DOLD SL 5881 VARIMETER IMD Insulation Monitor Installation Guide
- June 3, 2024
- DOLD
Table of Contents
VARIMETER IMD
Insulation Monitor
IL 5881, SL 5881
Translation of the original instructions
Installation / Monitoring Technique
Function Diagram
IL 5881/100, SL 5881/100; IL 5881, SL 5881
-
With reference to IEC/EN 61557-8 (see also section “Notes”)
-
For DC voltage systems up to 12 … 280 V
-
Wide voltage range of measuring input UN DC 12 … 280 V (on request DC 24 … 500 V with separate auxiliary supply, Measuring range 20 … 500 kΩ)
-
Adjustable tripping value RAL of 5 … 200 kΩ or 10 … 500 kΩ
-
Selective ground fault indication for L+ and L- allows fast fault finding
-
Without auxiliary supply
-
De-energized on trip
-
2 changeover contacts
-
Automatic or manual reset, programmable
-
With test and reset buttons
-
Connection for external test and reset button possible
-
Galvanic separated AC or DC auxiliary supply available as option
-
Adjustable time delay as option
-
2 models available:
IL 5881: 61 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880
SL 5881: 98 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts -
DIN rail or screw mounting
-
35 mm width
Approvals and Markings
Application
- Monitoring of asymmetrical insulation resistance of ungrounded DC-voltage systems to earth.
- For industrial and railway applications
Function
If the insulation resistance RE between L+ or L- to ground drops below the
adjusted alarm value RAL (insulation failure) the corresponding red LED goes
on and the output relay switches off (de-energized on trip). If the unit is on
auto reset (bridge between LT-X1) and the insulation resistance gets better
(RE rises), the insulation monitor switches on again with a certain hysteresis
and the red LED goes off.
Without the bridge between LT-X1 the insulation monitor remains in faulty
state even if the insulation resistance is back to normal. The location of the
fault on L+ or L- is indicated on the corresponding LED (selective fault
indication).
The reset is done by pressing the internal or external reset button or by
disconnecting the auxiliary supply.
By activating the “Test” button internal or external an insulation failure can
be simulated to test the function of the unit.
Indicators
Green LED “ON”: | On, when supply voltage connected |
---|---|
Red LED “RE+”: | On, when insulation fault detected (RE+< RAL) on L+ |
Red LED “RE-“: | On, when insulation fault detected (RE <RAL) on L- |
Circuit Diagrams
Connection Terminals
Terminal designation | Signal description |
---|---|
A1 | L / + |
A2 | N / – |
L+, L- | Connection for monitored IT-systems |
PE | Connection for protective conductor |
PT, X1 | Connection for external test button |
LT, X1 | Connections for external reset or manual and auto reset: |
LT/X1 bridged: Hysteresis function
LT/X1 not bridged: Manual reset
11, 12, 14, 21, 22, 24| Changeover contact (insulation failure)
Notes
WARNING
Risk of electrocution!
Danger to life or risk of serious injuries.
- Disconnect the system and device from the power supply and ensure they remain disconnected during electrical installation.
- The terminals of the control input PT, LT1 und X1 have no galvanic separation to the measuring circuit L+/L- and are electrically connected together, therefore they have to be controlled by volt free contacts or bridge. These contacts ore bridges must provide a sufficient separation depending on the mains voltage on L+/L-.
- No external potentials may be connected to external control terminals PT, LT1 und X1.
Attention!
- Before checking insulation and voltage, disconnect the insulation monitor IL/SL 5881 from the power source!
- In one voltage system only one insulation monitor can be used. This has to be observed when interconnecting two separate systems.
- According to IEC/EN 61 557-8 insulation monitors must be able to monitor the isolation resistance of the IT-system including symmetric and none symmetric occurance of the isolation resistance. Because of the measuring principle with a resistor bridge (asymmetry principle) the insulation monitor IL/SL 5881 will not detect symmetric ground faults of L+ and L-. Also a voltfree (disconnected UN = 0V) system cannot be monitored.
If the monitoring of symmetrical insulation resistances in ungrounded DC systems is required, the RL 5881 insulation monitor, for example, is suitable.
Attention!
-
The IL/SL 5881 can be used in systems with high leakage capacity to ground. When the unit is adjusted to high alarm values a leakage capacity can create a pulse when switching the system on (short alarm pulse).
