VENTS TT 100 Centrifugal Inline Fan User Manual

June 4, 2024
VENTS

CENTRIFUGAL INLINE FAN
USER’S MANUAL

This user’s manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about the purpose, technical details, operating principle, design, and installation of the TT unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
This appliance can be used by children aged 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning the use of the appliance in a safe way and understand the hazards involved Cleaning and user maintenance shall not be made by children without supervision
Children shall not play with the appliance.
Connection to the mains must be made through a disconnecting device, which is integrated into the fixed wiring system in accordance with the wiring rules for the design of electrical units and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a safety hazard.
If the cord set is damaged, it must be replaced by a special cord set available from the manufacturer or its service agent.
CAUTION: In order to avoid a safety hazard due to inadvertent resetting of the thermal cut-out, this unit must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility.
Ensure that the unit is switched off from the supply mains before removing the guard.
Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.
All operations described in this manual must be performed by qualified personnel only, properly trained and qualified to install, make electrical connections, and maintain ventilation units. Do not attempt to install the product, connect it to the mains, or perform maintenance yourself.
This is unsafe and impossible without special knowledge. Disconnect the power supply prior to any operations with the unit. All user’s manual requirements, as well as the provisions of all the applicable local and national construction, electrical, and technical
norms and standards, must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to 1000 V are allowed for installation. The present user’s manual should be carefully read before beginning work.
Check the unit for any visible damage to the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades. While mounting the unit, avoid compression of the casing!
Deformation of the casing may result in motor jams and excessive noise.
Misuse of the unit and any unauthorized modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.). Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure efficient airflow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the document’s preparation.
The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
THE PRODUCT MUST BE DISPOSED OF SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE OF THE UNIT AS UNSORTED DOMESTIC WASTE.

DELIVERY SET

Fan
Screws and dowels
Plastic screwdriver (all fans with a timer)
User’s manual
Packing box| 1 pc.
4 pcs.
1 pc.
1 pc.
1 pc.
---|---

BRIEF DESCRIPTION

The unit described herein is an axial mixed-flow fan for supply or exhaust ventilation of premises.
The fans for 100, 125, 150, and 160 mm air ducts have a two-speed motor and the fans for 250 and 315 mm have a single-speed motor.
The units for 100, 125, 150, and 160 air ducts are equipped with a two-speed motor, for 250 and 315 air ducts – with a single-speed motor.

| 0D| B| H| L
---|---|---|---|---
TT 100| 96| 167| 190/221| 246
TT 125| 123| 167| 190/221
| 246
TT 125 S| 123| 223| 250/279| 295
TT 150| 146| 223| 250/279
| 295
TT 160| 158| 233| 250/279| 295
TT 250| 247| 287| 323/340
| 383
TT 315| 310| 362| 408/424*| 445

*TT XXX U/Un/U1/U1n/U2/U2n/P

OPERATION GUIDELINES

The fan is rated for connection to single-phase AC 220-240 V/50 Hz or 220 V/60 Hz power mains.
The unit is rated for continuous operation.
The arrow on the fan casing must match the air direction in the system.
Ingress protection rating against access to hazardous parts and water ingress is IPX4.
The unit is rated as a Class II electrical appliance.
The fan is rated for operation at the ambient air temperature from +1 °C up to +40 °C.

Power supply [V/Hz] Transported air temperature [°C]
220-240/50 -25…+40 (TT 100/125)

-25…+60 (TT 125S/150/160/250/315)
220/60| -25…+40

To comply with the ErP 2018 regulation, a local demand controller and speed controller must be used.

DESIGNATION KEY

VENTS TT 100 Centrifugal Inline Fan - DESIGNATION KEY

MOUNTING

The fan is designed for horizontal or vertical installation on the floor, on the wall or on the ceiling (Fig. 1). The fan can be installed independently or as part of a set with a parallel or in-series connection (Fig. 2).
To be installed on the intake spigot side:

  • 1 m long air duct in case of horizontal fan installation
  • ventilation hood in case of vertical fan installation

The exhaust spigot must always be connected to the air duct.
The fan mounting steps are shown in Fig. 3–10 and 13-18.
The wiring diagrams are shown in Fig. 11-12.
Terminal designations:
L1: minimum speed terminal
L2: maximum speed terminal
QF: automatic circuit breaker
S: external speed switch
ST: external switch (for example, light switch)
X: input terminal block

CONTROL LOGIC

It is possible to control the fan rotation speed without options by voltage, as well as by thyristor controllers. The speed controller is purchased separately.
Warning!
When adjusting the voltage, make sure there is no unusual noise or vibration at reduced motor speed.
The motor current may exceed the rated current during voltage regulation.
The fan is equipped with a thermal switch with no self-reset.
To reset the thermal relay, switch off the power supply.
Find and eliminate the cause of overheating.
Make sure the motor has cooled down to operating temperature.
Switch on the power supply.
Caution!
The thermal switch of the TT 100 and TT 125 models cannot be reset. In case of overheating, replace the fan.
The TT 100/125/150/160 (R)V fans are equipped with a speed switch (Fig. 20).
The TT XXX T fan starts running after the external switch supplies a control signal to the LT input terminal (for example, during turning the light on).
After removal of the control signal the fan continues to run within the set time (adjustable with the turn-off delay timer from 2 to 30 minutes).
To adjust the fan turn-off delay time, rotate the control knob T clockwise to increase and counter-clockwise to decrease the turn-off delay time respectively (Fig. 19).
Warning! The timer circuit is under mains voltage. Disconnect the fan from the power supply prior to any adjustment operations. The fan delivery set includes a specially designed plastic screwdriver for adjustment of the fan parameters. Use exclusively the delivered plastic screwdriver to adjust the turn-off delay time. Do not use a metal screwdriver, knife, etc. for adjustment operations not to damage the circuit board.
The TT XXX U/U1/U2(n ) fan is equipped with an electronic TSC control unit (speed controller with electronic thermostat) for automatic speed control (airflow control) depending on the air temperature (Fig. 21).
The terminal box cover incorporates 2 control knobs:

  • for setting the fan speed;
  • for setting the thermostat set point.

The thermostat LED light is located on the fan casing.
The thermostat LED glows as air temperature exceeds the set point.
To set the thermostat set point rotate the temperature control knob clockwise to increase or counter-clockwise to decrease the temperature set point accordingly.
To set the fan speed (airflow) rotate the speed control knob in the same way.
The fan functioning logic may be based on temperature or timer controls:
TT ХХХ U (n): the fan switches to the maximum speed as the room air temperature exceeds the set point. As the air temperature drops down 2 °C below the temperature set point or if the initial temperature is below the set point, the fan operates with the set speed.
TT XXX U1 (n): the fan switches to the maximum speed as the room air temperature exceeds the set point. As the room air temperature drops down below the temperature set point, the timer starts 5 minutes countdown and then the fan switches to the set speed.
TT XXX U2 (n): As the indoor air temperature exceeds the set point, the fan switches to the maximum speed. As the air temperature drops 2 °C below the set point or if the initial temperature is below the set point, the fan is turned off.
The TT ХХХ P fan is equipped with a speed controller that enables switching the fan on/off, and smooth speed (airflow) control from minimum to the maximum value (Fig. 22).

MAINTENANCE

Clean the fan surfaces of dirt and dust each 6 months (Fig. 23–29).
Disconnect the fan from the power supply prior to any maintenance operations.
For cleaning the fan use a soft cloth or a brush wetted in a mild detergent solution.
Avoid water dripping on the electric components (Fig. 28)!
Wipe the fan surfaces dry after cleaning.

TROUBLESHOOTING

Problem Possible reasons Troubleshooting

When the unit is connected to power mains, the fan does not rotate and does not respond to any controls.| No power supply.| Make sure the power supply line is connected correctly, otherwise troubleshoot the connection error.
Internal connection fault.| Contact the Seller.
Low airflow.| The ventilation system is clogged.| Clean the ventilation system.
 Increased noise, and vibration.| The impeller is clogged.| Clean the impeller.
The fan is not secured well or is not mounted properly.| Troubleshoot the installation error.
The ventilation system is clogged.| Clean the ventilation system.

STORAGE AND TRANSPORTATION REGULATIONS

  • Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with a temperature range from +5 °C to +40 °C and relative humidity up to 70%.
  • Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
  • Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
  • Follow the handling requirements applicable for the particular type of cargo.
  • The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
  • Avoid sharp blows, scratches, or rough handling during loading and unloading.
  • Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.

MANUFACTURER’S WARRANTY

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of the Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following a test carried out on samples of the product referred to above. The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to the elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of the such unit component.
The warranty repair does not include:

  • routine technical maintenance
  • unit installation/dismantling
  • unit setup

To benefit from a warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:

  • User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
  • Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
  • User’s failure to ensure timely technical maintenance of the unit.
  • External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
  • Redesign or engineering changes to the unit.
  • Replacement and use of any assemblies, parts and components not approved by the manufacturer.
  • Unit misuse.
  • Violation of the unit installation regulations by the user.
  • Violation of the unit control regulations by the user.
  • Unit connection to power mains with a voltage different from the one stated in the user’s manual.
  • Unit breakdown due to voltage surges in power mains.
  • Discretionary repair of the unit by the user.
  • Unit repair by any persons without the manufacturer’s authorization.
  • Expiration of the unit warranty period.
  • Violation of the unit transportation regulations by the user.
  • Violation of the unit storage regulations by the user.
  • Wrongful actions against the unit were committed by third parties.
  • Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
  • Missing seals if provided by the user’s manual.
  • Failure to submit the user’s manual with the unit purchase date stamp.
  • Missing payment paperwork certifying the unit purchase.

FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE- FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT, AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP.

VENTS TT 100 Centrifugal Inline Fan - fig| VENTS
TT 100 Centrifugal Inline Fan - fig1
---|---
VENTS TT 100 Centrifugal Inline Fan - fig2| VENTS
TT 100 Centrifugal Inline Fan - fig3
VENTS TT 100 Centrifugal Inline Fan - fig4| VENTS
TT 100 Centrifugal Inline Fan - fig5
VENTS TT 100 Centrifugal Inline Fan - fig6| VENTS
TT 100 Centrifugal Inline Fan - fig7
VENTS TT 100 Centrifugal Inline Fan - fig8| VENTS
TT 100 Centrifugal Inline Fan - fig9

VENTS TT 100 Centrifugal Inline Fan - fig10

Certificate of Acceptance
The fan is recognized as serviceable.
www.ventilation-system.com
V10EN-12

Documents / Resources