Schneider Electric A9MEM152 Wireless Communication Energy Sensor Instructions
- June 3, 2024
- Schneider Electric
Table of Contents
Schneider Electric A9MEM152 Wireless Communication Energy Sensor
- Refer to the concentrator’s user manual to configure your system.
- Wireless-communication energy sensors for Acti9 and Multi9 modular equipment ranges
- This instruction sheet must be kept for future use.
- Visit our websitewww.schneider-electric.com to download the technical documents for Acti9 products.
PLEASE NOTE
-
PowerTap devices must only be installed and maintained by qualified professionals.
-
PowerTap devices should not be installed if, while unpacking, any damage is observed.
-
The PowerTap devices must be installed inside electrical panels or switchboards, behind a door or plate, so that they are inaccessible to unauthorized persons. The electric panels must meet the requirements of the applicable standards (IEC 61439-1) and be installed in compliance with current installation and safety rules
(IEC 61140). -
All relevant local, regional, and national regulations must be respected while installing and using PowerTap devices.
-
Schneider Electric declines any responsibility in the event that PowerTap equipment is associated with equipment that is not listed in the document CA908058E.
-
Schneider electric is not liable in case the instructions mentioned in this document and other referred documents are not respected.
DANGER
- HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
- Turn off all power supply sources before installing and during maintenance of this equipment.
- Do not use a PowerTag product for voltage testing purposes. A Voltage Tester must be used instead. Failure to follow these instructions will result in death or serious injury.
Description
- Power-supply and Voltage measurement connections.
- Product label.
- The detachable adhesive part carries a unique product identifier, useable during commissioning on certain concentrators.
- Conductor feedthroughs for current measurement.
- Comply with all safety instructions associated with this symbol to avoid any potential risk of injury or death.
- PowerTag communication status indicator light.
- Refer to the selection guide of PowerTap devices with Acti9 and Multi9 devices – CA908058E.
- Before proceeding with pairing, ensure that the concentrator has the latest available software version. Refer to the user manual of the concerned concentrator.
en Communication indicator light |
---|
PowerTap status
|
PowerTap switched off.
|
PowerTap is searching for a concentrator.
|
PowerTap in identification mode.
| PowerTap is in a network. Normal communication with the concentrator.
|
Occasional loss of communication.
| Loss of communication with the concentrator.
|
Internal error detected.
Installation and connection
WARNING
FIRE HAZARD
- Use an 18 mm cable end or strip over 18 mm to avoid tightening against the insulating material.
- Use the cable end to connect the neutral wire of the A9MEM1520.
- The PowerTap must be associated with an easily accessible upstream protection and circuit-breaker system, marked with callout A in the schematic below.
- This upstream
- protection and disconnection devices must be clearly identified and labeled. The electrical diagram is shown below.
- Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTICE
RISK OF DAMAGING THE POWERTAG
- Comply with the neutral position.
- Disconnect the PowerTag before performing the dielectric withstand test.
- Limit the insulation measurements up to 500 Vc. The input impedance of the PowerTag between phases or between phases and the neutral is equal to 1,8 MΩ.
- Failure to follow these instructions can result in equipment damage.
Installation
Connection
Technical data
- Nominal voltage Un: 230 V or 230/400 Va
- Operating range (power supply and voltage measurement inputs): Un ± 20%
- Frequency: 50/60 Hz
- Maximum power consumption: y 1 VA (1P+N); y 2 VA (3P/3P+N)
- Maximum current: 63 A
- Operating temperature: -25°C to +60°C
- Overvoltage and measurement category: Cat. III 300V / t
- Supports temporary surges relative to the ground
- Pollution degree: 3
- Altitude: y 2000 m
- Relative humidity: Maximum 93 % without condensation
- Impact resistance index: IK05
- For indoor use only
- Radio communication: ISM band 2.4 GHz (2.4 GHz to 2.4835 GHz) v Channels 11 to 26 (IEEE 802.15.4)
- Equivalent Isotropic Radiated Power (EIRP): 0 dBm
- Accuracy:
- Voltage: Class 0.5
- Current, Power, and Active Energy: Class 1
- Hereby, Schneider Electric Industries, declares that the wireless communication energy sensors PowerTag are in compliance with the essential requirements and other relevant provisions of RED-DIRECTIVE 2014/53/EU n°FD16090201. Declaration of conformity can be downloaded on: Schneider-electric.com/docs.
- Schneider Electric Industries SAS
- 35, rue Joseph Monier
- CS 30323
- F – 92506 Rueil Malmaison Cedex
- www.schneider-electric.com
- EAV31628-08
- © 2018 Schneider Electric – All rights reserved.
Documents / Resources
|
Schneider Electric A9MEM152 Wireless Communication Energy
Sensor
[pdf] Instructions
A9MEM152, PowerTag Acti9 M63, A9MEM152 PowerTag Acti9 M63, Acti9 M63,
A9MEM154, A9MEM152 Wireless Communication Energy Sensor, Wireless
Communication Energy Sensor, Communication Energy Sensor, Energy Sensor
---|---