This happens at the following values:
IL / SL 5881: RAL = 200 kΩ: CE > 1 µF
IL / SL 5881: RAL = 50 kΩ: CE > 6 µF
IL / SL 5881: RAL = 20 kΩ: CE > 16 µF
IL / SL 5881/100: RAL = 500 kΩ: CE > 0.8 µF
IL / SL 5881/100: RAL = 200 kΩ: CE > 0.8 µF
IL / SL 5881/100: RAL = 50 kΩ: CE > 2.0 µF
IL / SL 5881/100: RAL = 20 kΩ: CE > 4.5 µF
An optional time delay (on request) could suppress this pulse. -
On models with separate auxiliary supply the alarm state is not defined when the voltage drops below 3 V. To avoid false alarm an additional auxiliary relay should be used which is connected to the monitored voltage or the variant IL 5881.12/010 is used.
-
On the models with galvanic separation between DC auxiliary supply and measuring input, the supply (A1/A2) can be connected to the monitored voltage system (L+/L-). The voltage range of the auxiliary input must be noticed which is only 1.25 of UH while the measuring input always goes up to 280 V. If no auxiliary supply is available the model IL/SL 5881/100 (without auxiliary supply) can be used which takes the auxiliary supply from the monitored system (UH = UN = DC 12 … 280 V).
Technical Data
Auxiliary Circuit
(only at IL/SL 5881)
Auxiliary voltage UH:| AC 220 … 240 V, 380 … 415 V
DC 12 V, 24 V
DC 24 … 60 V
---|---
Voltage range:
AC:
DC:| 0.8 … 1.1 UH
0.9 … 1.25 UH
Frequency range (AC):| 45 … 400 Hz
Nominal consumption
AC:
DC:| Approx. 2 VA
Approx. 1 W
Measuring Circuit
| Standard| extended, on request
---|---|---
Nominal voltage UN at| |
≤ 5 % residual ripple:| DC 12 … 280 V| DC 24 … 500 V
≤ 48 % residual ripple:| DC 12 … 220 V|
Voltage range:| |
Alarm value RAL:| 1.) 5 … 200 kΩ| 20 … 500 kΩ
| 2.) 10 … 500 kΩ|
Setting RAL:| infinite setting| infinite setting
Internal DC resistance| 1.) each appr. 75 kΩ| each approx.
L+ and L- to PE:| 2.) each appr. 100 kΩ| 190 kΩ
Max. meas. current at PE (RE = 0):| 1.) UN / 75 kΩ
2.) UN / 100 kΩ| UN / 190 kΩ
Operate delay
RE
from ∞ to 0.9 RAL:| Approx. 0.8 s|
---|---|---
RE from ∞ to 0 kΩ:| Approx. 0.4 s|
Response inaccuracy:| ± 15 % + 1.5 kΩ| IEC 61557-8
Hysteresis
At RAL = 50 kΩ:| Approx. 10 … 15 %|
Time delay:| 0.5 … 20 s (variant)|
Output
Contacts:
IL / SL 5881.12:| 2 changeover contacts| .
Thermal current Ith:| 4:00 AM|
Switching capacity
To AC 15:| 3 A / AC 230 V| IEC/EN 60947-5-1
Switching capacity
To DC 13:| 2 A / DC 24 V|
0.2 A / DC 250 V| IEC/EN 60947-5-1
Electrical life
To AC 15 at 1 A, AC 230 V:| ≥ 2 x 10 5 switching cycles| IEC/EN 60947-5-1
Short circuit strength
max. fuse rating:| 4 A gG / gL| IEC/EN 60947-5-1
Mechanical life:| ≥ 10 x 10 6 switching cycles|
General Data
Operating mode: | Continuous operation |
---|
Temperature range
Operation:| – 20 … + 60°C
Storage:| – 20 … + 60°C
Altitude:| ≤ 2000 m
Clearance and creepage distances
Rated impulse voltage / pollution degree between auxiliary supply| 4 kV / 2 at
AC-auxiliary voltage| IEC 60664-1
---|---|---
Between measuring input connections (L+ / L- / PE):| 4 kV / 2| IEC 60664-1
Between auxiliary supply and measuring input
connections:| 4 kV / 2| IEC 60664-1
Input to output(contacts):| 6 kV / 2| IEC 60664-1
EMC
Electrostatic discharge: | 8 kV (air) | IEC/EN 61000-4-2 |
---|
HF irradiation:
80 MHz … 1 GHz:| 12 V / m| IEC/EN 61000-4-3
1 GHz … 2.7 GHz:| 10 V / m| IEC/EN 61000-4-3
Fast transients:| 2 kV| IEC/EN 61000-4-4
Surge voltages
Between A1 – A2 and L+ – L-:| 1 kV| IEC/EN 61000-4-5
Between A1, A2 – PE and L+, L- – PE:| 2 kV| IEC/EN 61000-4-5
HF-wire guided:| 10 V| IEC/EN 61000-4-6
Interference suppression:| Limit value class B| EN 55011
Degree of protection
Housing:| IP 40| IEC/EN 60529
Terminals:| IP 20| IEC/EN 60529
Housing:| Thermoplastic with V0 behaviour according to UL Subjekt 94
Vibration resistance:| Amplitude 0.35 mm frequency 10 … 55 Hz| IEC/EN
60068-2-6
Climate resistance:| 20 / 060 / 04| IEC/EN 60068-1
Terminal designation:| EN 50005|
Wire connection:| DIN 46228-1/-2/-3/-4|
Cross section:| 2 x 2.5 mm² solid or 2 x 1.5 mm² stranded wire|
Stripping length:| 10 mm|
Fixing torque:| 0.8 Nm|
Wire fixing:| Flat terminals with self-lifting clamping piece| IEC/EN 60999-1
Mounting:| DIN rail mounting (IEC/EN 60715) or screw mounting M4, 90 mm hole
pattern,
with additional clip available as accessory
Weight
IL 5881:| Approx. 170 g
SL 5881:| Approx. 200 g
Dimensions
Width x height x depth:
IL 5881: | 35 x 90 x 61 mm |
---|---|
SL 5881: | 35 x 90 x 98 mm |
Classification to DIN EN 50155 for IL 5881
Vibration and
shock resistance:| Category 1, Class B| IEC/EN 61373
---|---|---
Ambient temperature:| T1 compliant
T2, T3 and TX with operational limitations
Protective coating of the PCB:| No
Standard Types
IL 5881.12/100 DC 12 … 280 V 5 … 200 kΩ
Article number: 0053805
- Without auxiliary supply UH
- Nominal voltage UN: DC 12 … 280 V
- Adjustable alarm value RAL: 5 … 200 kΩ
- Width: 35 mm
SL 5881.12/100 DC 12 … 280 V 5 … 200 kΩ
Article number: 0055168
- Without auxiliary supply UH
- Nominal voltage UN: DC 12 … 280 V
- Adjustable alarm value RAL: 5 … 200 kΩ
- Width: 35 mm
Variants
IL / SL 5881.12: | With auxiliary supply |
---|---|
IL / SL 5881.12/010 | With auxiliary supply no alarm at UN < 3 V |
IL / SL 5881.12/300 | Without auxiliary supply |
Nominal voltage UN DC 12 … 280 V closed circuit operation
Time delay 0.5 … 20 s
IL / SL 5881.12/800:| Special low resistance range for the threshold value
with limitation of the
voltage range:
Article number:| 56910| 56911
---|---|---
Nominal voltage UN at ≤ 5 % residual ripple:| DC 12 … 110 V| DC 12 … 24 V
Voltage range:| 0.8 … 1.25 UN| 0.8 … 1.25 UN
Alarm value RAL:| 1 … 50 kΩ| 0.2 … 10 kΩ
Setting RAL:| infinite setting| infinite setting
Internal AC resistance
L+ and L- to PE:| each approx.
18.5 kΩ| each approx.
2.8 kΩ
Max. meas. current at PE (RE = 0):| UN / 18.5 kΩ| UN / 2.8 kΩ
Ordering example for variants
Accessories
ET 4086-0-2:| Additional clip for screw mounting
Article number: 0046578
---|---
Connections Examples
Monitoring of an ungrounded system.
1) Auxiliary supply UH (A1-A2) can be taken from monitored voltage system. The range of the auxiliary supply input must be observed.
2) With bridge LT – X1: Automatic reset
Without bridge LT – X1: Manual reset, reset with button LT
Monitoring of an ungrounded system without auxiliary supply.
*2) With bridge LT – X1: Automatic reset
Without bridge LT – X1: Manual reset, reset with button LT
All technical data in this list relate to the state at the moment of edition. We reserve the right for technical improvements and changes at any time.
E. Dold & Söhne GmbH & Co. KG • D-78120 Furtwangen
Bregstraße 18 • Phone +49 7723 654-0 • Fax +49 7723 654356
dold-relays@dold.com •
www.dold.com
17.02.22 en / 512A
Documents / Resources
| DOLD
SL 5881 VARIMETER IMD Insulation
Monitor
[pdf] Installation Guide
IL 5881, SL 5881, SL 5881 VARIMETER IMD Insulation Monitor, VARIMETER IMD
Insulation Monitor, VARIMETER IMD, Insulation Monitor
---|---