>
cn0d(Command mode selection) = 0 (Terminal board)
fn0d(Frequency setting mode selection 1) = 2 (RR/S4) f112(Input terminal selection 2 (R)) = 48 (Remote/Local control)

< Operation>
R-CC terminal open: VF-PS1 is controlled as a slave device of The APOGEE® FLN.
R- CC terminal closed:
F- CC terminal short to RUN
F-CC terminal open to STOP
Output frequency is set up by the RR/S4 signal input.

(Note)
When the local(HAND) / remote key (f750=2) is chosen as EASY key selection and the EASY key lamp of an inverter front panel is on, priority is most given to operation by a panel. (Refer to the inverter instruction manual for details).
Note that the HAND mode of the panel has priority over FLN local control.

Specifications

< Environmental specification >
Item Specification
Model number APG001Z
Service environment Conforms to VF-PS1
Ambient temperature Conforms to VF-PS1
Storage temperature Conforms to VF-PS1
Relative humidity Conforms to VF-PS1
Vibration Conforms to VF-PS1
Power supply 24VDC supplied from the inverter
Item Specification
Station type Remote device station
Number of occupied stations 1 station occupied by 1 unit
Maximum FLN device 32 FLN devices to each FLN port of the Field Cabinet.
Communication baud rate 4800, 9600, 19200, 38400, 57600, 76800bps
Bias resistor and termination Local bias resistors are mounted.

Termination resistor (120 ohm) can be select by SW.

Terminal block| Detachable terminal block 4-pole (5.08mm pitch) Manufacturer: PHOENIX CONTACT

Type-Form    : MSTB 2,5/4-STF-5.08

Warranty

Any part of APOGEE® FLN communication option that is proved to be defective will be repaired free of charge under the following conditions:

  1. This product will be repaired free of charge, if problem/fault occurs under normal handling within one year of delivery and is caused obviously by a design or manufacturing defect.
  2. The warranty applies only to the delivered product.
  3. For the following kinds of failure or damage, the repair cost shall be borne by the customer even within the warranty period.
    • Failure or damage caused by improper or incorrect use or handling, or unauthorized repair or modification of the inverter.
    • Failure or damage caused by the unit falling or an accident during transportation after the purchase.
    • Failure or damage caused by fire, salty water or wind, corrosive gas, earthquake, storm or flood, lightning, abnormal voltage supply, or other natural disasters.
    • Damage due to the use of APOGEE® FLN communication option for non-intended purposes.
  4. If an additional warranty is provided then those conditions will also apply.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>