Product Description

The Staircase lighting time switch IK 8810/003 of the MINITIMER series has an adjustable runningtime andcan be switched tocontinuous lightning by means of a slide switch.

Function Diagram

DOLD IK 8810-00 Staircase Lighting Time Switch - parts

Circuit Diagram

Connection Terminals

Terminal designation Signal description
L Phase voltage
N Neutral
T Control input for buttons
18 Output contact

Your Advantages

  • Energy saving
  • Increase of the service life of the lamps

Features

  • According to EN 60669-1, EN 60669-2-1
  • Setting range short pressing of button 0.5 … 10 min long pressing of button 2 … 40 min
  • For 4-wire circuit L on push button and 3-wire circuit N on push button
  • Can be retriggered
  • With pre-warning shortly before end of time
  • Switch for continuous light on unit
  • Contact: 16 A
  • Width 17.5 mm

Approvals and markings


Application
Time delayed switching off for lights
Function
If the button is pressed longer then 1 s the adjusted time will be multipied by 4, the timing is retriggerable i.e. if the pushbutton is pressed again during timing the adjusted delay time starts again without interruption.
Approx. 30 s before end of timing the light flashes shortly to indicate that the light will go off.

Indication

LED: On when output relay activated
Notes
Unit and push button have to be connected to the same phase (see connection diagram) The output contact is not volt free.

Technical Data

Time Circuit

Time range: At push < 1 s: 0.5 … 10 min at push > 1 s : 2 … 40 min

Repeat accuracy: < 1 % of setting value
Input

nominal voltage UN: AC 230 V
Voltage range: 0.8 … 1.1 UN

Nominal consumption
apparent power:
effective power:| 4 VA
1 W
nominal frequency:| 50 / 60 Hz
ermitted residual current caused by glow lamps in the push buttons| max. 10 glow lamps à 1 mA

Output

Contacts: 1 NO contact, delay
Contact opening gap: < 3 mm
Thermal current Ith: 16 A

Switching capacity at lamp load
Glow lamp load:| 1200 W at Tein / Taus = 1 s / 1s
Short circuit strength
max. fuse rating:
mechanical life:| 16 A gG / gL IEC/EN 60947-5-1

10 6 switching cycles

General Data

nominal operating mode: Impulse operation

Temperature range
Operation:| – 20 … + 60 °C
Storage:| – 20 … + 70 °C
Altitude:| ≤ 2000 m
Clearance and creepage distances
Rated impulse voltage /
pollution degree:| 4 kV / 2| IEC 60664-1
emC
Electrostatic discharge (ESD):| 8 kV (air)| IEC/EN 61000-4-2
HF-irradiation:
80 MHz … 2.7 GHz:| 10 V / m| IEC/EN 61000-4-3
Fast transients:| 2 kV| IEC/EN 61000-4-4
Surge voltages
between
wires for power supply:| 2 kV| IEC/EN 61000-4-5
between wire and ground:| 4 kV| IEC/EN 61000-4-5
HF wire guided:| 10 V|  IEC/EN 61000-4-6
Interference suppression:| Limit value class B| EN 55011
Degree of protection
Housing:| IP 40| IEC/EN 60529
Terminals:| IP 20| IEC/EN 60529
Housing:| Thermoplast with V0-behaviour according to UL subj. 94
Vibration resistance| Amplitude 0.35 mm frequenzy 10 … 55 Hz| IEC/EN 60068-2-6
Climate resistance:| 20 / 045 / 04| IEC/EN 60068-1
Terminal designation:| EN 50005
Wire connection:| DIN 46228-1/-2/-3/-4
Cross section:| 2 x 2.5 mm2  solid or 2 x 1.5 mm 2  stranded wire with sleeve
Insulation of wires or
sleeve length:| 10 mm
Wire fixing:| Flat terminals with self-lifting clamping piece| IEC/EN 60999-1
Fixing torque:| Max. 0.8 Nm
mounting:| DIN rail| IEC/EN 60715
Weight:| 75 g

Dimensions

Width x Height x Depth: 17.5 x 90 x 58 mm

Standard Type

IK 8810.41/003 AC 230 V 50 / 60 Hz 0.5 … 10 min / 2 … 40 min
Article number: 0057584

  • Output: 1 NO contact, delay
  • Nominal voltage UN : AC 230 V
  • Timer range: 0.5 … 10 min / 2 … 40 min
  • Width: 17.5 mm

Ordering example

DOLD IK 8810-00 Staircase Lighting Time Switch -
parts2

Characteristic

Application examples

3-wire circuit N on push button 4-wire circuit L on push button
All technical data in this list relate to the state at the moment of edition. We reserve the right for technical improvements and changes at any time.

E. Dold & Söhne GmbH & Co. KG
D-78120 Furtwangen
Bregstraße 18
Phone +49 7723 654-0
Fax +49 7723 654356
dold-relays@dold.com 
www.dold.com
13.07.23 en / 761A

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals