DOLD ND 5014 Split Current Transformer Installation Guide
- June 14, 2024
- DOLD
Table of Contents
Translation
of the original instructions
Installation- / Monitoring Technique
VARIMETER RCM
Split Current Transformer
ND 5014
ND 5014 Split Current Transformer
Your Advantages
- Easy mounting
- Simple retrofitting in existing plants
Features
- According to IEC 61869-1 and IEC 61869-8
- Measurement according to IEC/EN 62020, for AC and DC systems Type A
- Up to 30 A
- Vertical and horizontal mounting to DIN-rail
- ND 5014/120 also with screw fastening
Product Description
The split current transformers ND5014 are suitable for differential current
measurement in conjunction with a DOLD differential current monitor Il 5882,
SL 5882 and IP 5882 for AC and pulsating DC current. Opening the CT makes it
easy to install them to the current leading conductors. They are especially
suitable for retrofit, as the wires do not need to be disconnected.
The split current transformers are available in 3 sizes with through hole
diameters of 49, 79 and 119 mm.
For differential current measurement all current conducting wires run through
the CT with exception of the PE wire.
Normally we have rather low currents that are monitored between 10 mA and 30
A.
Connection Terminals
Terminal designation | Signal designation |
---|---|
i, i, k, k | Connecting the current transformer to the Residual Current Monitor |
IL 5882, SL 5882 or IP 5882 (i and k are double present)
Application
Measuring current transformers for monitoring differential currents in combination with DOLD Residual Current Monitors IL 5882, SL 5882 and IP 5882.
Note
The split current transformer is only designed for operation together with the
residual current monitors IL 5882 and SL 5882 from E. Dold & Söhne GmbH & Co.
KG.
Technical Data
Ambient temperature:
Inflammability class:| – 40 … + 80 °C / 233 K … 353 K
V0 according to UL94
---|---
Insulation coordination according to IeC 61869-1
Highest rated operating voltage Um :
Rated impulse voltage:
Rated impuls voltage / pollution degree:| AC 720 V
3 kV
8 kV / 3
rated transformation ratio:
Rated primary current:
Nominal load:
Accuracy:| 500 / 1
10 A
50 mVA
Class 3
Wire connection
Wire cross section:| 0.2 … 2.5 mm 2 rigid / 0.2 … 2.5 mm 2 flexible / AWG
24 … 12
Stripping length:| 6 mm
Wire fixing:| Terminals with spring connection and direct (Push in) technology
Actuating force:| 40 N max.
Mounting
DIN rail mounting:| Vertical and horizontal mounting on enclosed socket
ND 5014/120:| Screw fastening also possible
Order references
ND 5014/050
Article number:
• Diameter:| 0068614
49 mm
---|---
ND 5014/080
Article number:
• Diameter:| 0068613
79 mm
ND 5014/120
Article number:
• Diameter:| 0068565
119 mm
Dimensions
ND 5014/050 | A | B | C | D | E | F |
---|---|---|---|---|---|---|
Dimension/mm | 160 | 49 | 30 | 77 | 200 | 116 |
Weight / g | Approx. 380 | |||||
ND 5014/080 | A | B | C | D | E | F |
Dimension/mm | 204 | 79 | 30 | 108 | 260 | 156 |
Weight / g | Approx. 850 | |||||
ND 5014/120 | A | B | C | D | E | F |
Dimension/mm | 252 | 119 | 30 | 149 | 328 | 204 |
Weight / g | Approx. 1500 |
*) Drill tolerance for screw mounting:± 0.5mm
Dimensions Socket
Socket included in the delivery !
Mounting – Srew fixing at ND 5014/120
Screws are not included in the delivery !
Mounting instructions for srew fixing
To high forces applied during installation can damage the transformer on the
mounting foots.
The mounting foots are only designed to fix the transformer. Forces that are
applied to the CT by the conductors can only be supported within limitations.
When installing the CT, the conductors should be lead free through the
transformer and should later stay in that position.
Wiring Information
- The hinged cover protects the push-in terminal block and avoids unintended disconnection of the wiring
- The push-in terminal block provides easy mounting
- Stripping length: 10 mm
Connecting capacity: 0.2 …. 2.5 mm 2
E. Dold & Söhne GmbH & Co. KG • D-78120 Furtwangen
• Bregstraße 18 • Phone +49 7723 654-0 • Fax +49 7723 654356
dold-relays@dold.com • www.dold.com
All technical data in this list relate to the state at the moment of edition.
We reserve the right for technical improvements and changes at any time.
09.03.23 en / 703A
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>