Schneider Electric A9MEM152 Wireless Communication Energy Sensor Instructions

June 3, 2024
Schneider Electric

Schneider Electric A9MEM152 Wireless Communication Energy Sensor

Schneider-Electric-A9MEM152-Wireless-Communication-Energy-Sensor-
PRODUCT

  • Refer to the concentrator’s user manual to configure your system.
  • Wireless-communication energy sensors for Acti9 and Multi9 modular equipment ranges
  • This instruction sheet must be kept for future use.
  • Visit our websitewww.schneider-electric.com to download the technical documents for Acti9 products.

PLEASE NOTE

  • PowerTap devices must only be installed and maintained by qualified professionals.

  • PowerTap devices should not be installed if, while unpacking, any damage is observed.

  • The PowerTap devices must be installed inside electrical panels or switchboards, behind a door or plate, so that they are inaccessible to unauthorized persons. The electric panels must meet the requirements of the applicable standards (IEC 61439-1) and be installed in compliance with current installation and safety rules
    (IEC 61140).

  • All relevant local, regional, and national regulations must be respected while installing and using PowerTap devices.

  • Schneider Electric declines any responsibility in the event that PowerTap equipment is associated with equipment that is not listed in the document CA908058E.

  • Schneider electric is not liable in case the instructions mentioned in this document and other referred documents are not respected.

DANGER

  • HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
  • Turn off all power supply sources before installing and during maintenance of this equipment.
  • Do not use a PowerTag product for voltage testing purposes. A Voltage Tester must be used instead. Failure to follow these instructions will result in death or serious injury.

Description

  • Power-supply and Voltage measurement connections.
  • Product label.
  • The detachable adhesive part carries a unique product identifier, useable during commissioning on certain concentrators.
  • Conductor feedthroughs for current measurement.
  • Comply with all safety instructions associated with this symbol to avoid any potential risk of injury or death.
  • PowerTag communication status indicator light.
  • Refer to the selection guide of PowerTap devices with Acti9 and Multi9 devices – CA908058E.
  • Before proceeding with pairing, ensure that the concentrator has the latest available software version. Refer to the user manual of the concerned concentrator.
  en Communication indicator light

PowerTap status
|

PowerTap switched off.

|

PowerTap is searching for a concentrator.

|

PowerTap in identification mode.

| PowerTap is in a network. Normal communication with the concentrator.
|

Occasional loss of communication.

| Loss of communication with the concentrator.
|

Internal error detected.

Installation and connection

WARNING

FIRE HAZARD

  • Use an 18 mm cable end or strip over 18 mm to avoid tightening against the insulating material.
  • Use the cable end to connect the neutral wire of the A9MEM1520.
  • The PowerTap must be associated with an easily accessible upstream protection and circuit-breaker system, marked with callout A in the schematic below.
  • This upstream
  • protection and disconnection devices must be clearly identified and labeled. The electrical diagram is shown below.
  • Failure to follow these instructions can result in death, serious injury, or equipment damage.Schneider-Electric-A9MEM152-Wireless-Communication-Energy-Sensor-FIG-2

NOTICE

RISK OF DAMAGING THE POWERTAG

  • Comply with the neutral position.
  • Disconnect the PowerTag before performing the dielectric withstand test.
  • Limit the insulation measurements up to 500 Vc. The input impedance of the PowerTag between phases or  between phases and the neutral is equal to 1,8 MΩ.
  • Failure to follow these instructions can result in equipment damage.

Installation

Schneider-Electric-A9MEM152-Wireless-Communication-Energy-
Sensor-FIG-10

Connection

Schneider-Electric-A9MEM152-Wireless-Communication-Energy-Sensor-
FIG-11

Technical data

  • Nominal voltage Un: 230 V or 230/400 Va
  • Operating range (power supply and voltage measurement inputs): Un ± 20%
  • Frequency: 50/60 Hz
  • Maximum power consumption: y 1 VA (1P+N); y 2 VA (3P/3P+N)
  • Maximum current: 63 A
  • Operating temperature: -25°C to +60°C
  • Overvoltage and measurement category: Cat. III 300V / t
  • Supports temporary surges relative to the ground
  • Pollution degree: 3
  • Altitude: y 2000 m
  • Relative humidity: Maximum 93 % without condensation
  • Impact resistance index: IK05
  • For indoor use only
  • Radio communication: ISM band 2.4 GHz (2.4 GHz to 2.4835 GHz) v Channels 11 to 26 (IEEE 802.15.4)
  • Equivalent Isotropic Radiated Power (EIRP): 0 dBm
  • Accuracy:
  • Voltage: Class 0.5
  • Current, Power, and Active Energy: Class 1
  • Hereby, Schneider Electric Industries, declares that the wireless communication energy sensors PowerTag are in compliance with the essential requirements and other relevant provisions of RED-DIRECTIVE 2014/53/EU n°FD16090201. Declaration of conformity can be downloaded on: Schneider-electric.com/docs.
  • Schneider Electric Industries SAS
  • 35, rue Joseph Monier
  • CS 30323
  • F – 92506 Rueil Malmaison Cedex
  • www.schneider-electric.com
  • EAV31628-08
  • © 2018 Schneider Electric – All rights reserved.

Documents / Resources

| Schneider Electric A9MEM152 Wireless Communication Energy Sensor [pdf] Instructions
A9MEM152, PowerTag Acti9 M63, A9MEM152 PowerTag Acti9 M63, Acti9 M63, A9MEM154, A9MEM152 Wireless Communication Energy Sensor, Wireless Communication Energy Sensor, Communication Energy Sensor, Energy Sensor
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals